Halcyon 9RLS3 Troubleshooting Manual Download Page 19

Halcyon HFI Flex Outdoor Unit

AOU48RLXFZ, AOU48RLXFZ1

 When error occurs, “Err” and “Number of error occurred” are alternately displayed in 7 seg. Display.

 The latest error code can be confirmed by pressing the ENTER button.

 When error codes are displayed, all the error codes can be confirmed by pressing the SELECT button.

Example: When “Discharge thermistor error” and “Compressor thermistor error” have occurred.

E

r

r

2

E

7

1

1

E

7

2

1

ENTER

SELECT

SELECT

    Press the “SELECT” button.

ENTER

    Press the “ENTER” button.

CODE

DESCRIPTION

CODE

DESCRIPTION

E113

Serial communication error

E751

Suction gas thermistor error

E114

E771

Heat sink thermistor error

E156

Check-run unfinished

E821

Sub-cool heat EX. gas inlet thermistor error

E212

Number of wires and pipe error 

E882

Sub-cool heat EX. gas outlet thermistor error

E221

Indoor unit capacity error

E831

Liquid pipe thermistor error

E242

Number of indoor units error 

E841

Current sensor error

E243

Number of Branch boxes error 

E861

Discharge pressure sensor error

E5U1

Indoor unit error

E863

Suction pressure sensor error

E621

Outdoor unit model 

E864

High pressure switch error

E631

Inverter error

E941

Over current error

E641

A.F. voltage error 

E951

Compressor control error

E653

IPM error

E973

Outdoor unit fan motor error 

E6A1

Display P.C.B. communication error

E991

4-way valve error

E711

Discharge thermistor error

EA11

Discharge temp. error

E721

Compressor thermistor error 

EA31

Compressor temp. error

E733

Heat Ex. Liquid outlet thermistor error

EA51

Low pressure error 

E741

Outdoor thermistor error

EJ2U

Branch boxes error 

Summary of Contents for 9RLS3

Page 1: ...SHOOTING GUIDE FUJITSU GENERAL AMERICA INC 353 Route 46 West Fairfield NJ 07004 866 952 8324 973 575 03881 Service Dept Phone 973 836 0449 Service Dept Fax servicehvac fujitsugeneral com Service Dept...

Page 2: ...Wired Remote Controller System When the address number set by auto setting manual setting are mixed in on RC group When the duplicated address number exists in one RC group Check for wrong wiring conn...

Page 3: ...rror Evaporator pipe thermistor detected an abnormal temperature Check thermistor for open for open or short Check thermistor resistance value Refer to Thermistor character istics table Controller PCB...

Page 4: ...or resistance value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error When the compressor temper...

Page 5: ...out of phase with actual rotor location more than 90 degrees the compressor stops After the compressor restarts if the same operation is repeated within 40 seconds the compressor stops again Check if...

Page 6: ...times within 24 hours Check if 3 way valve is open Check EEV strainer Check outdoor unit fan heat exchanger Check discharge thermistor Check refrigerant amount leak check 10 Times 3 Times Continuous...

Page 7: ...orator Check for correct voltage at panel condenser and evaporator Refer to the Service Instructions manual Serial Signal Troubleshooting for further details 8 Times 0 Wire remote controller error Com...

Page 8: ...or is loose defective contact Rotate fan motor by hand to ensure it is not locked Controller PCB defective 7 Times 2 Times 0F Discharge temperature error The discharge temperature error is activated H...

Page 9: ...ing or piping 2 Times 2 Times Continuous 22 Indoor unit capacity error Indoor Unit Capacity Error The total capacity of the indoor units has been exceeded or is under the minimum acceptable range Chec...

Page 10: ...ch is on for more than 3 minutes error will trigger Check operation of float switch blockages dust etc Remove float and check on off switching operation by using a meter Check connector of CN9 wire Ch...

Page 11: ...value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error Compressor temperature thermistor is ope...

Page 12: ...tance of thermistor Check voltage to thermistor 8 Times 4 Times Continuous 84 Current sensor error Current Sensor Error When input current sensor has detected 0A while the inverter compressor is opera...

Page 13: ...es 1 Time Continuous A1 Discharge temperature error Discharge Temperature Error Protection stop by discharge temperature 230 F 110 C during compressor operation generated 2 times within 24 hours Check...

Page 14: ...Control System Error Manual Auto button error 4 flashes 2 flashes Off Off 20 Power supply 50 HZ 60 HZ detection error 4 flashes 4 flashes Off Off 08 Electronic air clean filter error 4 flashes 7 flash...

Page 15: ...oor unit B Off 6 flashes Off Off 3 way valve thermistor error for indoor unit C Off Off 6 flashes Off 3 way valve thermistor error for indoor unit D Off Off Off 6 flashes Compressor thermistor error 7...

Page 16: ...6 2 Inverter error 6 3 IPM error trip terminal L error 6 5 Discharge temp sensor error 7 1 Compressor temp sensor error 7 2 Heat Ex liquid sensor error 7 3 Outdoor temp sensor error 7 4 Valve sensor...

Page 17: ...mistor error 2 7 2 Heat Ex middle temp sensor error 2 7 3 Heat Ex liquid temp sensor error 2 7 3 Outdoor thermistor error 2 7 4 Heat sink temp sensor error 2 7 7 Current sensor error 2 8 4 Pressure se...

Page 18: ...or unit and branch box Serial communication error between branch boxes 4 Serial communication error between branch boxes 5 Serial communication error between indoor unit A and branch box Serial commun...

Page 19: ...t EX gas inlet thermistor error E212 Number of wires and pipe error E882 Sub cool heat EX gas outlet thermistor error E221 Indoor unit capacity error E831 Liquid pipe thermistor error E242 Number of i...

Page 20: ...shes Continuous blink Continuous blink Outdoor communication error forward reverse transfer error 6 flashes Continuous blink OFF Indoor fan abnormal Continuous blink 2 flashes OFF Outdoor power source...

Page 21: ...or 08 Power source connection error 09 Float switch operated 0A Outdoor temperature sensor error 0c Discharge pipe temperature sensor 11 Model abnormal indoor EPROM abnormal 12 Indoor fan abnormal 13...

Page 22: ...5 ft 49 ft 2 oz ft 9 ft 53A 12RLQ 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RL 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS 2 lbs 9 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS2 12RLS2H 2 lbs 10 oz 49 ft 66...

Page 23: ...164 ft 21 oz ft 16 ft 24A 24RLXFZH 4 lbs 14 oz 98 ft 229 ft 21 oz ft 16 ft 49 ft combined N A 30CLX 30CLX1 4 lbs 10 oz 66 ft 165 ft 43 oz ft 16 ft 36A 34A 30RLXB 4 lbs 10 oz 66 ft 164 ft 43 oz ft 16...

Page 24: ...12 7 67 80 3 68 20 12 54 5 86 62 91 28 14 64 5 62 55 6 1 12 64 6 1 62 9 77 25 10 5 24 49 7 25 15 51 27 49 84 4 89 10 4 89 49 7 86 30 8 04 4 64 39 57 22 26 41 07 40 01 3 95 7 97 3 95 39 6 95 35 6 51 3...

Reviews: