16
MiniCAFS 2.1A Operating Manual
GP/211/05 Issue 2. April 2005
©Hale Products Europe. Our policy is one of continuous development. We therefore
reserve the right to amend specifications without notice or obligation.
”no Pr” = No prime display
7.
When prime is achieved, deselect simulated flow by pressing both up
↑
& down
↓
at the
same time.
8.
Return the bypass valve to the inject position (arrow points to right).
The unit is now ready to run.
OPERATING MiniCAFS FROM A VEHICLE WATER SOURCE
1. Connect a suitable delivery hose and branch to the CAFS discharge.
φ
38 to
φ
45mm
diameter layflat hose is suitable for delivering compressed air foam. If a single discharge
is being used, a
φ
25 to
φ
38mm smooth bore nozzle would be suitable. If two delivery
hoses were to be deployed, then two
φ
19 nozzles would be appropriate.
Note
: The best foam quality is produced using a smooth bore nozzle with the foam going
through the minimum number of valves and sharp bends. However, the scrubbing action
of the foam on the hose wall tends to improve the foam quality.
Note
: A standard fog nozzle can be used with CAFS if used on the ‘Flush’ setting. Using
the ‘Fog’ settings will severely degrade the foam quality.
Note:
the following controls on the FoamLogix Control Panel -