Maximum loading of IS circuit 

Because of the finite resistance of the safety barrier, there will be a limit to the current drain which can be 
tolerated before the voltages on the circuit fall outside the specified limits for Orbis I.S. devices. The system 
certification allows up to 20 Orbis IS detectors to be connected to a single barrier circuit with an end-of-line 

resistor of not less than 1.8kΩ. However, it must be ensured that the voltage available at each detector is 

above the minimum specified in the quiescent condition. It is also important to ensure that the alarm load 
is suitable for the control and indicating equipment. The system certification also allows the use of remote 
LED indicators. These may be connected to individual detectors or may use a connection common to two or 
more detectors as shown in Figure 6. 

13

 

Installation 

It is important that the Orbis I.S. detectors be installed in such a way that all terminals and connections are 
protected to at least IP20 when the detector is in the base. Special care must be taken with the rear of the 
mounting base where live metal parts may be accessible. Flush mounting of the base on a flat surface will 
provide the required degree of protection. 

A conduit, Item No 201-0192 (part No 45681-204), is also acceptable for mounting I.S. bases together with 
a range of deckhead mounting boxes. For more information, please refer the Ampac eCatalogue. 

Note that the earth terminal in the base is provided for convenience where continuity of a cable sheath or 
similar  is  required.  It  is  not  necessary  for  the  correct  operation  of  the  detector  nor  is  it  provided  as  a 
termination point for a safety earth. 

14

 

Remote LED connection 

A  drive  point  is  provided  on  each  of  the  Orbis  I.S.  detectors  for  a  remote  LED  indicator.  For  connection 
details see Figure 5. The indicator must be a standard high-efficiency 

red 

LED and does not require a series 

limiting resistor since current is limited by the detectors. 

The system certification allows for the use of any LED indicator having a surface area between 20mm

and 

10cm2  which  covers  all  commonly  used  case  styles  from  T1  (3mm)  upwards  but  would  exclude  some 
miniature and surface mounted types. Additional requirements of the certification are that the LED and its 
terminations must be afforded a degree of protection of at least IP20 and must be segregated from other 
circuits  and  conductors  as  defined  in  BS  EN  60079-  14:2003.  The  MiniDisc  Remote  Indicator,  part  No  
(53832-070) may be used with Orbis IS detectors. 

15

 

MiniDisc Remote Indicator 

The MiniDisc remote indicator is only 20mm high and 80mm in diameter. It comprises two parts, the base 
which is installed onto a wall or soffit and the lid which is fitted to the base with a bayonet fitting. An anti-
tamper screw in the lid locks the unit together.  

Two pairs of keyholes  are  provided

one  for  50mm and the other  for 60mm fixing centres.  The MiniDisc 

Remote Indicator is polarity sensitive. Connect positive line to Terminal B and negative line to Terminal C. 

 

 

Summary of Contents for Ampac Orbis IS ORB-OP-52027-APO

Page 1: ...Fire detection and evacuation solutions that save lives Orbis IS Product Guide MAN3041 1...

Page 2: ...nviornmental Performance 11 6 4 Technical Data 12 7 Orbis IS Heat Detector 13 7 1 Where to use heat detectors 13 7 2 Choosing the correct class of heat detector 13 7 3 How does Orbis IS heat detectors...

Page 3: ...detectors which has been developed from the standard range of Orbis smoke and heat detectors Orbis IS is a range with modern styling and a TimeSaver IS base It is electrically compatible with Series 6...

Page 4: ...uipment Regulations 1999 Detectors have been declared as being compliant with the essential requirements of the EMC Directive 98 336 EEC the Construction Products Directive 89 106 EEC and the ATEX Dir...

Page 5: ...tion and cable termination Wide operating temperature range StartUp for fast commissioning DustDefy housing which limits ingress of dirt into detector New optical sensor for high reliability reduced f...

Page 6: ...of optical detectors in the standard test fires described in the European standard EN54 7 2000 The results of these tests are given in Figure 1 The graph shows the acceptable response in terms of smok...

Page 7: ...een Orbis Optical Multisensor How are heat detectors classified EN54 5 2000 classifies heat detectors according to the ambient temperature in which they will be working An additional classification ma...

Page 8: ...MAN3041 1 8 So what is the best way to choose a heat detector To make things easier we have produced a flow chart to help you decide Figure 3 Choosing a Heat Detector...

Page 9: ...ensation for slow changes in sensitivity Extra confirmation of smoke before alarm signal given The algorithms are used to verify signals from the sensing chamber to filter out transients and to decide...

Page 10: ...20 seconds Minimum detector active voltage 12V dc Switch on surge current 105 A at 24V dc Quiescent current 85 A at 24V dc Alarm load 325 in series with 1 0V drop Material Detector and base moulded i...

Page 11: ...reas where the fire risk is likely to include heat at an early stage in the development of the fire As with Orbis IS optical smoke detectors the increased reliability of detection is combined with hig...

Page 12: ...A at 24V dc Alarm load 325 in series with 1 0V drop Material Detector and base moulded in white polycarbonate Alarm Indicator Integral indicator with 360 visibility Dimensions and weight of detector...

Page 13: ...er possible since smoke detection provides earlier warning of fire than heat detection There are however limits to the application of smoke detectors and these are described in the section 4 Choosing...

Page 14: ...midity unless specified otherwise Detector operating principle Measurement of heat by means of a thermistor Sampling frequency Once every 2 seconds Supply voltage 14 28V dc Supply wiring 2 wires polar...

Page 15: ...re positive IN positive OUT negative IN and OUT common terminal remote LED negative connection functional earth screen The terminal screws are captive screws and will not fall out of the terminals The...

Page 16: ...ovided It is not necessary for the correct operation of the detector nor is it provided as a termination point for a safety earth If screened cable is used screen continuity should be maintained and t...

Page 17: ...ts for 4 minutes so it may be necessary to reset or de power the circuit to allow all detectors to be observed The LED status is the same as method 1 above 8 3 Orbis LED Status Indication Feature Desc...

Page 18: ...ng passive devices they also impose the minimum of restrictions on the operation of the fire detectors Thus single channel barriers are available either as positive or negative polarity where the pola...

Page 19: ...max out 93 3mA W max out 0 67W In any safety barrier used the output current must be limited by a resistor R such that I max out Uz R A number of shunt zener diode barriers meet this specification and...

Page 20: ...The connection must be such that the impedance from the connection point to the main power system earth is less than one ohm Intrinsically safe circuits in the hazardous area should be insulated from...

Page 21: ...ulate the total capacitance or inductance for the length of cables in the hazardous area refer to Table 5 which gives typical per kilometre capacitance and inductance for commonly used cables Note All...

Page 22: ...at segregation be provided between the IS and non IS circuits A distance of at least 50mm must be preserved between live conducting parts of IS and other circuits If the enclosure is used as part of a...

Page 23: ...eCatalogue Note that the earth terminal in the base is provided for convenience where continuity of a cable sheath or similar is required It is not necessary for the correct operation of the detector...

Page 24: ...should be carried out as recommended by the code of practice BS 5839 Part 1 or other local regulations in force 17Achnowledgement All Orbis IS detectors and products are manufactured for Ampac by Apo...

Page 25: ...MAN3041 1 25 AMPAC TECHNOLOGIES UNCONTROLLED DOCUMENT NOTE Due to AMPAC s commitment to continuous improvement specifications may change without notice...

Reviews: