Halcyon 9RLS3 Troubleshooting Manual Download Page 3

3 Times

10 

Times

Continuous

3A

Indoor unit communication 

circuit (WRC) error

Indoor Unit Communication Circuit (WRC) Error – When the indoor unit detects the configuration of the remote 

controller group is abnormal or the indoor unit detects lack of primary remote controller.  

-Check the connection of the terminal; check the connection of the terminal between the remote controller and 

indoor unit, or check between indoor unit if there is a disconnect or short of the cable. 

-Check indoor unit controller PCB; check terminal voltage of the controller PCB connector on CNC01 (power 

supply for remote) If 12vDC, remote controller failure, replace remote controller. If 0vDC, controller PCB failure, 

replace controller PCB.

4 Times

1 Time Continuous

41

Indoor room thermistor 

error

Indoor Room Thermistor Error – Room temperature thermistor detected an abnormal temperature. 

-Check thermistor for open or short. Check thermistor resistance value. (Refer to “Thermistor characteristics 

table”). 

-Controller PCB defective.

4 Times

2 Times Continuous

42

Indoor heat ex. (Pipe) 

thermistor error

Indoor Heat Ex. (Pipe) Thermistor Error – Evaporator pipe thermistor detected an abnormal temperature. 

-Check thermistor for open for open or short. Check thermistor resistance value (Refer to “Thermistor character-

istics table”). 

-Controller PCB defective.

5 Times

1 Time Continuous

51

Indoor unit fan motor error

Indoor Unit Fan Motor Error – When the condition that actual frequency of indoor fan is below 1/3 of target 

frequency is continued more than 56 seconds. 

-Check rotation of fan. 

-Check ambient temperature around motor. 

-Check indoor unit fan motor resistance values. 

-Replace controller PCB.

5 Times

8 Times Continuous

58

Intake grille error

Intake Grille Error – When the micro switch is detected open while running the compressor. 

-Check limit switch. 

-Check connector (CN11) / wire. 

-Replace controller PCB.

6 Times

2 Times Continuous

62

Outdoor unit main PCB error

Outdoor Unit Main PCB Error – Access to EEPROM failed due to some cause after outdoor unit started. 

-Reset power supply and operate. 

-Check external cause; voltage drop, poor ground connection. 

-Replace Main PCB.

6 Times

3 Times Continuous

63

Inverter error

Inverter Error – Error information received from the transistor PCB. 

-Check wiring (Power supply to filter PCB to transistor PCB); connector and wiring connection, cable open. 

 

-Replace transistor PCB 

-Replace main PCB 

-Replace filter PCB

Summary of Contents for 9RLS3

Page 1: ...SHOOTING GUIDE FUJITSU GENERAL AMERICA INC 353 Route 46 West Fairfield NJ 07004 866 952 8324 973 575 03881 Service Dept Phone 973 836 0449 Service Dept Fax servicehvac fujitsugeneral com Service Dept...

Page 2: ...Wired Remote Controller System When the address number set by auto setting manual setting are mixed in on RC group When the duplicated address number exists in one RC group Check for wrong wiring conn...

Page 3: ...rror Evaporator pipe thermistor detected an abnormal temperature Check thermistor for open for open or short Check thermistor resistance value Refer to Thermistor character istics table Controller PCB...

Page 4: ...or resistance value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error When the compressor temper...

Page 5: ...out of phase with actual rotor location more than 90 degrees the compressor stops After the compressor restarts if the same operation is repeated within 40 seconds the compressor stops again Check if...

Page 6: ...times within 24 hours Check if 3 way valve is open Check EEV strainer Check outdoor unit fan heat exchanger Check discharge thermistor Check refrigerant amount leak check 10 Times 3 Times Continuous...

Page 7: ...orator Check for correct voltage at panel condenser and evaporator Refer to the Service Instructions manual Serial Signal Troubleshooting for further details 8 Times 0 Wire remote controller error Com...

Page 8: ...or is loose defective contact Rotate fan motor by hand to ensure it is not locked Controller PCB defective 7 Times 2 Times 0F Discharge temperature error The discharge temperature error is activated H...

Page 9: ...ing or piping 2 Times 2 Times Continuous 22 Indoor unit capacity error Indoor Unit Capacity Error The total capacity of the indoor units has been exceeded or is under the minimum acceptable range Chec...

Page 10: ...ch is on for more than 3 minutes error will trigger Check operation of float switch blockages dust etc Remove float and check on off switching operation by using a meter Check connector of CN9 wire Ch...

Page 11: ...value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error Compressor temperature thermistor is ope...

Page 12: ...tance of thermistor Check voltage to thermistor 8 Times 4 Times Continuous 84 Current sensor error Current Sensor Error When input current sensor has detected 0A while the inverter compressor is opera...

Page 13: ...es 1 Time Continuous A1 Discharge temperature error Discharge Temperature Error Protection stop by discharge temperature 230 F 110 C during compressor operation generated 2 times within 24 hours Check...

Page 14: ...Control System Error Manual Auto button error 4 flashes 2 flashes Off Off 20 Power supply 50 HZ 60 HZ detection error 4 flashes 4 flashes Off Off 08 Electronic air clean filter error 4 flashes 7 flash...

Page 15: ...oor unit B Off 6 flashes Off Off 3 way valve thermistor error for indoor unit C Off Off 6 flashes Off 3 way valve thermistor error for indoor unit D Off Off Off 6 flashes Compressor thermistor error 7...

Page 16: ...6 2 Inverter error 6 3 IPM error trip terminal L error 6 5 Discharge temp sensor error 7 1 Compressor temp sensor error 7 2 Heat Ex liquid sensor error 7 3 Outdoor temp sensor error 7 4 Valve sensor...

Page 17: ...mistor error 2 7 2 Heat Ex middle temp sensor error 2 7 3 Heat Ex liquid temp sensor error 2 7 3 Outdoor thermistor error 2 7 4 Heat sink temp sensor error 2 7 7 Current sensor error 2 8 4 Pressure se...

Page 18: ...or unit and branch box Serial communication error between branch boxes 4 Serial communication error between branch boxes 5 Serial communication error between indoor unit A and branch box Serial commun...

Page 19: ...t EX gas inlet thermistor error E212 Number of wires and pipe error E882 Sub cool heat EX gas outlet thermistor error E221 Indoor unit capacity error E831 Liquid pipe thermistor error E242 Number of i...

Page 20: ...shes Continuous blink Continuous blink Outdoor communication error forward reverse transfer error 6 flashes Continuous blink OFF Indoor fan abnormal Continuous blink 2 flashes OFF Outdoor power source...

Page 21: ...or 08 Power source connection error 09 Float switch operated 0A Outdoor temperature sensor error 0c Discharge pipe temperature sensor 11 Model abnormal indoor EPROM abnormal 12 Indoor fan abnormal 13...

Page 22: ...5 ft 49 ft 2 oz ft 9 ft 53A 12RLQ 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RL 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS 2 lbs 9 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS2 12RLS2H 2 lbs 10 oz 49 ft 66...

Page 23: ...164 ft 21 oz ft 16 ft 24A 24RLXFZH 4 lbs 14 oz 98 ft 229 ft 21 oz ft 16 ft 49 ft combined N A 30CLX 30CLX1 4 lbs 10 oz 66 ft 165 ft 43 oz ft 16 ft 36A 34A 30RLXB 4 lbs 10 oz 66 ft 164 ft 43 oz ft 16...

Page 24: ...12 7 67 80 3 68 20 12 54 5 86 62 91 28 14 64 5 62 55 6 1 12 64 6 1 62 9 77 25 10 5 24 49 7 25 15 51 27 49 84 4 89 10 4 89 49 7 86 30 8 04 4 64 39 57 22 26 41 07 40 01 3 95 7 97 3 95 39 6 95 35 6 51 3...

Reviews: