CONFIGURATION #2

Configuration #2 – CASCADE WATER HEATERS

 

• In this configuration, an external sensor on terminals 1 & 2 (or 3 & 4, 28 & 29 depending on model) or an

 

  aquastat on terminals 5 & 6 (or 13 & 14, 57 & 58 depending on model) 

MUST

 be connected to the 

LEAD 

 

  HEATER ONLY

.

 

In this configuration the following can be done on the 

LEAD HEATER ONLY:

 

   1. Adjust the heater minimum and maximum temperature setting via the red wheel located on the display 

 

       panel, within the range of 50 – 159°F 

(Parameter 2 EA, 2 EB)

 

It is important to set the red potentiometer wheel to the desired setpoint on the Lag heaters with the power off to

  

the Lead heater. This way, in the event of a control or power failure to the Lead heater, the Lag heaters will

 

operate at the desired temperature.

 

Adjust offset, Hysterese (droop) and modulation range in Parameters 2IF – 2IM and 2CD – 2CF.

 

CDM

4/11/06

1/2"=1'

Dwg. By:

34000 Autry
Livonia, MI 48150

PH: (800) 968-5530
Fax: (734) 419-0209

Description:

Date:

Scale:

Customer:

HAMILTON

ENGINEERING

Dwg. 
No.:

Checked. 
By:

Cascading Water Heater

With External Tank Sensor

Pump 3

Storage

Tank

Pump 3

Pump 3

Lead

Lag 1

Lag 2

Required parameter changes

from base program

Default

Change to

Base Program - DXXXLCO.pia

All Lag Heaters - 2CA

5

2

All Lag Heaters - 2IA

0

1 - 7

Summary of Contents for EVO 129-599

Page 1: ...causing property damage personal injury or death WARNING New York Massachusetts SCAQMD CEC Listed MEA 425 05 E Boilers G1 06 06 24A Compliant Rule1146 2 California Energy Commission Heaters G1 06 06 2...

Page 2: ...Central Heating Only Single Boiler 8 CONFIGURATION 4 Central Heating Only Multiple Boiler Cascade 9 CONFIGURATION 5 Residential Heating w Pumped DHW Single Combi Boiler 10 CONFIGURATION 6 Central Hea...

Page 3: ...ng Boiler 5 minutes Pump P1 Domestic Hot Water heating zone pump 1 minute Pump P2 Diverting Valve Zone Transport Pump 5 minutes Pump P3 DISPLAY The 3 digit display will show different information duri...

Page 4: ...EV 06 2018 GENERAL DESCRIPTION That are represented by The following pages contain drawings that apply to all models of EVO products In addition most drawings reference a Low Loss Header which may als...

Page 5: ...wing can be done 1 Adjust the heater minimum and maximum temperature setting via the red wheel located on the display panel within the range of 50 159 F Parameter 2 EA 2 EB 2 An external on off tank t...

Page 6: ...range of 50 159 F Parameter 2 EA 2 EB It is important to set the red potentiometer wheel to the desired setpoint on the Lag heaters with the power off to the Lead heater This way in the event of a con...

Page 7: ...ermistor is connected to terminals 1 2 or 9 10 26 27 depending on model The control will automatically sense the presence of the sensor When an outside temperature sensor is connected the flow tempera...

Page 8: ...195 F Parameter 2 EB 2 EA 2 Outdoor temperature reset can be enabled by connecting a 10k ohm sensor to terminals 1 2 or 9 10 26 27 depending on model this will be automatically sensed by the FMT 914...

Page 9: ...be controlled based on the Room Thermostat must add heating harness WRE74090 and wire to P3 leads Caution maximum available wattage for external load on the FMT 914 control board is 550 watts If pumps...

Page 10: ...ry heating loop In this configuration the following can be done 1 Adjust the boiler minimum and maximum temperature setting via the potentiometer located on the display panel within the range of 50 19...

Page 11: ...nfiguration the following can be done 1 Adjust the boiler minimum and maximum temperature setting via the potentiometer located on the display panel within the range of 50 192 F Parameter 2 EB 2 EA 2...

Page 12: ...entiometer located on the display panel within the range of 50 192 F Parameter 2 EB 2 EA 2 Set boiler water temperature to the DHW tank Factory default is 185 Parameter 2 CE 3 Set the DHW water temper...

Page 13: ...ting valve is to be connected to the harness leads labeled 3 way Open 3 way Close and 3 way L In this configuration the following can be done 1 Adjust the boiler minimum and maximum temperature settin...

Page 14: ...maximum temperature setting via the potentiometer located on the display panel within the range of 95 195 F Parameter 2 EB 2 EA 2 Set the flow temperature to the DHW tank Factory default is 185 F Par...

Page 15: ...15 34000 Autry Street Livonia MI 48150 800 968 5530 Fax 734 419 0209 www hamiltonengineering com LIT91110 REV 06 2018 HWD 129 199 8 STANDARD WIRING...

Page 16: ...1 1 2 K6 K2 K2 K10 K6 On Off Switch 4 3 2 1 K6 K10 K2 Printed Circuit Board FMT914 K6 K2 K10 K1 K0 K10 K6 K2 K2 K2 K2 K2 K5 K5 K3 K3 K6 K10 K2 K7 K8 K6 K10 K6 K2 K10 K6 K2 K6 K2 K6 K6 3 15 Amp Pressu...

Page 17: ...17 34000 Autry Street Livonia MI 48150 800 968 5530 Fax 734 419 0209 www hamiltonengineering com LIT91110 REV 06 2018 HWH 129 199 8 W 3 WAY...

Page 18: ...ow white blue white red white black white K10 K12 K17 K18 K19 K5 K6 K7 K8 K9 orange blue red black purple white yellow brown green gray K0 K1 K2 K3 K4 K6 K6 K2 K6 K2 K6 K10 K2 K6 K10 K6 K8 K7 K2 K10 K...

Page 19: ...X 4 X 2 X 1 Gas valve 1 Power Supply Cascade Connection 15 3 16 17 20 19 18 4 2 1 4 3 2 1 X 3 K2 K6 K10 K10 K6 K2 6 5 Thermostat Central Heat Room K1 K1 K4 K4 0 10 VDC 7 8 10 9 Sensor Outside K8 K8 1...

Page 20: ...Fuse X 10 X 9 X 8 X5 X 4 X 2 X 1 Gas valve 1 Power Supply Cascade Connection 15 3 16 17 20 19 18 4 2 1 4 3 2 1 X 3 K2 K6 K10 K10 K6 K2 6 5 Thermostat Central Heat Room K1 K1 K4 K4 0 10 VDC 7 8 10 9 S...

Page 21: ...ndirect OPEN THERM PCB BURNER L1 24 ST 3 8 7 Thermostat Remote Additional Heat Source Dry Contact Dry Contact Signal Lock Out External L2 K2 Pressure switch Open switch indicates as H 1 High limit the...

Reviews: