HAKARU PLUS CORPORATION Tel. 81-6-6300-2195
Page 10
05/12/16 TFL-B101Q DS (FL6)
1 3 5 7
2 4 6 8
9
10
Socket for Input Signal
Conditioning Module
2
3
5
1
4
1
2
3
4
5
6
7
8
9
10
Input and output
pins vary for
different modules.
Please see the
specific module
data sheet for
details.
1.25 V
Bandgap
Reference
8
9
10
11
12
13
14
15
17
18
19
20
21
23
24
NO3
COM 1 & 3
NO1
NC1
NO4
COM 2 & 4
NO2
NC2
Analog –
Program Lock
Common
Dim
Display
Driver
Multiplexer
and
Buffer
Amplifier
Micro
Processor
1M
1M
0.1
0.1
GND
FL-B101Q Functional Diagram
Input Hi
Input Lo
+5VDC
-5VDC
+24VDC
Ref Hi
Analog Common
System Ground
MUXO
24 V Return
GND
+ 5 V
14 Bit
Single
Slope
A to D
GND
+ 5 V
GND
+ 5 V
GND
Isolated 16 Bit Sigma Delta D to A
Select Header
mA
V
AC Neutral, – DC
AC Line, + DC
AC/DC Power Input
MOV's
10A
5A
+ 5 V
SP3
+ 5 V
SP1
MOV's
10A
5A
+ 5 V
SP4
+ 5 V
SP2
+15 V DC
CENTER
ZERO
SELECT
HEADER
RELAYS
ACTIVE ON
SELECT
HEADER
MODE 1
MODE 2
MODE 3
CTO CH2
CTO CH1
Relay 4
Relay 3
Relay 2
Relay 1
SP1 SP2 SP3 SP4
Zero Span
0
10
20
30
40
50
60
70
80
90
100
NTC
EMI Filter
Isolated
Switching
Supply
-5 V DC
+5 V DC
+24 V DC
ISO
GND
GND
+15 V DC
ISO
GND
!
WARNING
AC and DC power supply voltages are hazard-
ous. Make sure the power supply is isolated
before connecting to the meter.
COM
1&3
NO3
SP3
NO
SP1/3
COM
SP1
NC
SP2
N1
SP1
NO
SP2/4
COM
SP2
NC
SP2
NO
LOCK
COMMON
DIM
NC1
SP3
COM
2&4
NC2
NO4
SP4
NO1
SP1
NO2
SP2
8 9 10 11 12 13 14 15
17 18 19 20 21
23 24
1-6
See Leopard Family Input
Signal Conditioning Moduls
Analog
Analog
Output –
AC
Neutral
AC
Line
– DC
+ DC
or
This meter uses plug-in type screw terminal connectors
for all input and output connections. The power supply
connections (pins 23 and 24) have a unique plug and
socket outline to prevent cross connection. The main
board uses standard right-angled connectors.
Replacement 2-, 3-, and 4-pin plug connectors are
available (see Accessories on page 16).
Input Signal – Pins 1 to 6
Pins 1 to 6 are reserved for the input signal conditioner.
See the data sheet for the selected input signal conditioner.
Pins 8 to 15 – Relay Output Pins
Pin 8 SP3 NO.
Normally Open 5 Amp Form A.
Pin 9 SP1/3 COM.
Common for SP1 and SP3.
Pin 10 SP1 NC.
Normally Closed 10 Amp Form C.
Pin 11 SP1 NO.
Normally Open 10 Amp Form C.
Pin 12 SP4 NO.
Normally Open 5 Amp Form A.
Pin 13 SP2/4 COM.
Common for SP3 and SP4.
Pin 14 SP2 NC.
Normally Closed 10 Amp Form C.
Pin 15 SP2 NO.
Normally Open 10 Amp Form C.
Pins 17 to 21 – Rear Panel Switches
Pin 17 ANALOG OUTPUT (+).
mA (0 to 20 mA/4 to 20 mA)
or V (0 to 10 V) output is header selectable.
Pin 18 ANALOG OUTPUT (–).
mA (0 to 20 mA/4 to
20 mA) or V (0 to 10 V) output is header selectable.
Pin 19 Programming LOCK.
By connecting the LOCK pin
to the COMMON pin, the meter's programmed
parameters can be viewed but not changed.
Pin 20 COMMON.
To activate the LOCK or DIM functions
from the rear of the meter, the respective pins have
to be connected to the COMMON pin. This pin is
connected to the internal power supply ground.
Pin 21 DIM.
By connecting the display dim (DIM) pin to
the COMMON pin, the display brightness setting
is halved.
Pins 23 and 24 – AC/DC Power Input
Auto-sensing AC/DC power supply. For voltages between
85-265 V AC / 95-370 V DC (PS1) or 18-48 V AC / 10-72 V
DC (PS2).
Pin 23 AC Neutral / –DC.
Neutral power supply line.
Pin 24 AC line / +DC.
Live power supply line.
Functional Diagram
Connector Pinouts
Pin Descriptions
Note: The sequence of setpoint outputs on meters shipped prior to 2002
was 1-2-3-4. The sequence is now 3-1-4-2, enabling delay on make
(dom) and delay on break (dob) to be used with both Form “C” relays.