1.2 General Specification Summary
PARAMETER
VALUE
Power Input
Voltage Range
80-160 VDC; 120 VDC nominal
Maximum Current
20 A
Typical Transient Current
+20A < 60ms; +10A < 120ms; -5A < 100ms
Typical Continuous Current
< 1A
Inputs and Outputs
Discrete Inputs
RUN
and
RESET
commands
ON Voltage:
12 – 32 VDC,
+24 VDC nominal @ 6.5 mA
OFF Voltage:
1.0 VDC, maximum
Discrete Outputs
FAULT
&
OVERTEMP
alarms
OFF Voltage:
32 VDC maximum @ 150 µA typical
Effective ON Resistance
1.1 k
Ώ
, nominal
@
≥
1.5 VDC:
Analog Input
DEMAND
command signal
Current: 4 to 20 mA; 25 mA Maximum
Voltage: 5 VDC Maximum
Internal Impedance: 200
Ώ
Analog Outputs
POSITION
&
MTR
CURRENT
feedback
Current: 4 to 20 mA
External Load Resistance: 300
Ώ
, Maximum
Maximum Common Mode Voltage
±200 VDC User I/O to 120 VDC Return (less serial interface)
Performance
All performance values are based on use with HFG2.0 in default configuration.
Any changes to HFG2.0 firmware settings to change stroke profile will alter
performance values.
Maximum Operating Pressure
500 psig
Proof Pressure
2000 psig
Minimum Controllable Flow (Natural Gas)
15 pph (configuration dependent)
Maximum Controllable Flow
30,000 pph (configuration dependent)
Step Response (10% to 90%)
100 ms
Flow Accuracy
±
5% of flow point, typical
Mean Time Before Unscheduled Removal
30,000 Hours
Life Cycles
32,000 Minimum
Environmental
Temperature, Operating Ambient:
-40
°
C (-40
°
F) to +93
°
C (+200
°
F)
Temperature, Operating Fuel:
-40
°
C (-40
°
F) to +125
°
C (+257
°
F)
Temperature, Storage
-40
°
C (-40
°
F) to +125
°
C (+257
°
F)
Environmental Rating
Rated to CSA Type 3 and European IP65
Sealed against dust, protected against water
EMC
Meets EN 50081-2 and EN50082-2 for DC powered industrial equipment
Vibration
Meets Mil-Std-810E, Category 4 (5 – 2000 Hz)
INSTALLING THE HFG2.0
3
Summary of Contents for Gas Fuel Metering Valve HFG2.0
Page 15: ...Figure 1 4 HFG2 0 Dimensions 1 Piece Housing INSTALLING THE HFG2 0 9...
Page 16: ...10 HFG2 0 USER GUIDE Figure 1 5 HFG2 0 Mounting Orientations...
Page 30: ...24 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 34: ...28 HFG2 0 USER GUIDE Figure 2 1 HFG2 0 Electronics System Block Diagram...
Page 40: ...34 HFG2 0 USER GUIDE Figure 2 2 HFG2 0 Cut Away View Actuator Main Housing Assembly...
Page 41: ...Figure 2 3 HFG2 0 Cut Away View Partial CH 2 UNDERSTANDING THE HFG2 0 35...
Page 43: ...Figure 2 5 Typical Refurbishment Plate CH 2 UNDERSTANDING THE HFG2 0 37...
Page 44: ...38 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 47: ...Figure 3 1 HFG2 0 Basic Operation Flow Chart CH 3 OPERATING THE HFG2 0 41...
Page 58: ...52 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 60: ...54 HFG2 0 USER GUIDE INTENTIONALLY BLANK...