background image

Indoor unit

1.Fitting of the Mounting Plate and Positioning of the wall Hole

2.Making a Hole on the Wall and Fitting the Piping Hole Cover

When the mounting plate is first fixed

When the mounting plate is fixed side bar and lintel

1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be

   fixed against the wall, then temporarily fasten the plate with one steel nail.

2. Make sure once more the proper level of the plate, by hanging a thread with a weight from

    the central top of the plate, then fasten securely the plate with the attachment steel nail.

3. Find the wall hole location A using a measuring tape

Refer to the previous article, "    When the mounting plate is first fixed   ", for the

position of wall hole.

Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten
the plate to the fixed mounting bar.

Make a hole of 60 mm in diameter,
slightly descending to outside the wall.
Install piping hole cover and seal it
off with putty after installation

(Section of wall hole)

Piping hole pipe

Outdoor side

Thickness

of wall

Indoor side

Wall hole

60mm

3.Installation of the Indoor Unit

Drawing of pipe

[ Rear piping ]

Draw pipes and the drain hose, then fasten them with the adhesive tape

[ Left Left-rear piping ]

In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear
piping which is marked on heat insulation materials.

3

G

Indoor unit

A=137mm

B= 6

0

mm

30mm

Summary of Contents for HSU-18CRA03-T

Page 1: ...Drain hose Heating insulating material Piping hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance betw...

Page 2: ...ptacle with enough space around Refer to drawings Place where the distance of more than lm from televisions radios wireless apparatuses and fluorescent lamps can be left In the case of fixing the remo...

Page 3: ...ticle When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a...

Page 4: ...ody aslant from the underside and then put it down perpendicularly 1 Insert the drain hose into the dent of heat insulation materials of indoor unit 2 Insert the indoor outdoor electric cable from bac...

Page 5: ...h the wiring cover Note When connecting the cable confirm the terminal number of indoor and outdoor units carefully If wiring is not correct proper operation can not be carried out and will cause defe...

Page 6: ...wiring is not correct proper operation can not be carried out and controller may be damaged If the drain elbow is used please attach it as figure Note Only for heat pump unit Drawing for the installat...

Page 7: ...ing to the following list Piping length Additional amount 5m 7m No need 40g 10m 100g for 9k 12k 18k Push the air out of the indoor unit and piping as followes 1 Remove the valve cap on 2 way valve in...

Page 8: ...pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly expla...

Reviews: