A 120 volt circuit from the control panel to the make up air fan starter coil or relay. 
There is a 2 wire circuit to the fire suppression micro switch for a dry contact closure to let the control panel know of 
a fire condition under the hood. 
There may be additional wiring circuits for fire alarm notification to a building BMS.  This is optional. 
 

Note:

  The selector switch on the control panel controls the exhaust fan operation. 

 
Please see job specific wiring connection information in the job submittal drawings and an additional wiring diagram is 
included in the electrical control box shipped with the job.  Additional copies may be obtained from the factory if this 
wiring diagram is missing or lost.   Please be prepared to provide the job order number (found on the sales invoice), 
job name and address or submittal drawing series number when contacting the factory for this or other job specific 
documents. 

7.  Plumbing service requirements:   

 
1.  Hot water supply to the control panel must be sized to accept appropriate volume of water measured in U.S. 
gallons per minute at 40 psig/min. at a constant flow pressure of 25 psig at the hot water nozzles in the hood.  Supply 
the recommended hot water temperature of 120˚F (50˚C) to 140˚F (60˚C).  Calculate water requirements by using 
the longest water wash hood served by the control panel and multiplying the length of this hood, in feet, by 1.2.  The 
result will be the figure used for gallons per minute.  Example: The longest hood connected to the control panel is 
168” long.  168/12 = 14 feet, 14 X 1.2 = 16.8 gallons per minute. 
 
2.  Supply and connect 1” ips for hot water to control panel, provide and connect 1” lines to ventilator sections.  
Supply and connect drains as specified from ventilator section(s) to floor drain as required by local codes.  Waste 
drain is 2” pipe.  Do not use 90˚ elbows in drain line.  If 90˚ bend is required use two 45˚ fittings.  If traps are required 
in drain line install it in the vertical section of the line.  Supply and install grease traps as required by local codes, 
sized to handle maximum volume as calculated above.  Supply and install back flow preventers, anti-syphon valves or 
vacuum breakers as required by local codes.  Di-electric connections, where required by code on water supply feed 
to panel, are to be supplied by mechanical trade.  Internal piping in control panel is brass.  Hot water lines should be 
thoroughly flushed prior to connecting lines to control panel.  Remove one of the spray nozzles farthest from water 
intake to flush lines, replace nozzle when flushing is completed.  Inlet and drain line attachment points at the hood 
are illustrated on pg. 5. 

8.  Halton hoods come standard with high output, long lasting LED light fixtures.  Optionally incandescent or recessed 

fluorescent fixtures may be ordered.  Please note only install 100 watt maximum light bulbs in incandescent light 
fixtures.  Fluorescent bulbs should be type T8, 36” or 48” long in fluorescent fixtures. **Note: Halton does not 
provide bulbs for incandescent or fluorescent lights. 

9.  For multiple hoods end to end, or back to back see pg. 9 for Installation of Splice Strips and U-Channels. 

10.  If Closure Panels are supplied by Halton see pgs. 10 - 12 for details on the installation. 

11.  Protect the hood from damage under normal job site conditions, until all work is complete and system is ready to be 

put into operation.

Summary of Contents for Capture Jet KVC-WW

Page 1: ...pture Jet Hoods with Water WashTechnology Manual provides Operation Maintenance and Service Instructions Form OM006_CAPTURE JET WITH WATER WASH Date 07 11 2016 Rev2 Capture Jet Hoods with Water WashTe...

Page 2: ...ance Manual In addition to this information technical support is available from the Halton Factory during regular office hours 7 A M to 5 P M Central Time to provide support for products applications...

Page 3: ...backsplash assembly then the splash assembly should be installed first for installation procedures see pg 6 4 Hang the hood using threaded rods by attaching the rods to the hood through the hanger br...

Page 4: ...X 1 2 16 8 gallons per minute 2 Supply and connect 1 ips for hot water to control panel provide and connect 1 lines to ventilator sections Supply and connect drains as specified from ventilator secti...

Page 5: ...5 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN Water Inlet point on back of hood Water Drain point on hood...

Page 6: ...016 rev2 EN BACKSPLASH INSTALLATION Screw through top flange into wall Screw head will not interfere with hood Screw backsplash to wall or attached with adhesive Halton canopy hoods should be installe...

Page 7: ...7 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN HOOD INSTALLATION DETAILS...

Page 8: ...8 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN EXHAUST DUCT CONNECTION DETAILS...

Page 9: ...9 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN SPLICE STRIP U CHANNEL ASSEMBLIES...

Page 10: ...10 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN CLOSURE PANEL ASSEMBLY...

Page 11: ...11 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...

Page 12: ...12 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...

Page 13: ...them clean The cap should be removed for taking the static pressure measurements and then replaced when the measurements are completed The exhaust static pressure is measured using the negative conne...

Page 14: ...the removal and replacement process 3 Exhaust airflows should be properly set for each exhaust hood and supply or make up air should be brought into the space to balance the exhaust air leaving the s...

Page 15: ...tion Maintenance Manual OM 006 112016 rev2 EN CROSS SECTION OF CAPTURE JET WATER WASH HOOD Item Description A Water Wash Intake Supply B Water Wash Nozzle Manifolds C Multi cyclone KSA extractor D Dra...

Page 16: ...arsh or abrasive cleaners on Stainless Steel or Painted surfaces making sure to wipe clean all interior and exterior surfaces of the hood including the light fixtures Never clean the hood canopy when...

Page 17: ...the nozzles in the wash manifold that washes the inside of the KSA grease filter The B5 nozzles have an inlet connection size of 1 8 orifice diameter 0 031 The balance of the nozzles which wash the in...

Page 18: ...Wash Operation Maintenance Manual OM 006 112016 rev2 EN Control Panel Operation The Water Wash control panel is designed to operate only under safe conditions and warn when there are fan failures or o...

Page 19: ...19 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...

Page 20: ...cator will change text from Fan OFF to Fan ON When the exhaust fan is on pressing on the left of the virtual rocker switch will turn the exhaust fan off At the bottom of the screen is a red light that...

Page 21: ...sired wash cycle start time using the 24 hour format for the days of the week selected The Use End Time should be set 15 seconds later than the Start Time This second setting Use End Time ensures the...

Page 22: ...xhaust fan is turned off before the first wash cycle starts All wash cycles will complete one after the other until all hoods and or duct sumps have been washed The wash and rinse times are entered in...

Page 23: ...ack font the alarm is an active alarm The remaining alarm history will be in green font Active alarms require action by an authorized service technician Detergent Prime Pump Screen Press and hold the...

Page 24: ...n Maintenance Manual OM 006 112016 rev2 EN Menu Options button Pressing the Menu Options button at the bottom left of the screen will bring up a quick access screen overlay that allows the user to sel...

Page 25: ...r Wash Operation Maintenance Manual OM 006 112016 rev2 EN Water Wash User Guide The Water Wash User Guide button will take you through depictions of all of the screens with explanations of the functio...

Page 26: ...26 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN...

Page 27: ...Wash Operation Maintenance Manual OM 006 112016 rev2 EN Electrical Wiring Connections Two electrical wiring diagrams are shown below 1 Control Panel electrical wiring diagram 2 Field wiring diagram CO...

Page 28: ...28 Capture Jet with Water Wash Operation Maintenance Manual OM 006 112016 rev2 EN FIELD WIRING DIAGRAM...

Page 29: ...p Date Product Serial Numbers Contact Information Contact Name Title Chef Kitchen Mgr Facility Mgr Property Mgr etc Facility Management Company Name if applicable Email Phone Number Cell Number Fax co...

Page 30: ...ied third party No claims for labor charges will be approved for payment if work commences without prior authorization by Halton Purchaser shall pay incurred premium labor charge including overtime we...

Reviews: