APPENDIX B: GLOSSARY
Term
Definition
RUN Command
A discrete 24 VDC signal that enables the HFG2.0 actuator and valve
to move.
RESET Command
A discrete 24 VDC signal that causes the HFG2.0 internal program
(firmware) to jump to the beginning.
Controller
A user-provided computer that executes commands to the HFG2.0
and accepts analog and discrete feedback.
Fuel Demand
A 4 mA to 20 mA signal that commands the HFG2.0 to move to a
certain actuator/valve position. The signal is scaled with SPAN.
Position Demand Feedback
A 4 mA to 20 mA signal that communicates the actual HFG2.0
actuator/valve position to the controller.
Motor Current Feedback
A 4 mA to 20 mA signal that is proportional to the HFG2.0 motor
current. The signal is scaled with Max. Force.
FAULT alarm
A discrete signal from the HFG2.0 that communicates an internal
failure. The user’s controller will see an open circuit when a FAULT
alarm is active.
OVERTEMP alarm
A discrete signal from the HFG2.0 that communicates an internal
over temperature; electronics or motor. The user’s controller will see
an open circuit when the OVERTEMP alarm is active.
HOME
A mechanical rigid stop from which the HFG2.0 calculates position.
HOME is found at start-up during the Homing sequence. The HFG2.0
defines HOME when the motor current exceeds the HOMING
FORCE and velocity is zero. HOME is defined as the actuator/valve
position when the Demand signal is 4 mA. HOME is the Valve Closed
condition for the HFG2.0
Homing sequence
When the HFG2.0 extends or retracts to find a rigid mechanical stop.
SPAN
Maximum distance from HOME. SPAN is defined as the position
when the Demand signal is 20 mA.
STOP position
A user-defined position between HOME and SPAN that the HFG2.0
travels to upon loss of RUN or position Demand signal.
Maximum Velocity
A user defined maximum velocity in inches per second.
Maximum Homing Force
A user defined maximum homing force output setting. The motor
control electronics uses this setting to determine the maximum motor
current in the Homing sequence.
Maximum Holding Force
A user-defined maximum force while in the Holding Motor Current
state.
APPENDIX C: GLOSSARY
63
Summary of Contents for Gas Fuel Metering Valve HFG2.0
Page 15: ...Figure 1 4 HFG2 0 Dimensions 1 Piece Housing INSTALLING THE HFG2 0 9...
Page 16: ...10 HFG2 0 USER GUIDE Figure 1 5 HFG2 0 Mounting Orientations...
Page 30: ...24 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 34: ...28 HFG2 0 USER GUIDE Figure 2 1 HFG2 0 Electronics System Block Diagram...
Page 40: ...34 HFG2 0 USER GUIDE Figure 2 2 HFG2 0 Cut Away View Actuator Main Housing Assembly...
Page 41: ...Figure 2 3 HFG2 0 Cut Away View Partial CH 2 UNDERSTANDING THE HFG2 0 35...
Page 43: ...Figure 2 5 Typical Refurbishment Plate CH 2 UNDERSTANDING THE HFG2 0 37...
Page 44: ...38 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 47: ...Figure 3 1 HFG2 0 Basic Operation Flow Chart CH 3 OPERATING THE HFG2 0 41...
Page 58: ...52 HFG2 0 USER GUIDE INTENTIONALLY BLANK...
Page 60: ...54 HFG2 0 USER GUIDE INTENTIONALLY BLANK...