![Halcyon 9RLS3 Troubleshooting Manual Download Page 19](http://html1.mh-extra.com/html/halcyon/9rls3/9rls3_troubleshooting-manual_3392197019.webp)
Halcyon HFI Flex Outdoor Unit
AOU48RLXFZ, AOU48RLXFZ1
• When error occurs, “Err” and “Number of error occurred” are alternately displayed in 7 seg. Display.
•
The latest error code can be confirmed by pressing the ENTER button.
•
When error codes are displayed, all the error codes can be confirmed by pressing the SELECT button.
Example: When “Discharge thermistor error” and “Compressor thermistor error” have occurred.
E
r
r
2
E
7
1
1
E
7
2
1
ENTER
SELECT
SELECT
Press the “SELECT” button.
ENTER
Press the “ENTER” button.
CODE
DESCRIPTION
CODE
DESCRIPTION
E113
Serial communication error
E751
Suction gas thermistor error
E114
E771
Heat sink thermistor error
E156
Check-run unfinished
E821
Sub-cool heat EX. gas inlet thermistor error
E212
Number of wires and pipe error
E882
Sub-cool heat EX. gas outlet thermistor error
E221
Indoor unit capacity error
E831
Liquid pipe thermistor error
E242
Number of indoor units error
E841
Current sensor error
E243
Number of Branch boxes error
E861
Discharge pressure sensor error
E5U1
Indoor unit error
E863
Suction pressure sensor error
E621
Outdoor unit model
E864
High pressure switch error
E631
Inverter error
E941
Over current error
E641
A.F. voltage error
E951
Compressor control error
E653
IPM error
E973
Outdoor unit fan motor error
E6A1
Display P.C.B. communication error
E991
4-way valve error
E711
Discharge thermistor error
EA11
Discharge temp. error
E721
Compressor thermistor error
EA31
Compressor temp. error
E733
Heat Ex. Liquid outlet thermistor error
EA51
Low pressure error
E741
Outdoor thermistor error
EJ2U
Branch boxes error