Halcyon 9RLS3 Troubleshooting Manual Download Page 5

8 Times

4 Times Continuous

84

Current sensor error

Current Sensor Error – When input current sensor has detected 0A, while the inverter compressor is operating at 

higher than 56rps, after 1 minute upon starting the compressor. (Except during defrost operation) 

-Check if terminal connection is loose. 

-Check if connector is removed. 

-Check if erroneous connection.

8 Times

6 Times Continuous

86

Pressure sensor error

Pressure Sensor Error – Detects after 30 seconds or more after power up when the pressure sensor detection 

value detects the condition below continuously for 30 seconds or more:  

    

    Ps≤ 37.71 psi (-0.26 Mpa) or Ps ≥ 816.56 psi (5.63 Mpa)

 

-Check connection of pressure sensor; check if terminal connection is loose, connector is removed, connector 

has erroneous connection, cable is open. 

-Check voltage of main PCB.

9 Times

4 Times Continuous

94

Over current error

Over Current Error – Protection stop by overcurrent generation after inverter compressor start processing com-

pleted generated consecutively 10 times. The number of generations is reset if the start-up of the compressor 

succeeds. 

-Clogged heat exchanger. 

-Condenser fan motor defective. 

-Discharged air not sucked in.

9 Times

5 Times Continuous

95

Compressor control error

Compressor Motor Control Error – If the detected rotor location is out of phase with actual rotor location more 

than 90 degrees, the compressor stops. After the compressor restarts, if the same operation is repeated within 

40 seconds, the compressor stops again. 

-Check if connector is removed. 

-Check erroneous connection. 

-Check if cable is open.

9 Times

7 Times Continuous

97

Outdoor unit fan motor 

error

Outdoor Unit Fan Motor Error – When outdoor fan motor rotation speed is less than 100 RPMs in 20 seconds 

after fan motor starts, fan motor stops. After fan motor restarts, if the same operation within 60 seconds is 

repeated 3 times in a row, compressor and fan motor stops. 

-Check rotation of fan, locked motor, or resistance for motor to rotate. 

-Check ambient temperature around motor, excessive high temperature around motor or surrounding equip-

ment that causes heat. 

-Ohm fan motor windings, check for DC voltage to motor.

9 Times

8 Times  Continuous

98

Outdoor unit fan motor 2 

error 

Outdoor Unit Fan Motor 2 Error – When the outdoor fan rotation speed is less than 100 RPMs in 20 seconds 

after the fan motor starts, the fan will stop. After motor restarts, if same operation within 60 seconds is 

repeated 3 times in a row, compressor and fan stop. If above repeats 5 times in a row, compressor and fan stop 

permanently. 

-Check rotation of fan, locked motor, or resistance for motor to rotate. 

-Check ambient temperature around motor, excessive high temperature around motor or surrounding equip-

ment that causes heat. 

-Ohm fan motor windings, check for DC voltage to motor.

Summary of Contents for 9RLS3

Page 1: ...SHOOTING GUIDE FUJITSU GENERAL AMERICA INC 353 Route 46 West Fairfield NJ 07004 866 952 8324 973 575 03881 Service Dept Phone 973 836 0449 Service Dept Fax servicehvac fujitsugeneral com Service Dept...

Page 2: ...Wired Remote Controller System When the address number set by auto setting manual setting are mixed in on RC group When the duplicated address number exists in one RC group Check for wrong wiring conn...

Page 3: ...rror Evaporator pipe thermistor detected an abnormal temperature Check thermistor for open for open or short Check thermistor resistance value Refer to Thermistor character istics table Controller PCB...

Page 4: ...or resistance value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error When the compressor temper...

Page 5: ...out of phase with actual rotor location more than 90 degrees the compressor stops After the compressor restarts if the same operation is repeated within 40 seconds the compressor stops again Check if...

Page 6: ...times within 24 hours Check if 3 way valve is open Check EEV strainer Check outdoor unit fan heat exchanger Check discharge thermistor Check refrigerant amount leak check 10 Times 3 Times Continuous...

Page 7: ...orator Check for correct voltage at panel condenser and evaporator Refer to the Service Instructions manual Serial Signal Troubleshooting for further details 8 Times 0 Wire remote controller error Com...

Page 8: ...or is loose defective contact Rotate fan motor by hand to ensure it is not locked Controller PCB defective 7 Times 2 Times 0F Discharge temperature error The discharge temperature error is activated H...

Page 9: ...ing or piping 2 Times 2 Times Continuous 22 Indoor unit capacity error Indoor Unit Capacity Error The total capacity of the indoor units has been exceeded or is under the minimum acceptable range Chec...

Page 10: ...ch is on for more than 3 minutes error will trigger Check operation of float switch blockages dust etc Remove float and check on off switching operation by using a meter Check connector of CN9 wire Ch...

Page 11: ...value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error Compressor temperature thermistor is ope...

Page 12: ...tance of thermistor Check voltage to thermistor 8 Times 4 Times Continuous 84 Current sensor error Current Sensor Error When input current sensor has detected 0A while the inverter compressor is opera...

Page 13: ...es 1 Time Continuous A1 Discharge temperature error Discharge Temperature Error Protection stop by discharge temperature 230 F 110 C during compressor operation generated 2 times within 24 hours Check...

Page 14: ...Control System Error Manual Auto button error 4 flashes 2 flashes Off Off 20 Power supply 50 HZ 60 HZ detection error 4 flashes 4 flashes Off Off 08 Electronic air clean filter error 4 flashes 7 flash...

Page 15: ...oor unit B Off 6 flashes Off Off 3 way valve thermistor error for indoor unit C Off Off 6 flashes Off 3 way valve thermistor error for indoor unit D Off Off Off 6 flashes Compressor thermistor error 7...

Page 16: ...6 2 Inverter error 6 3 IPM error trip terminal L error 6 5 Discharge temp sensor error 7 1 Compressor temp sensor error 7 2 Heat Ex liquid sensor error 7 3 Outdoor temp sensor error 7 4 Valve sensor...

Page 17: ...mistor error 2 7 2 Heat Ex middle temp sensor error 2 7 3 Heat Ex liquid temp sensor error 2 7 3 Outdoor thermistor error 2 7 4 Heat sink temp sensor error 2 7 7 Current sensor error 2 8 4 Pressure se...

Page 18: ...or unit and branch box Serial communication error between branch boxes 4 Serial communication error between branch boxes 5 Serial communication error between indoor unit A and branch box Serial commun...

Page 19: ...t EX gas inlet thermistor error E212 Number of wires and pipe error E882 Sub cool heat EX gas outlet thermistor error E221 Indoor unit capacity error E831 Liquid pipe thermistor error E242 Number of i...

Page 20: ...shes Continuous blink Continuous blink Outdoor communication error forward reverse transfer error 6 flashes Continuous blink OFF Indoor fan abnormal Continuous blink 2 flashes OFF Outdoor power source...

Page 21: ...or 08 Power source connection error 09 Float switch operated 0A Outdoor temperature sensor error 0c Discharge pipe temperature sensor 11 Model abnormal indoor EPROM abnormal 12 Indoor fan abnormal 13...

Page 22: ...5 ft 49 ft 2 oz ft 9 ft 53A 12RLQ 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RL 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS 2 lbs 9 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS2 12RLS2H 2 lbs 10 oz 49 ft 66...

Page 23: ...164 ft 21 oz ft 16 ft 24A 24RLXFZH 4 lbs 14 oz 98 ft 229 ft 21 oz ft 16 ft 49 ft combined N A 30CLX 30CLX1 4 lbs 10 oz 66 ft 165 ft 43 oz ft 16 ft 36A 34A 30RLXB 4 lbs 10 oz 66 ft 164 ft 43 oz ft 16...

Page 24: ...12 7 67 80 3 68 20 12 54 5 86 62 91 28 14 64 5 62 55 6 1 12 64 6 1 62 9 77 25 10 5 24 49 7 25 15 51 27 49 84 4 89 10 4 89 49 7 86 30 8 04 4 64 39 57 22 26 41 07 40 01 3 95 7 97 3 95 39 6 95 35 6 51 3...

Reviews: