background image

Open

No gas leakage?

5.

Detach the charge hose

6.

from the service port, open 2-way valve and 3-way. Turn

In case of gas leakage, tighten parts of pipe connection. If leakage stops,
then proceed

Anti countercurrent joint

Gaugemanifold(for R410A)

2-way valve Liquid Side

3-way valve Gas Side

Vacuum pump(for R410A)

Tube(for R410A)

Close

2-way valve

3-way valve

Open 90

O

2-way valve

3-way valve

2-way valve 3-way valve

2-way valve

3-way valve

Valve rod cap

Valve rod cap

Service port cap

To prevent the gas leakage,

After attaching each cap, check for gas leakage around the caps.

7.

8.

Step 1.

Step 2.

Step 3.

Step 7.

Step 6.

Step 4.

The power source must be exclusively used for air

ƽ

conditioner. (Over I0A)

In the case of installing an air conditioner in a moist place,

ƽ

please install an ea-

For installation in other places, use a circuit breaker as far

ƽ

as possible.

Pipe cutting is carried out with  a  pipe cutter and burs must

ƽ

be removed.

After inserting the flare nut, flaring work is carried out.

ƽ

If the refrigerant  of  the air conditioner leaks, it is necessary to discharge all the

ƽ

refrigerant. Vacuum first, then charge the liquid refrigerant into air conditioner
according to the amount marked on the name plate.

Please do not let other cooling medium, except specified one (R410A), or air

ƽ

enter into the cooling circulation system. Otherwise, there will be abnormal

high pressure in the system casuing damage and possibly personal injuries.

Power Source Installation

Cutting and Flaring Work of Piping

Flare tooling die

1.Cut pipe

2.Remove burs

3.Insert the flare nut

CAUTION

Flare tool for R410A

Conventional flare tool

Clutch-type

clutch-type(Rigid-type) Wing-nut type (Imperial-type)

A

0~0.5mm

1.0~1.5mm

1.5~2.0mm

rth leakage breaker (GFCI).

4.Flare pipe

Lean

Damage of flare Crack

Partial

Too outside

Correct

Incorrect

On Drainage

It becomes

high midway.

The gap with the

ground is too small

There is the bad
smell from a ditch

It waves.

The end is imm-
ersed in water.

Please install the drain hose so as to be downward slope without fail.
Please don’t do the drainage as shown below.

ƽ
ƽ

Please pour water in the drain pan  of  the indoor unit, and

ƽ

is carried out surely to outdoor.

In case that the attached drain hose is in a room, please

ƽ

apply heat insulation to

Less than

5cm

confirm that drainage

it without fail.

4

Check Items for Test Run

Put check mark

in boxes

Gas leak from

pipe

connecting

?

Heat insulation of 

Are the connecting wirings of indoor and outdoor firmly

Is the connecting wiring of indoor and outdoor firmly fixed?
Is drainage securely carried out?
Is the ground wire securely connected?
Is the indoor unit securely fixed?
Is power source voltage abided by the code?

Is there any noise?

Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performed normally?

Is the operation of room temperature regulator normal?

Please kindly explain to our customers how to operate
through the instruction manual.

Check for Installation and Test Run

Ƶ

inserted to the terminal block?

Ƶ

1

1+2=

kg

R410A

2

kg

2=

1=

B

C

D

F

E

kg

A

This product contains fluorinated greenhouse gases covered by 
the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type:R410A
GWP* value:1975
GWP=global warming potential
Please fill in with indelible ink,
• 1      the factory refrigerant charge of the product
• 2      the additional refrigerant amount charged in the field and
• 1+2  the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the stop valve cover).
A  contains fluorinated greenhouse gases covered by the Kyoto 
Protocol
B  factory refrigerant charge of the product: see unit name plate
C   additional refrigerant amount charged in the field
D   total refrigerant charge
E   outdoor unit
F   refrigerant cylinder and manifold for charging 

Contains fluorinated greenhouse gases
covered by the Kyoto Protocol

Refrigerant charge label

Ƶ

the valve stem counterclockwise.

step 6. If leak continues, remove the refrigerant used for the 

leakage check and flare tubes again. Repeat vacuum and leak and if no 
leakage, proceed to step 6.

replace the service port and valve stem caps securely.

pipe

connecting

?

0~1/51 inch

3/76 ~1/17 inch

1/17 ~1/8 inch

Summary of Contents for Room Air Conditioner

Page 1: ...n fitting the unit to wall ƽ surface roof or rooftop fix a supporter securely with nails or wires in consideration of earthquake and strong wind If vibration may affect the ƽ house fix the unit by attaching a vibration proof mat The marks from to in the figure are the parts numbers The distance between the indoor unit and the floor should be more than 2m The models adopt HCFC free refrigerant R410A mor...

Page 2: ...ld up ƽ the body at a slant from the underside and then put it down perpendicularly Connecting the indoor outdoor Electric Cable Removing the wiring cover Remove terminal cover at right bottom corner of indoor unit then take ƽ off wiring cover by removing its screws 1 Insert from outside the room cable into left side of the wall hole in which the pipe has already existed 2 Pull out the cable on th...

Page 3: ... and 2 operate vacuum pump If the low 3 After the completion of vacuuming close the handle Lo in gaugemanifold and stop the operation of the vacuum pump Attaching Drain Elbow Purging Method To use vacuum pump Open the valve rod stem the 2 way valve counterclockwise to 90 degrees 4 After 6 seconds close the 2 way valve and inspect for gas leakage Power cable HSU12VHJ DB W Outdoor unit 3 2 Power Wir...

Page 4: ... Please don t do the drainage as shown below ƽ ƽ Please pour water in the drain pan of the indoor unit and ƽ is carried out surely to outdoor In case that the attached drain hose is in a room please ƽ apply heat insulation to Less than 5cm confirm that drainage it without fail 4 Check Items for Test Run Put check mark in boxes Gas leak from pipe connecting Heat insulation of Are the connecting wiri...

Page 5: ... generado por la unidad no cause una molestia a los vecinos Coloque la unidad en un lugar en el que pueda disponerse de la distancia de separación marcada en la figura anterior Herramientas necesarias para realizar la instalación Fuente de alimentación Selección del lugar de instalación diagrama de instalación de unidades interiores y exteriores Los modelos cumplen la norma R410A sobre refrigerante...

Page 6: ...per los tubos al doblarlos Conecte previamente el cable eléctrico de interior exterior y tire de la conexión al aislante de calor del componente de conexión Conexión de los cables eléctricos de interior exterior Accesorios Selección de tubo Al fijar por primera vez la placa de montaje Orificio de pared Ø70mm Cara interior Grosor de la pared Cara exterior Manguera de drenaje Fijación de la unidad int...

Page 7: ...realizada por un ingeniero profesional en aire acondicionado Antes de añadir refrigerante adicional realice una purga de aire desde los tubos refrigerantes y la unidad interior utilizando una bomba de vacío y cargue después el refrigerante adicional PRECAUCIÓN Unidad interior Unidad exterior Filtro de aceite Unidad exterior Elevación máx Amáx 10m En caso de que la elevación A sea superior a 5m el ...

Page 8: ...invernadero regulados por el Protocolo de Kioto B Carga de refrigerante que contiene el producto de fábrica consulte la placa de características de la unidad C Cantidad de refrigerante adicional cargada durante la instalación D Carga total de refrigerante E Unidad exterior F Botella de refrigerante y colector de carga Prueba de instalación y ejecución de la prueba Explique al cliente cómo utilizar...

Page 9: ... un emplacement où le vent et le bruit ne risquent pas de gêner les voisins Choisir un endroit dans lequel les distances marquées illustrées dans le schéma ci dessus sont disponibles Outillage requis pour l installation Source d alimentation Sélection de l emplacement pour l installation schéma d installation des unités intérieures et extérieures Les modèles utilisent le réfrigérant R410A sans HCF...

Page 10: ... et cintrez ensuite le tuyau selon la position du trou dans le mur Lors du cintrage prenez soin de ne pas écraser les tuyaux Connectez au préalable le câble des unités intérieures extérieures et recouvrez ensuite les câbles connectés avec l isolation Connexion du câble des unités intérieures extérieures Accessoires Sélection du tuyau Lorsque la plaque de fixation est installée pour la 1e fois Trou ...

Page 11: ...outefois la charge de réfrigérant doit être exécuté par un professionnel de la climatisation Avant d ajouter du réfrigérant purgez l air des tuyaux de réfrigération et de l unité intérieure avec pompe à vide Chargez AVERTISSEMENT Unité intérieure Unité extérieure Piège dl huile Unité extérieure Hauteur max Amax 10m Si la hauteur A dépasse les 5m installez un piège à huile tous les 5 à 7 m Longueur...

Page 12: ... unité voir sur la plaque signalétique de l unité C Quantité supplémentaire de réfrigérant chargée sur place D Charge totale de réfrigérant E Unité extérieure F Cylindre réfrigérant et collecteur de chargement Vérification de l installation et test de fonctionnement Expliquez le fonctionnement à vos clients en vous servant du manuel Cochez les cases Fuite de gaz dans le raccordement du tuyau Isolat...

Reviews: