background image

Page  20

31-5000752   Rev. 0

Before final adjustment is made to the refrigerant charge, 

it is imperative that proper indoor airflow be established. 

Airflow will be higher across a dry coil versus a wet coil. 

Blower charts are calculated with a dry or wet coil basis. 

Recommended  airflow  is  350-450  CFM  per  ton  (12,000 

Btuh) through a wet coil. Refer to indoor unit instructions for 

methods of determining air flow and blower performance.

The optimum method for checking the charge is by 

weight. However the following methods may be used 

to confirm the proper charge:

Cooling Mode

1. 

Operate unit a minimum of 10 minutes before checking 

charge.

2. 

Measure liquid service valve pressure by attaching an 

accurate  gage  to  service  port.  Determine  saturation 

temp. from T/P chart.

3. 

Measure  liquid  line  temperature  by  attaching  an 

accurate thermistor type or electronic thermometer to 

liquid line near outdoor coil.

4. 

Calculate  subcooling  (saturation  temp.  measured 

temp.) and compare with table on back of central box 

cover.

5. 

Add  refrigerant  if  subcooling  is  lower  than  table. 

Recover refrigerant if subcooling is high.

6. 

If ambient temp is lower than 60°F, check charge in 

heating mode or weigh refrigerant according to name 

plate data.

Heating Mode

Check charge in heating mode if ambient temp is below 

60° F. Indoor temp must be between 65° and 75° F.

Follow  steps  (1)  to  (6)  above  and  compare  with  heating 

mode subcooling range on the table on back of central box 

cover.

Charge  must  be  rechecked  again  during  the  cooling 

season.

Cold Weather Application

A  cold  weather  accessory  kit  may  be  required  for  heat 

pumps  operating  at  ambient  conditions  below  25°F. 

Supplemental heat should be provided for these conditions.

Operation

Pressure Switch Connections

The unit’s automatic reset pressure switches (LO PS - S87 

and HI PS - S4) are factory-wired into the control board on 

the LO-PS and HI-PS terminals, respectively.

Low Pressure Switch (LO-PS)

When the low pressure switch trips, the control board will 

cycle  off  the  compressor,  and  the  strike  counter  in  the 

board  will  count  one  strike.  The  low  pressure  switch  is 

ignored under the following conditions:

• 

during  the  defrost  cycle  and  90  seconds  after  the 

termination of defrost

• 

when  the  average  ambient  sensor  temperature  is 

below 15° F (-9°C)

• 

for 90 seconds following the start up of the compressor 

• 

during “test” mode

High Pressure Switch (HI-PS)

When  the  high  pressure  switch  trips,  the  control  board 

will cycle off the compressor, and the strike counter in the 

board will count one strike.

Pressure Switch Settings

•  High Pressure (auto reset)

 - trip at 590 psig; reset 

at 418.

•  Low Pressure (auto reset)

 - trip at 25 psig; reset at 

40.

5-Strike Lockout Feature

The internal control logic of the board counts the pressure 

switch  trips  only  while  the  Y1  (Input)  line  is  active.  If  a 

pressure switch opens and closes four times during a Y1 

(Input), the control logic will reset the pressure switch trip 

counter to zero at the end of the Y1 (Input). If the pressure 

switch opens for a fifth time during the current Y1 (Input), 

the control will enter a lockout condition.

The 5-strike pressure switch lockout condition can be reset 

by cycling OFF the 24-volt power to the control board or by 

shorting the TEST pins between 1 and 2 seconds. All timer 

functions (run times) will also be reset.

If a pressure switch opens while the Y1 Out line is engaged, 

a 5-minute short cycle will occur after the switch closes.

Demand Defrost System

The  demand  defrost  system  measures  differential 

temperatures  to  detect  when  the  system  is  performing 

poorly  because  of  ice  build-up  on  the  outdoor  coil.  The 

system  “self-calibrates”  when  the  defrost  system  starts 

and after each system defrost cycle. The demand defrost 

components on the control board are listed below.

NOTE: 

The demand defrost system accurately measures 

the performance of the system as frost accumulates on the 

outdoor coil. This typically will translate into longer running 

time between defrost cycles as more frost accumulates on 

the outdoor coil before the board initiates defrost cycles.

Summary of Contents for GE APPLIANCES NS17HS

Page 1: ...31 5000752 Rev 0 11 22 GEA READ CAREFULLY KEEP THESE INSTRUCTIONS NS17HS SINGLE STAGE HIGH EFFICIENCY SPLIT SYSTEM HEAT PUMP UP TO 17 SEER 9 5 HSPF UP TO 16 SEER2 8 5 HSPF2 Service Manual...

Page 2: ...al for personal injury or death Electric shock hazard Can cause injury or death Before attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch es Un...

Page 3: ...53 33 9 50 25 0 120 0 2 6 1 3 825 NS17H60SA4 208 230 60 1 197 253 32 5 50 23 9 124 5 2 6 1 3 825 UNIT DIMENSIONS IN Model Dimensions inch Shipping Weight lbs A Width B Depth C Height NS17H18SA4 28 25...

Page 4: ...146 H4TXV02 7 8 3 8 7 8 3 8 7 8 3 8 NS17H60SA4 164 H4TXV03 1 1 8 3 8 1 1 8 3 8 7 8 3 8 Factory charged for 15 feet of line set adjust per installation instructions Field supplied adapter required COO...

Page 5: ...ompressors usually do not require hard start maybe needed for utility brown out or low voltage areas 42 48 60 81J69 Crankcase Heater 18 24 30 93M04 Prevents liquid migration to compressor in cold weat...

Page 6: ...e 6 31 5000752 Rev 0 FAN BLADE SPECS 4SHP17LE 51 Fan Blade Dia of Blades Pitch Part 18 22 2 24 23C06 24 22 2 24 23C06 30 22 2 24 23C06 36 26 3 24 23V42 42 26 3 29 23V43 48 26 3 29 23V43 60 26 3 29 23V...

Page 7: ...Page 7 31 5000752 Rev 0 Figure 1 Typical Parts Arranegment Figure 2 Typical Parts Arranegment...

Page 8: ...the outdoor section To reduce the possibility of noise transmission the foundation slab should NOT be in contact with or be an integral part of the building foundation See Figure 3 General Read this e...

Page 9: ...rhang is 36 NOTE At least one side should be unobstructed by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 Figure 4 NOTE See Table 2 for specific minimum clearance guidelines D...

Page 10: ...enced burnout it is recommended that the existing line set and indoor coil be replaced NOTE Refrigeration Piping Use only refrigerant grade copper tubes Split systems may be installed with up to 50 fe...

Page 11: ...STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices should be used if line set is to be installed on...

Page 12: ...instructions Figure 5 1 Connect gauges and equipment as shown in Figure 5 2 Set the recovery machine for liquid recovery and start the recovery machine Open the gauge set valves to allow the recovery...

Page 13: ...sing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 I...

Page 14: ...side to liquid line service valve service port B Connect gauge set center port to bottle of nitrogen with regulator C Remove core from valve in vapor line service port to allow nitrogen to escape NITR...

Page 15: ...INT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and copper...

Page 16: ...ve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to...

Page 17: ...frigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Reinst...

Page 18: ...er may result in property damage Size wiring and circuit breaker s per Product Specifications and unit rating plate WARNING ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostaticdischarg...

Page 19: ...th nameplate rating Field wiring connections are tight and factory wiring has not been disturbed and are tight Indoor fan motor is on correct speed tap 2 Set thermostat selector switch to OFF and fan...

Page 20: ...When the low pressure switch trips the control board will cycle off the compressor and the strike counter in the board will count one strike The low pressure switch is ignored under the following con...

Page 21: ...de Heating and cooling operation will be allowed in this fault condition NOTE The coil temperature probe is designed with a spring clip to allow mounting to the outside coil tubing Coil sensor locatio...

Page 22: ...the control board will initiate a defrost cycle Actuation When the reversing valve is de energized the Y1 circuit is energized and the coil temperature is below 35 F 2 C the board logs the compressor...

Page 23: ...rform demand or time temperature defrost operation System will still heat or cool ON ON Fault Demand Defrost Control Failure Indicates that demand defrost control has internal component failure Cycle...

Page 24: ...jumper is installed on the DELAY pins the compressor will be cycled off for 30 seconds going in and out of the defrost mode Units are shipped with jumper installed on DELAY pins NOTE The 30 second off...

Page 25: ...nser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Damaged or bent fins may affect unit operation Figure 9 Removing Louvers Remove two screws at top...

Page 26: ...conditions that may cause panels to be blown around and battered WARNING REMOVAL STEP 1 INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE STEP 2 PANEL INSTALLA...

Page 27: ...available in various configurations from different manufacturers The information below is typical for most thermostats Ask your dealer for specific information regarding the model of thermostat instal...

Page 28: ...T OPERATE CONTACT YOUR SERVICING DEALER Be sure to describe the problem and have the model and serial numbers of the equipment available If warranty replacement parts are required the warranty must be...

Page 29: ...Page 29 31 5000752 Rev 0 Figure 11 Typical Factory Wiring 018 through 036 models...

Page 30: ...Page 30 31 5000752 Rev 0 Figure 12 Typical Factory Wiring 042 through 060 models...

Page 31: ...Page 31 31 5000752 Rev 0 Figure 13 Wiring Diagram 018 036 Models...

Page 32: ...Page 32 31 5000752 Rev 0 Figure 14 Wiring Diagram 042 060 Models...

Page 33: ...IENT TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4...

Page 34: ...TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4 CHEC...

Page 35: ...IENT TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4...

Page 36: ...RATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4 CHECK AIR...

Page 37: ...AMBIENT TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTIN...

Page 38: ...OW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM SETTING 4 CHECK AIR FLOW AND RUN...

Page 39: ...E 1 IF AMBIENT TEMPERATURE IS BELOW 65 F CHARGE THE SYSTEM IN HEATING MODE 2 ALL HEAT PUMPS HAVE FACTORY INSTALLED OUTDOOR TXV 3 START THE SYSTEM IN HEATING AND RAISE THE THERMOSTAT SETTING TO MAXIMUM...

Page 40: ...less than 15ft subtract this amount see Installation Instructions for more details Charge Using the Weigh in Method If the system is void of refrigerant locate and repair any leaks evacuate system and...

Page 41: ...o charge shown on unit nameplate Indoor Matchup Subcool Additional Charge Heat 5 F Cool 1 F lbs oz 3 0 Ton HP NAM36P1 15 8 1 lb 2 oz NAM30P1 14 7 1 lb 6 oz NAM36E1 15 8 1 lb 2 oz NAM36V2 17 8 1 lb 1 o...

Page 42: ...__________________________________________ Rated LoadAmpacity ________________ Compressor _______________________ Outdoor Fan ________________________ Maximum Fuse or Circuit Breaker _________________...

Page 43: ...Page 43 31 5000752 Rev 0 Notes...

Page 44: ...Printed in the U S A All specifications and illustrations subject to change without notice and without incurring obligations...

Reviews: