Haiwell PLC - Temperature & Humidity Module User Manual

7 / 23

25H~28H

A/D data bit of channel 1~4

34H

Configuration number of channel 1

29H~2CH

Zero point correction of channel 1~4

35H

Configuration number of channel 2

2DH

Sensor disconnection alarm of channel 1~4, each bit

indicates 1 channel, 0- normal, 1- disconnection

36~75H

Serial numbers in 1~16 path of channel 1, each serial

number occupies 4 registers

2EH~2FH

Reserve

76~B5H

Serial numbers in 1~16 path of channel 2, each serial

number occupies 4 registers

30H-3FH

Serial numbers of channel 1~4, each serial number

occupies 4 registers

B6~C5H

Reserve

40H-4FH

Reserve

C6H

Channel 1 clears the power-off counts in the configuration

C7H

Channel 2 clears the power-off counts in the configuration

8.2 Parameter table for 4-channel thermal resistance and thermocouple modules

Note: CR code is corresponding to the Modbus register address, the gray parts are read-only ,the white parts are readable and

writable.

CR code

Function description

H04RC

H04TC

00H

Low byte for module code, and high byte for module version number

01H

Communication address

0

2

H

Communication protocol: The low 4-bit of the low byte: 0 - N,8,2 For RTU

1 - E,8,1 For RTU

2 - O,8,1 For RTU

3 - N,7,2 For ASCII

4 - E,7,1 For ASCII

5 - O,7,1 For ASCII

6 - N,8, 1 For RTU

The high 4-bit of the low byte: 0 – 2400

1 – 4800

2 – 9600

3 – 19200

4 – 38400

5 – 57600

6 - 115200

03H~06H

Module name

07H~08H

Default IP address: 192.168.1.111

09~0AH

Reserve

0BH

High byte subnet mask

b3~b0,1 indicates 255, 0 indicates 0, for example, subnet mask 255.255.255.0, b3~b0=1110

, low byte reserved

0CH-0EH

Reserve

0FH

Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V power

supply

10H

channel 1 input value

channel 1 input value

11H

channel 2 input value

channel 2 input value

12H

channel 3 input value

channel 3 input value

13H

channel 4 input value

channel 4 input value

14H

channel 1 signal type, note 2

channel 1 signal type, note 3

15H

channel 2 signal type, note 2

channel 2 signal type, note 3

16H

channel 3 signal type, note 2

channel 3 signal type, note 3

17H

channel 4 signal type, note 2

channel 4 signal type, note 3

18H

Use the engineering value mark, note 5

Use the engineering value mark, note 5

19H

channel 1 engineering lower limiting value

channel 1 engineering lower limiting value

1AH

channel 2 engineering lower limiting value

channel 2 engineering lower limiting value

1BH

channel 3 engineering lower limiting value

channel 3 engineering lower limiting value

1CH

channel 4 engineering lower limiting value

channel 4 engineering lower limiting value

1DH

channel 1 engineering upper limiting value

channel 1 engineering upper limiting value

1EH

channel 2 engineering upper limiting value

channel 2 engineering upper limiting value

1FH

channel 3 engineering upper limiting value

channel 3 engineering upper limiting value

20H

channel 4 engineering upper limiting value

channel 4 engineering upper limiting value

21H

channel 1 sampling frequency, note 1

channel 1 sampling frequency, note 1

22H

channel 2 sampling frequency, note 1

channel 2 sampling frequency, note 1

23H

channel 3 sampling frequency, note 1

channel 3 sampling frequency, note 1

24H

channel 4 sampling frequency, note 1

channel 4 sampling frequency, note 1

25H

channel 1 zero point correction value

channel 1 zero point correction value

26H

channel 2 zero point correction value

channel 2 zero point correction value

27H

channel 3 zero point correction value

channel 3 zero point correction value

28H

channel 4 zero point correction value

channel 4 zero point correction value

29H

Channel 1~4 input disconnection alarm, note 4

Channel 1~4 input disconnection alarm, note 4

2AH

Reserve

Reserve

2BH~2FH

Summary of Contents for H04DT

Page 1: ...m Haiwell PLC Temperature Humidity Module User Manual Xiamen Haiwell Technology Co Ltd www haiwell com Haiwell PLC User Manual Programmable Logic Controller Temperature Humidity Module User Manual App...

Page 2: ...se 1 Expand module through the host PLC parallel port 10 1 1 Module power supply 10 1 2 Temperature modules need t be written any conversion program read the current temperature value directly when ac...

Page 3: ...35 0 5 6 7 8 9 10 11 12 0 1 2 3 4 5 6 7 AI AI LINK POW RT1 RT0M RT2M RT0 RT2 RT0 RT2 RT3M GND RT3 A RT1M B RT1 RT3 RS485 RT4M RT6M RT4 RT6 RT4 RT5M RT7 RT7 RT7M RT5 RT5 RT6 1 2 3 4 ON DIP H08RC 13 14...

Page 4: ...d maintenance Without serial or parallel port in communication Constant light in red With serial or parallel port in communication Red jitter quickly indicator on 30ms and off 30ms 3 RJ45 Ethernet ind...

Page 5: ...0 50 mV 0 100 mV Resolution 0 1 0 1 Input impedance 6M 6M Maximum input range 13V 30mA Input indication LED light ON means normal OFF means external disconnection Response time 560ms 4 Channel 880ms 8...

Page 6: ...code H32DTfunction description 00H Low byte for module code and high byte for module version number 01H Communication address 02H Communication protocol The low 4 bit of the low byte 0 N 8 2 For RTU...

Page 7: ...1 input value 11H channel 2 input value channel 2 input value 12H channel 3 input value channel 3 input value 13H channel 4 input value channel 4 input value 14H channel 1 signal type note 2 channel...

Page 8: ...note 5 21H channel 1 engineering lower limiting value channel 1 engineering lower limiting value 22H channel 2 engineering lower limiting value channel 2 engineering lower limiting value 23H channel...

Page 9: ...bit indicates 1 channel 0 normal 1 disconnection 5 5 Use the engineering value mark Each bit indicates 1 channel 0 No 1 Yes 9 Expansion modules installation The PLC should be secured to an enclosed c...

Page 10: ...dule is added external power supply it can still work this time the module will automatically determine and give priority to external power supply 1 2 Temperature modules need t be written any convers...

Page 11: ...uration that is the actual temperature value for example you can set 1 on decimal places of Haiwell Cloud SCADA settings So that when the PLC read AI0 value AI0 123 that is the actual value of 12 3 th...

Page 12: ...uted installation is very important for the system which needs to collect and monitor a large number of decentralized digital or analog signals temperature humidity differential pressure blowing rate...

Page 13: ...configured via programming software tools remote modules recommended 2 It can be configured via the hardware configuration and TO instructions when the module is hung behind the host PLC through the p...

Page 14: ...ameter configuration Click to exit enter the configuration interface as shown below We can change the module name address IP subnet mask baud rate data format and other communication parameters in the...

Page 15: ...ut values are stored in 10H 13H of H04RC module 3 PLC program Host PLC wants to read the 4 channel temperature values of remote IO module H04RC 4 channel temperature sensors for PT100 2000 8500 indica...

Page 16: ...ed in the V10 V17 as follows 1 8 Remote IO appliciation example Haiwell Cloud configuration communicates directly with H08TC module 1 1 Open Haiwell SCADA software select the new project choose to add...

Page 17: ...can see that when choosing to measure the temperature and humidity the analog input register does not appear two consecutive addresses such as the above channel 2 and 3 are connected to temperature h...

Page 18: ...ensor 4 how to replace broken module First let s look at the hardware wiring How to connect H32DT with the remote module tools of PLC software Hardware connection and power supply PC side USB transfer...

Page 19: ...rent temperature is 25 1 2 No 1 sensor serial number 3904 16A0 A719 FF28 that is 1 sensor serial number 3 Numerical 1250 indicates that the maximum value of engineering quantity displayed by the chann...

Page 20: ...sors we have to save the configuration parameters of H32DT module this step is very important The back will introduce the application occasions The specific operation is as follows in the menu bar of...

Page 21: ...default station number defaults to 1 and supports Modbus protocol So communication program is as follows The above introduce the normal use steps and methods for H32DT Then we will introduce how to d...

Page 22: ...through the remote module tool import the previous configuration table and finally click parameters download to download the parameters into the module The each position s temperature value and the se...

Page 23: ...ng to the 16 sensors in channel 2 so the communication program is as follows What is the role of configuring the number of sensors A If the number of sensors in the H32DT channel is less than the numb...