Ensbury LT 70 - 580
We reserve the right to make changes to dimensions and construction
18
edition 12.2020
Hamworthy Heating Limited – Dorset BH17 ONF
6.6. Turbulators
Thanks to the turbulators, which are to be inserted in the smoke tubes, the combustion gas temperature can be
controlled.
All smoke tubes in the third pass must equally be provided with turbulators. These smoke tubes are those that
are open on the rear part, in the direction of the combustion gas collector. Also, read and follow the instructions
in the assembly guide.
L
Da
0007AX
Ensbury LT
70
90 120 145 165 190
225 260 300 335 370 440 510 580
Number of turbulators
9
9
11
11
11
11
15
15
15
19
19
25
25
25
Outer diameter
Da
36
Edge diameter
d
6
Pitch
A
55
Length
L
400 600 600 800 600 800 800 400 600 600 800 400 600
1000
6.7. Boiler control panel and casing assembly
Please refer to the separate assembly guide enclosed with the supply.
Attention:
Mount the casing prior to connecting the unit to the flue!