HL116DA/DA2/P

: If the difference between room temperature and set-point exceed (or 

under) 1

, FCU valve will be open; if room temperature are equal to set-point, the FCU valve will close with the fan still 

running.

 

"

 Control cooling-heating FCU Valve under 4-pipe configuration (HL116FCV2): In cooling Mode, when the room 

temperature is higher than set-point, the cooling valve will be opened. Otherwise it will be closed. Heating valve is always 

closed In heating, in heating Mode When the room temperature is lower than set-point, the heating valve will be opened. 

Otherwise it will be closed. Cooling valve is always closed. 

LOW TEMPERATURE PROTECTION 

"

 If thermostat is at shut state, and when room temperature is lower than 5

, thermostat will start valve for heating, 

HL116DA/DA2/P for electric motorized valve and HL116FCV2 for heating water valve respectively, when temperature 

returns to 7

 or above, it will close valve.   

SET LOW TEMPERATURE PROTECTION 

"

Turn off the thermostat, press “ ” until backlight is on and parameter setting is displayed with icon “

” and “00”, “01”, 

press “

S

” or “

T

” key to adjust. “00” indicates low temperature protection is invalid, “01” indicates low temperature protection 

function valid. The default is “00”. 

Caution: test Mode modification is prohibited while “F” is displayed in the middle of the LCD screen.   

WIRING DIAGRAMS 

 

 

 

 

 

 

 

 

 

 

 

 
 

MOUNTING 

 

Note: Be sure to connect all the wires as per the wiring diagrams and keep it away from water, mud 

and other material so as to prevent the unit being spoiled!

 

 
 
 
 
 
 
 
 
 

1. Open the front cover.   

 
 
 
 
 
 
 
 
 

2. Connect the wires follow the diagram.

 
 
 
 
 
 
 
 
 

3. Fix the base with screw. 

 
 
 
 
 
 
 
 
 

4. Fix the front panel and 

finish the installation. 

Valve 

HL116DA2

 

 

 

 

FAN-H

Fan 

AC 220V    50/60Hz

N L

FAN-M 

FAN-L 

VAL-NC/HEAT 

VAL-NO/COOL 

N

L

FAN-H

Fan 

Valve 

AC 220V    50/60Hz

N  L

FAN-M 

FAN-L 

VAL-NC/HEAT

VAL-NO/COOL

HL116P

 

 

 

 

AC 220V    50/60Hz

N  L 

HL116DA

 

 

 

 

FAN-H 

Fan 

VAL-NO/COOL 

FAN-M 

FAN-L 

Valve 

AC 220V    50/60Hz

N L

N

L

FAN-H

Fan 

VAL-NO/COOL

FAN-M 

FAN-L 

HL116FCV2/AFCV2

 

 

 

 

VAL-NC/HEAT

Val2 

VAl1 

FAN-H