31-5000788   Rev. 0

17

Step 3 - Installation of the Outdoor Unit (Cont.)

E.  System Evacuation

NOTE–

 Do not open service valve.

•  Attach a manifold gauge, micron gauge, and vacuum 

pump to the suction line port using adapter AD-87 
(see illustration).

•  Evacuate the system to at least 350 microns.

•  Close the vacuum pump valve and allow temperature 

to stabilize. Check micron gauge. If the gauge 
rises 150 microns in 60 seconds, the evacuation is 
incomplete or there is a leak in the system. If the 
gauge does not rise 150 microns in 60 seconds, the 
evacuation is complete.

•  Once evacuation is complete, remove the adapter 

and hose connection from the suction line port and 
dry the area before reinstalling the cap. Freezing 
conditions with soap solution still on the valve could 
cause damage.

CAUTION

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

A

B

•  Max. Elevation: A Max =  

100ft / 30m (24k / 3036k / 4248k)

•  In case the height of A is more than 15ft / 5m, an oil 

trap should be installed every 16-23ft /5-7m

D.  Leak Test 

•  Remove the cap on the service valve.

•  Using a tank of dry nitrogen and approved regulator, charge 

the system with 150 psig of dry nitrogen using mini-split 
adapter to connect the valve. 

•  Check for leaks at the flare fittings using soap bubbles 

or another detection device.  If a leak is detected, make 
repairs to the fittings and recheck. Proceed if no leaks are 
detected within 3 minutes.

•  Using the same tank/regulator, charge the system to  

300 psig.

•  Check for leaks as earlier. Proceed if no leaks are detected 

within 3 minutes.

•  Using the same tank/regulator, charge the system to  

500 psig.

•  Check for leaks as earlier.  Keep system pressurized for at 

least 20 minutes.

WARNING

 Do not use acetylene, oxygen or 
compressed air or mixtures containing air, 

oxygen, or combustible gases for pressure testing.  Do not 
use mixtures of hydrogen containing refrigerant and air above 
atmospheric pressure for pressure testing as they may 
become flammable and could result in an explosion.  
Refrigerant, when used as a trace gas, should only be mixed 
with dry nitrogen for pressurizing units.  Failure to follow 
these recommendations could result in death or serious injury 
as well as equipment or property damage.

Model Number

Factory 
Charge

Pipe 

Length 

of 

factory 
charge

Additional 

charge 

rule*

System 

Maximum 

pipe 

length

System 

Minimum 

pipe 

length

Unit

oz

ft

oz/ft

ft

ft

ASH124UCDDA

85

25

0.5

165

10

ASH3036UCDDA

88

ASH4248UCDDA

141

230

Installation Instructions

Summary of Contents for GE ASH124UCDDA

Page 1: ...allation est uniquement imprim en anglais Pour la version fran aise ou espagnole visitez le site GEAppliancesairandwater com El dise o puede variar seg n el n mero de model Este manual de instalaci n...

Page 2: ...his manual contains installation instructions for outdoor and highwall indoor units For the applications using other style indoor units please refer to the Installation Manual supplied with the corres...

Page 3: ...bo Mode It is recommended to have a secondary heating source s available in case the temperature drops below the operating range Install Wind Baffle to expand cooling operating range to 4F 115F ______...

Page 4: ...with contaminants Improper line sizing will degrade performance Peak pressure of R410A is much higher than R22 Use copper tubing with adequate wall thickness To prevent breaking of the pipe avoid sha...

Page 5: ...s not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction con...

Page 6: ...urface int rieure Autrement des contaminants peuvent bloquer le d tendeur ou le tube capillaire Un dimensionnement incorrect de la tuyauterie diminue le rendement Les pointes de pression du r frig ran...

Page 7: ...responsable de leur s curit Les enfants doivent tre surveill s afin de s assurer qu ils ne jouent pas avec l appareil Pour pr venir le risque de suffocation gardez l cart des enfants les sacs ou les p...

Page 8: ...Stud finder Torque wrench Vacuum pump Wire strippers All usual and customary HVAC hand and power tools meters and testing devices consumable INDOOR CLEARANCES Appearance may vary This picture is for r...

Page 9: ...Contact GEA Ductless for assistance if the above conditions cannot be met WIND BAFFLE AND SNOW HOOD INSTALL If the outdoor unit is installed in a region that affected by strong wind it is recommended...

Page 10: ...ve16 400 Above16 400 Above80 2000 Above12 300 Above 40 1000 Above 177 4500 Above 24 600 If wall is half the height of the unit 8 250 If wall is between half the height of the unit and the same height...

Page 11: ...the unit s power communication wiring at least 10 feet away from television and radio sets to prevent interference Ensure any moisture sensitive items are kept away from the condensate drain path of...

Page 12: ...installed as high on the wall as possible but allow a minimum of 4 from the ceiling Use a stud finder to locate and mark stud locations for mounting and to prevent unnecessary damage to the wall Inst...

Page 13: ...minal plate and the plate is tightened Ensure the 14 4 cable is secured under the strain relief bracket After the terminal block wiring is completed replace both cover plates and lower the front casin...

Page 14: ...to cut the hole for piping NOTE Some models may not have a cardboard template in this case a manual measurement is needed to determine the piping hole location When mounting the unit use a stud finde...

Page 15: ...n a solid foundation 8 above the highest snowfall Correct Installation Drainage D H Correct Installation Minimum height H should be higher than the highest snowfall depth D H D 8 D H Incorrect Install...

Page 16: ...an result in control board damage and communication issues E7 error code This includes improper wire size use of solid core wire midline splicing and poor terminal connections C Install Copper Lineset...

Page 17: ...dry nitrogen using mini split adapter to connect the valve Check for leaks at the flare fittings using soap bubbles or another detection device If a leak is detected make repairs to the fittings and...

Page 18: ...a sealant to seal the piping on both sides of the wall in order to prevent drafts weather or pests from entering the building This product contains fluorinated greenhouse gases covered by the Kyoto P...

Page 19: ...ces a Haier company e g a used and or unapproved condenser air handler Component or parts are not provided by GE Appliances a Haier Company Product that has been moved from its original installation t...

Page 20: ...e the remainder of the Standard Base Warranty The remedy provided in this warranty is exclusive and is granted in lieu of all other remedies This warranty does not cover incidental or consequential da...

Page 21: ...31 eWDSH 9pUL FDWLRQ QDOH 35 GARANTIE LIMIT E 37 Nous vous remercions de votre achat de ce produit GE Appliances Ce manuel d installation vous aidera obtenir le meilleur rendement de votre nouvelle un...

Page 22: ...urface int rieure Autrement des contaminants peuvent bloquer le d tendeur ou le tube capillaire Un dimensionnement incorrect de la tuyauterie diminue le rendement Les pointes de pression du r frig ran...

Page 23: ...responsable de leur s curit Les enfants doivent tre surveill s afin de s assurer qu ils ne jouent pas avec l appareil Pour pr venir le risque de suffocation gardez l cart des enfants les sacs ou les p...

Page 24: ...pe vide Pinces d nuder Tous les outils les appareils de mesure et les appareils d essai HVAC habituels et usuels consommables D GAGEMENTS INT RIEURS L aspect peut varier Cette illustration est pour r...

Page 25: ...crites ci dessus ne peuvent tre satisfaites Murs de protection Unit ext Unit ext Brise marine Mer Unit ext Unit ext Unit ext Brise marine Brise marine Mer Mer INSTALLATION DU D FLECTEUR DE VENT ET DU...

Page 26: ...12 300 Above 40 1000 Above 16 400 Above 16 400 Above 16 400 Above16 400 Above16 400 Above80 2000 Above12 300 Above 40 1000 Above 177 4500 Above 24 600 If wall is half the height of the unit 8 250 If...

Page 27: ...l viseurs et radios afin de pr venir les perturbations Assurez vous de garder les articles sensibles l humidit l cart du chemin d vacuation du condensat de l unit ext rieure REMARQUES L unit ext rieu...

Page 28: ...es Des ancrages muraux sont fournis s il y a impossibilit d aligner tous les trous de vis sur les goujons V rifiez que la plaque de montage a t fix e solidement et que le poids est distribu uniform me...

Page 29: ...uez les connexions chaque borne selon le sch ma de c blage Notez la couleur du fil chaque borne et assure vous que les fils connect s l unit ext rieure correspondent Assurez vous que chaque fil se tro...

Page 30: ...en carton n est pas fourni avec certains mod les Il faudra alors effectuer manuellement les mesures afin de d terminer l emplacement du trou pour la tuyauterie Pendant le montage de l unit utilisez u...

Page 31: ...sur une base solide 8 au dessus de la moyenne des chutes de neige Installation correcte vacuation D H Installation correcte Hauteur minimale H doit tre sup rieure la profondeur de neige maximale P H...

Page 32: ...ndard du jeu de tuyaux est de 25 pieds 7 6 m Si la longueur de l installation est diff rente ajustez la charge de r frig rant en ajoutant 0 2 oz pi si le tuyau de liquide est de 1 4 po ou de 0 5 oz pi...

Page 33: ...d tection Si une fuite est d tect e effectuez les r parations aux raccords et v rifiez de nouveau Proc dez si aucune fuite n est d tect e sous 3 minutes Si vous utilisez le m me r servoir r gulateur c...

Page 34: ...e l orifice de charge sous la plaque de recouvrement de l unit ext rieure Si l tiquette est absente inscrivez les quantit s sur l unit ext rieure l aide d un marqueur permanent au dessus de l orifice...

Page 35: ...cit local Des bruits irr guliers se font ils entendre La temp rature de refroidissement descend elle entre 20 et 30 F 6 7 et 1 1 C La temp rature de r chauffementmonte t elle entre 35 et 40 F 1 7 et 4...

Page 36: ...36 31 5000788 Rev 0 Remarques...

Page 37: ...s similaires Un Produit qui n a pas t install ou r par par un technicien agr en chauffage ventilation et climatisation La main d uvre et les services connexes pour la r paration ou l installation du P...

Page 38: ...is dans cette garantie est exclusif et il est accord en remplacement de tout autre recours Cette garantie ne couvre pas les dommages accessoires ou indirects Certains tats ou provinces ne permettent p...

Page 39: ...er a la garant a del compresor y de las piezas por 10 a os es necesario realizar un registro dentro de los 60 d as desde el momento de la instalaci n En la siguiente informaci n figura un listado del...

Page 40: ...es El tama o inadecuado de una tuber a degradar el rendimiento El pico de presi n del R410A es muy superior al del R22 Use tuber as de cobre con un grosor de pared adecuado A fin de evitar la rotura d...

Page 41: ...ni os deber n ser supervisados para asegurar que no se juegue con el electrodom stico A fin de evitar el riesgo de sofocaci n mantenga la bolsa pl stica o la pel cula fina usada como material de embal...

Page 42: ...ntas medidores y dispositivos de prueba HVAC de uso habitual consumible ESPACIOS INTERIORES El aspecto puede variar Esta imagen s lo sirve como referencia El aspecto de su producto podr ser diferente...

Page 43: ...less para solicitar asistencia Unidad de Exterior Brisa marina Brisa marina Mar Mar Unidad de Exterior Unidad de Exterior Paredes Protectoras Brisa marina Mar Unidad de Exterior Unidad de Exterior INS...

Page 44: ...12 300 Above 40 1000 Above 16 400 Above 16 400 Above 16 400 Above16 400 Above16 400 Above80 2000 Above12 300 Above 40 1000 Above 177 4500 Above 24 600 If wall is half the height of the unit 8 250 If...

Page 45: ...comunicaci n por lo menos a 10 pies de distancia de los equipos de televisi n y radio a fin de evitar interferencias Aseg rese de que cualquier tem sensible a la humedad sea mantenido lejos del camin...

Page 46: ...l uso de un jab n como lubricante y un destornillador peque o permitir n un posicionamiento m s f cil del tap n Perfore el agujero del conjunto de cables con una sierra de agujero de 2 1 4 Angule el t...

Page 47: ...en cada terminal de acuerdo con el diagrama del cableado Tome nota del color del cable en cada terminal y aseg rese de que los cables se encuentren conectados a la unidad de exterior de forma consecue...

Page 48: ...e que algunos modelos no cuenten con una plantilla de carb n en este caso ser necesaria una medici n manual para determinar la ubicaci n del agujero de la tuber a Al montar la unidad use un buscapolos...

Page 49: ...re una base s lida 8 por encima de la nevada promedio Instalaci n correcta Desag e D H Instalaci n correcta La altura m xima H deber ser superior a la profundidad de ca da de nieve m xima D H D 8 D H...

Page 50: ...del juego de tuber as es de 25 pies Si la longitud de instalaci n es diferente ajuste la carga de refrigerante agregando 0 2 onzas pie si la tuber a de l quido es de o en 0 5 onzas pie si la tuber a d...

Page 51: ...itud m xima de la tuber a del sistema Longitud m nima de la tuber a del sistema Unit oz ft oz ft ft ft ASH124UCDDA 85 25 0 5 165 10 ASH3036UCDDA 88 ASH4248UCDDA 141 230 D Prueba de P rdidas Retire la...

Page 52: ...la v lvula en la casilla de suma D Adhiera la etiqueta completada en la proximidad con el Puerto de carga del producto y debajo de la placa de la tapa de las unidades exteriores Si no encuentra el adh...

Page 53: ...s el voltaje de la fuente de alimentaci n el correcto de acuerdo con el c digo local Hay alg n ruido extra o Descendi la temperatura de enfriamiento a entre 20 y 30 F Ascendi la temperatura de calefac...

Page 54: ...Da o resultante de inundaciones incendios viento iluminaci n accidentes o condiciones similares Un producto que no fue instalado o su servicio t cnico no fue realizado por un t cnico con licencia de H...

Page 55: ...s La soluci n provista en esta garant a es exclusiva y es garantizada en lugar de todas las dem s soluciones Esta garant a no cubre da os incidentales o consecuentes Algunos estados y provincias no pe...

Page 56: ...uese al 877 337 3639 para solicitar el nombre y n mero telef nico del centro de servicio al cliente autorizado m s cercano NECESITA UNA PRUEBA DE COMPRA FECHADA N MERO DE MODELO Y DE SERIE PARA EL SER...

Reviews: