20
HFG2.0
USER
GUIDE
Analog Inputs
The analog input, DEMAND, has a current range of 4 - 20 mA. It is
electrically isolated up to 500 VAC from the enclosure, 120 VDC power,
digital I/O, and serial interface. The analog interfaces are not isolated from
each other. See Figure 1-13 for a typical analog input connection.
HFG2.0
4-20mA INPUT
CONTROLLER 4-20 mA OUTPUT
+
-
DEMAND [BRN]
DEMAND RT N [WHT/BRN]
200
Ω
+
-
Figure 1-13. Typical Analog Input Connection
Analog Outputs
The analog outputs, MOTOR CURRENT and POSITION, have a current
range of 4 - 20 mA. They are electrically isolated up to 500 VAC from the
enclosure, 120 VDC power, digital I/O, and serial interface. The analog
interfaces are not isolated from each other. See Figure 1-14 for a typical
analog output connection.
CONTROL LER 4-20mA INPUT
HFG2.0 4-20mA OUTPUT
+
-
POSIT ION
[YEL]
MT R CURRENT
[BLU]
POSIT ION RT N
[W HT /YEL]
MT R CURRENT RT N [W HT /BLU]
<500
Ω
+
-
Figure 1-14. Typical Analog Output Connection
Discrete Inputs
The discrete inputs are 24 VDC ON (High) and 0 VDC OFF (Low). They
are electrically isolated up to 500 VAC. See Figure 1-15 for a typical
discrete input connection.
CONTROLLER DISCR ETE OUT PUT
HFG2.0 DISCRET E INPUT
RUN RTN
[WHT/VIO]
RESET RTN [WHTGRY]
RUN
[VIO]
RESET
[GRY]
Figure 1-15. Typical Discrete Input Command Connection
Summary of Contents for Gas Fuel Metering Valve HFG2.0
Page 15: ...Figure 1 4 HFG2 0 Dimensions 1 Piece Housing INSTALLING THE HFG2 0 9...
Page 16: ...10 HFG2 0 USER GUIDE Figure 1 5 HFG2 0 Mounting Orientations...
Page 30: ...24 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 34: ...28 HFG2 0 USER GUIDE Figure 2 1 HFG2 0 Electronics System Block Diagram...
Page 40: ...34 HFG2 0 USER GUIDE Figure 2 2 HFG2 0 Cut Away View Actuator Main Housing Assembly...
Page 41: ...Figure 2 3 HFG2 0 Cut Away View Partial CH 2 UNDERSTANDING THE HFG2 0 35...
Page 43: ...Figure 2 5 Typical Refurbishment Plate CH 2 UNDERSTANDING THE HFG2 0 37...
Page 44: ...38 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 47: ...Figure 3 1 HFG2 0 Basic Operation Flow Chart CH 3 OPERATING THE HFG2 0 41...
Page 58: ...52 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 60: ...54 HFG2 0 USER GUIDE INTENTIONALLY BLANK...