Haiwell PLC - Temperature & Humidity Module Application Case

22 / 23

If in the process of using, one of the temperature sensors is broken(any position), how to replace the sensor at this time?

A: The module does not need to be powered down, simply remove the damaged sensor, put a new one, then H32DT module will

automatically identify and determine it. The temperature read by new sensor will automatically replace the damaged sensor,
without affecting the other normal sensors' temperature acquisition.

If in the process of using, multiple temperature sensors are broken(any position, such as 3), how to replace these sensors at

this time?

A: Just remove these damaged sensors and replace them with new ones in order.
The sequence here that is described earlier, it means the sequence of access sensors at the beginning, from near to far or from

far to near. For example, the 16 sensors of channel 1 begin to be accessed from near to far in order, when using, the 2 #, 7 # and
13 # sensors are broken. At this point, the module need't power off, remove the 2 #, 7 #, 13 # sensors, put on new ones, according
to the sequence, first access to the original position 2 # sensor, then 7 #, and finally the sensor position 13 #. In this way, the
H32DT module will automatically identify and determine, the temperature values read by new sensors will automatically replace
the damaged sensor, without affecting the other normal sensors' temperature acquisition.

In a similar way, if accessing to sensors according to from far to near, then when replacing them also from far to near.

If in the process of using, H32DT module itself is damaged, at this time, how to deal with to make sure that the sensors

configured in front of are still the same order and can work normally?

A: The method for saving the module parameters was introduced in the previous section. Here you can use this configuration

parameter to reflect the importance of the H32DT module configuration parameters.

H32DT module is damaged, at this moment, we only need to import the previously saved module parameters to new H32DT

module through the remote module tool, import the previous configuration table, and finally click parameters download to
download the parameters into the module.

The each position's temperature value and the sequence of the module will be consistent with the previous module.This can be

very convenient to solve the replacement damaged modules problems.

The 4th point introduces the inportance of H32DT module parameter table, so does it mean that we should re-save a

parameter table every time after replacing the probe?

A: Yes. After replacement each time, save a copy, this is a very rigorous and safe operation.

In the actual application, how to clear the H32DT module parameter configuration?

A: There are two ways, one for software removal configuration and one for hardware removal configuration. The following

introduction:

Software removal configuration, click the default value in the channel without accessing any sensor, then click the parameter

download to clear the configuration (sensor serial number).

Hardware removal configuration, configuration can be cleared (sensor serial number) by powering off and powering on the module

for three times without accessing any sensor in the channel. The times of channel removal power-down configuration can be
viewed in CRC6H and CRC7H.

H32DT channel indicator on the module is 0 and 1, what are the states of always-on and flashing?

A: 0 and 1 always-on means that the channel is working normally, flashing indicates that the sensor is disconnected.

For H32DT module, how to do the channel sensor communication break alarm?

A: The digital temperature module parameter table shows, H32DT module communication break alarm register are CR32H

channel 1 and CR33H channel 2. So when extending through the parallel port, we can write the program as follows:

This example, the module is in the second lacation of hardware configuration, so in FROM instruction, we set Slot = 2,

hexadecimal 32H, that is, decimal 50, the V30V31 in the program respectively indicates channel 1 break alarm register and
channel 2 break alarm register . Through WTOB, we know that M100 ~ 115 as the break alarm status bits corresponding to 16
sensors in channel 1. M116 ~ 131 is the break alarm status bits corresponding to 16 sensors in channel 2, so the program is as

Summary of Contents for H04DT

Page 1: ...m Haiwell PLC Temperature Humidity Module User Manual Xiamen Haiwell Technology Co Ltd www haiwell com Haiwell PLC User Manual Programmable Logic Controller Temperature Humidity Module User Manual App...

Page 2: ...se 1 Expand module through the host PLC parallel port 10 1 1 Module power supply 10 1 2 Temperature modules need t be written any conversion program read the current temperature value directly when ac...

Page 3: ...35 0 5 6 7 8 9 10 11 12 0 1 2 3 4 5 6 7 AI AI LINK POW RT1 RT0M RT2M RT0 RT2 RT0 RT2 RT3M GND RT3 A RT1M B RT1 RT3 RS485 RT4M RT6M RT4 RT6 RT4 RT5M RT7 RT7 RT7M RT5 RT5 RT6 1 2 3 4 ON DIP H08RC 13 14...

Page 4: ...d maintenance Without serial or parallel port in communication Constant light in red With serial or parallel port in communication Red jitter quickly indicator on 30ms and off 30ms 3 RJ45 Ethernet ind...

Page 5: ...0 50 mV 0 100 mV Resolution 0 1 0 1 Input impedance 6M 6M Maximum input range 13V 30mA Input indication LED light ON means normal OFF means external disconnection Response time 560ms 4 Channel 880ms 8...

Page 6: ...code H32DTfunction description 00H Low byte for module code and high byte for module version number 01H Communication address 02H Communication protocol The low 4 bit of the low byte 0 N 8 2 For RTU...

Page 7: ...1 input value 11H channel 2 input value channel 2 input value 12H channel 3 input value channel 3 input value 13H channel 4 input value channel 4 input value 14H channel 1 signal type note 2 channel...

Page 8: ...note 5 21H channel 1 engineering lower limiting value channel 1 engineering lower limiting value 22H channel 2 engineering lower limiting value channel 2 engineering lower limiting value 23H channel...

Page 9: ...bit indicates 1 channel 0 normal 1 disconnection 5 5 Use the engineering value mark Each bit indicates 1 channel 0 No 1 Yes 9 Expansion modules installation The PLC should be secured to an enclosed c...

Page 10: ...dule is added external power supply it can still work this time the module will automatically determine and give priority to external power supply 1 2 Temperature modules need t be written any convers...

Page 11: ...uration that is the actual temperature value for example you can set 1 on decimal places of Haiwell Cloud SCADA settings So that when the PLC read AI0 value AI0 123 that is the actual value of 12 3 th...

Page 12: ...uted installation is very important for the system which needs to collect and monitor a large number of decentralized digital or analog signals temperature humidity differential pressure blowing rate...

Page 13: ...configured via programming software tools remote modules recommended 2 It can be configured via the hardware configuration and TO instructions when the module is hung behind the host PLC through the p...

Page 14: ...ameter configuration Click to exit enter the configuration interface as shown below We can change the module name address IP subnet mask baud rate data format and other communication parameters in the...

Page 15: ...ut values are stored in 10H 13H of H04RC module 3 PLC program Host PLC wants to read the 4 channel temperature values of remote IO module H04RC 4 channel temperature sensors for PT100 2000 8500 indica...

Page 16: ...ed in the V10 V17 as follows 1 8 Remote IO appliciation example Haiwell Cloud configuration communicates directly with H08TC module 1 1 Open Haiwell SCADA software select the new project choose to add...

Page 17: ...can see that when choosing to measure the temperature and humidity the analog input register does not appear two consecutive addresses such as the above channel 2 and 3 are connected to temperature h...

Page 18: ...ensor 4 how to replace broken module First let s look at the hardware wiring How to connect H32DT with the remote module tools of PLC software Hardware connection and power supply PC side USB transfer...

Page 19: ...rent temperature is 25 1 2 No 1 sensor serial number 3904 16A0 A719 FF28 that is 1 sensor serial number 3 Numerical 1250 indicates that the maximum value of engineering quantity displayed by the chann...

Page 20: ...sors we have to save the configuration parameters of H32DT module this step is very important The back will introduce the application occasions The specific operation is as follows in the menu bar of...

Page 21: ...default station number defaults to 1 and supports Modbus protocol So communication program is as follows The above introduce the normal use steps and methods for H32DT Then we will introduce how to d...

Page 22: ...through the remote module tool import the previous configuration table and finally click parameters download to download the parameters into the module The each position s temperature value and the se...

Page 23: ...ng to the 16 sensors in channel 2 so the communication program is as follows What is the role of configuring the number of sensors A If the number of sensors in the H32DT channel is less than the numb...

Reviews: