2.2. Gas category
The DR-SG water heater has been factory-set to operate with
group H
natural gas (type G20) with a nominal supply pressure of 20 mbar.
See chapter 4.8 for how to change the gas, and use a qualified professional.
INFORMATION:
Any work on a sealed component will lead to loss of the guarantee.
Gas category
Dorchester DR-SG XX-210 (20 to 30kW)
II2H3P
Dorchester DR-SG XX-356 (35 to 60kW)
II2H3P
Dorchester DR-SG XX-538 (70 to 120kW)
II2H3P
2.3. Gas supply pressures
INFORMATION:
The pressures provided below must be taken at the inlet to the gas
valve.
Natural gas
H G20
Propane
gas G31
Nominal pressure (mbar)
20
37
Minimum pressure (mbar)
17
25
Maximum pressure (mbar)
25
45