FastSense25
specification
SELV rating (EN 60950)
Class III or AS/NZ S3260:93
Supply Voltage
21.6V - 26.4V DC
PSU Type: conforming to EN 54-4
AS4428 Part 5 or NZ4512 Electrical
safety complies with BS EN 610190-1
Size (mm)
140W x 215H x 85D
Weight
1.7kg with docking station
Operating temperature range
-10 to +60°C
Operating humidity range
0 - 90% Non Condensing
BS EN 61010-1 Pollution degree 1
BS EN 61010-1 Installation Cat. II
Sensitivity range (%Obs/m)
Min = 25% Max = 0.03% FSD
Maximum sensitivity resolution
0.0015 % obs/m
Detection principle
Laser light scattering mass detection
Particle sensitivity range
0.0003µm to 10µm
Current consumption
250mA
Relay contact rating
500mA @ 30V
Maximum sampling pipe length
60 metres total
Sampling pipe inlets
1
Sampling pipe internal diameter
15-25mm
Alarm levels
4 (Fire 2, Fire 1, Pre-Alarm and Aux)
1 relay as standard, others available
Chamber service intervals
Greater than 8 years (depending on
environment)
Dust separator replacement intervals
Greater than 5 years (depending on
environment)
Laser lifetime (MTTF)
Greater than 1000 years
Programming
PC via RS232/RS485
Data bus cable
RS485 data cable
Data bus length
1.2 km
IP rating
IP50
Note:
This
equipment is only to be used in accordance with this specification. Failure to operate the
equipment as specified may cause damage to the unit.