![Hamilton Sundstrand Company Gas Fuel Metering Valve HFG2.0 User Manual Download Page 50](http://html1.mh-extra.com/html/hamilton-sundstrand-company/gas-fuel-metering-valve-hfg2-0/gas-fuel-metering-valve-hfg2-0_user-manual_3425095050.webp)
44
HFG2.0
USER
GUIDE
A non-linear interpolation table can be created to define positioning at 16
discrete current levels in the DEMAND signal range, but only during Set
Up using the ActWiz Software. See the Section 3.8 for additional details
about Set Up parameters.
Figure 3-3. Dead Band of Actuator, Position vs. DEMAND Curve
3.6 Resetting the Actuator
To reset the HFG2.0, +24 VDC must be applied across the RESET wires
for at least 0.5 seconds. The leading edge of the RESET command
causes the HFG2.0 to stop all other operations, but the actual resetting of
the HFG2.0 does not begin until RESET is returned to its OFF state. The
RESET command causes the HFG2.0 to reset all internal position
indicators, reload all Set-Up parameters, and check the health of the
electronics. See the flow chart in Figure 3-1 for an illustration of this. The
HFG2.0 is now in the Power Up / Reset state.
Once the RUN command is detected as ON, the actuator will then move
through its initial homing sequence again. RUN and DEMAND inputs are
ignored during the RESET command.
If FAULT alarm is detected, toggling the RESET command will clear the
FAULT alarm, but it will NOT clear the fault file.
Summary of Contents for Gas Fuel Metering Valve HFG2.0
Page 15: ...Figure 1 4 HFG2 0 Dimensions 1 Piece Housing INSTALLING THE HFG2 0 9...
Page 16: ...10 HFG2 0 USER GUIDE Figure 1 5 HFG2 0 Mounting Orientations...
Page 30: ...24 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 34: ...28 HFG2 0 USER GUIDE Figure 2 1 HFG2 0 Electronics System Block Diagram...
Page 40: ...34 HFG2 0 USER GUIDE Figure 2 2 HFG2 0 Cut Away View Actuator Main Housing Assembly...
Page 41: ...Figure 2 3 HFG2 0 Cut Away View Partial CH 2 UNDERSTANDING THE HFG2 0 35...
Page 43: ...Figure 2 5 Typical Refurbishment Plate CH 2 UNDERSTANDING THE HFG2 0 37...
Page 44: ...38 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 47: ...Figure 3 1 HFG2 0 Basic Operation Flow Chart CH 3 OPERATING THE HFG2 0 41...
Page 58: ...52 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 60: ...54 HFG2 0 USER GUIDE INTENTIONALLY BLANK...