MAN2285-9
Page 36
Versions higher than V2.1
Remote isolate is input 3
Remote reset is input 1
No further action is required by the FireFinder programmer as the software automatically assigns these outputs
in the application software.
When an APIC is connected to a FireFinder and the classifier override is required then the remote day night box
must be ticked and the number 5 placed in the corresponding box. In addition to this the classifier override
percentage must be set to 101 or greater. This sets the percentage that is added to the detector when it is
required to de-sensitise the detector.
The Classifier Override feature must be programmed into the FireFinder using a function in order for this
feature to work.
Reporting to FireFinder.
Fastsense
Plus will report the following to
FireFinder
.
Status
Count
Fault
4
Normal
16
Aux alarm
32
Pre-Alarm
48
Fire 1
64
Fire 2
127
Bit
Use
Flow/separator fault 1
1
Mains/battery fault
2
Detector Isolated
3
The three output bits from the fire panel are monitored as inputs 1 to 3 or 4 to 6 depending upon the detector
type as follows:
It is possible to reset, isolate and activate
Classifire
Override (Remote Day / Night settings in ConfigManager)
on the
Fastsense
Plus from the
FireFinder