Main Protective Grounding
W hen grounding the rack syste m or enclosu re it is essen tial
that the mai n protective ground is connected and se cured
first with its own nut before any bonding connections are
ma de on top. (Figure 2)
Bonding Connections
Centre Section: Attach bonding wire found in ground kit to a
centre se ction bonding s tud, closes t to the hinged sid e of the
enclosu re, usin g the ring termin al and hardware provided.
Attach opposit e end of wire to the nearest PET on the rear
sec tion.
Door: Attach bonding wire to the door stud using the sa me
me thod desc ribed above. Attach the opposit e end to the
nearest centre se ction bonding stud.
Bonding Connection
Protective Earth Ground
Figure 2
2
Centre Section
Bonding Studs
Rear Section PETs
Top View
Door Bonding Studs
3