Halcyon 9RLS3 Troubleshooting Manual Download Page 2

Wall Mounted: 9RL2, 9RLS3, 9RLS3H, 9RLS3Y, 12RL2, 12RLS3, 12RLS3H, 12RLS3Y, 15RLS3, 15RLS3H, 15RLS3Y, 18RLB, 24RLB, 30RLXB, 30RLXEH, 36RLXB

Error Indication

Wired Remote 

Controller

Error 

Diagnosis Method

Operation

Timer

Economy

1 Time

1 Time Continuous

11

Serial communication error

Communication Error – At Start up, evaporator and condenser are not communicating. 

-Check wiring from panel to condenser, condenser to evaporator. Wire nuts and splices are not recommended. 

Check for correct voltages at panel, condenser and evaporator. Refer to the Service Instruction manual – Serial 

Signal Troubleshooting for further details.

1 Time

2 Times Continuous

12

Wired remote controller 

communication error

Wired Remote Controller Communication Error – When the indoor unit cannot receive the signal from the Wired 

Remote Control for more than 1 minute during normal operation.

-Check the connection of terminal between remote control and indoor unit and check if there is a disconnection 

of the cable.

1 Time

8 Times Continuous

18

External communication 

error

External Communication Error – After receiving a signal from the external I/O PCB, the same signal has not 

been received for 15 seconds.  

-Check any loose or removed connections between the controller PCB to the external I/O PCB, open cable or 

mis-wiring.  

-Replace controller PCB.

2 Times 

3 Times  Continuous

23

Combination error 

Combination Error – The outdoor unit received a signal that the applied indoor unit is that of a multi type. 

-Replace indoor unit with correct matching indoor unit.

2 Times 

6 Times  Continuous

26

Address setting error in 

wired remote controller 

system

Address Setting Error in Wired Remote Controller System – When the address number set by auto setting & 

manual setting are mixed in on RC group. When the duplicated address number exists in one RC group.  

-Check for wrong wiring connection in the RC group. (Refer to Installation Manual) 

-Wrong RC group setting; the given address number by auto setting (00) and the manual set number (except 

00) were not existing in one RC group, the remote controller address setting by U.I. was not an existing same 

address, duplicated address number is not existing in one RC group. 

-Check indoor unit controller PCB; check if the controller PCB is damaged.

2 Times 

9 Times  Continuous

29

Connection unit number 

error

Combination Unit Number Error – When the number of connecting indoor units are out of a specified rule.

 

-Check wire installation; wrong number of connecting indoor unit.  

-Check indoor unit controller PCB; check if controller PCB is damaged, check for error after setting remote 

controller address.

3 Times

2 Times Continuous

32

Indoor unit model informa-

tion error 

EEPROM access abnormal

EEPROM Error – Electronically erasable and programmable read only memory. It is a non-volatile memory 

which keeps memorized information even if power is turned off. It can change the contents electronically. To 

change the contents, it uses higher voltage than normal, and cannot change partial contents. Rewriting shall 

be done upon erasing all the contents. There is a limit in several rewritings. 

-Check if the ground connection is proper.  

-Check if there is any equipment that causes harmonic wave near the power cables, i.e. neon light bulb.

3 Times

5 Times Continuous

35

Manual auto switch error

Manual Auto Switch Error – When the manual auto switch becomes on for 60 or more consecutive seconds. 

-Check if Manual/Auto switch is kept pressed. Check On/Off switching operation by using a meter.

Summary of Contents for 9RLS3

Page 1: ...SHOOTING GUIDE FUJITSU GENERAL AMERICA INC 353 Route 46 West Fairfield NJ 07004 866 952 8324 973 575 03881 Service Dept Phone 973 836 0449 Service Dept Fax servicehvac fujitsugeneral com Service Dept...

Page 2: ...Wired Remote Controller System When the address number set by auto setting manual setting are mixed in on RC group When the duplicated address number exists in one RC group Check for wrong wiring conn...

Page 3: ...rror Evaporator pipe thermistor detected an abnormal temperature Check thermistor for open for open or short Check thermistor resistance value Refer to Thermistor character istics table Controller PCB...

Page 4: ...or resistance value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error When the compressor temper...

Page 5: ...out of phase with actual rotor location more than 90 degrees the compressor stops After the compressor restarts if the same operation is repeated within 40 seconds the compressor stops again Check if...

Page 6: ...times within 24 hours Check if 3 way valve is open Check EEV strainer Check outdoor unit fan heat exchanger Check discharge thermistor Check refrigerant amount leak check 10 Times 3 Times Continuous...

Page 7: ...orator Check for correct voltage at panel condenser and evaporator Refer to the Service Instructions manual Serial Signal Troubleshooting for further details 8 Times 0 Wire remote controller error Com...

Page 8: ...or is loose defective contact Rotate fan motor by hand to ensure it is not locked Controller PCB defective 7 Times 2 Times 0F Discharge temperature error The discharge temperature error is activated H...

Page 9: ...ing or piping 2 Times 2 Times Continuous 22 Indoor unit capacity error Indoor Unit Capacity Error The total capacity of the indoor units has been exceeded or is under the minimum acceptable range Chec...

Page 10: ...ch is on for more than 3 minutes error will trigger Check operation of float switch blockages dust etc Remove float and check on off switching operation by using a meter Check connector of CN9 wire Ch...

Page 11: ...value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error Compressor temperature thermistor is ope...

Page 12: ...tance of thermistor Check voltage to thermistor 8 Times 4 Times Continuous 84 Current sensor error Current Sensor Error When input current sensor has detected 0A while the inverter compressor is opera...

Page 13: ...es 1 Time Continuous A1 Discharge temperature error Discharge Temperature Error Protection stop by discharge temperature 230 F 110 C during compressor operation generated 2 times within 24 hours Check...

Page 14: ...Control System Error Manual Auto button error 4 flashes 2 flashes Off Off 20 Power supply 50 HZ 60 HZ detection error 4 flashes 4 flashes Off Off 08 Electronic air clean filter error 4 flashes 7 flash...

Page 15: ...oor unit B Off 6 flashes Off Off 3 way valve thermistor error for indoor unit C Off Off 6 flashes Off 3 way valve thermistor error for indoor unit D Off Off Off 6 flashes Compressor thermistor error 7...

Page 16: ...6 2 Inverter error 6 3 IPM error trip terminal L error 6 5 Discharge temp sensor error 7 1 Compressor temp sensor error 7 2 Heat Ex liquid sensor error 7 3 Outdoor temp sensor error 7 4 Valve sensor...

Page 17: ...mistor error 2 7 2 Heat Ex middle temp sensor error 2 7 3 Heat Ex liquid temp sensor error 2 7 3 Outdoor thermistor error 2 7 4 Heat sink temp sensor error 2 7 7 Current sensor error 2 8 4 Pressure se...

Page 18: ...or unit and branch box Serial communication error between branch boxes 4 Serial communication error between branch boxes 5 Serial communication error between indoor unit A and branch box Serial commun...

Page 19: ...t EX gas inlet thermistor error E212 Number of wires and pipe error E882 Sub cool heat EX gas outlet thermistor error E221 Indoor unit capacity error E831 Liquid pipe thermistor error E242 Number of i...

Page 20: ...shes Continuous blink Continuous blink Outdoor communication error forward reverse transfer error 6 flashes Continuous blink OFF Indoor fan abnormal Continuous blink 2 flashes OFF Outdoor power source...

Page 21: ...or 08 Power source connection error 09 Float switch operated 0A Outdoor temperature sensor error 0c Discharge pipe temperature sensor 11 Model abnormal indoor EPROM abnormal 12 Indoor fan abnormal 13...

Page 22: ...5 ft 49 ft 2 oz ft 9 ft 53A 12RLQ 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RL 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS 2 lbs 9 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS2 12RLS2H 2 lbs 10 oz 49 ft 66...

Page 23: ...164 ft 21 oz ft 16 ft 24A 24RLXFZH 4 lbs 14 oz 98 ft 229 ft 21 oz ft 16 ft 49 ft combined N A 30CLX 30CLX1 4 lbs 10 oz 66 ft 165 ft 43 oz ft 16 ft 36A 34A 30RLXB 4 lbs 10 oz 66 ft 164 ft 43 oz ft 16...

Page 24: ...12 7 67 80 3 68 20 12 54 5 86 62 91 28 14 64 5 62 55 6 1 12 64 6 1 62 9 77 25 10 5 24 49 7 25 15 51 27 49 84 4 89 10 4 89 49 7 86 30 8 04 4 64 39 57 22 26 41 07 40 01 3 95 7 97 3 95 39 6 95 35 6 51 3...

Reviews: