10.  The operation method of fan controller

Through the fan controller switch in the electric box, the air volume of this unit can be continuously
adjusted.
It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment).
The air volume set should be in the operation air volume range.

Figure I shows the position of fan controller in the electric box and operation method.

After finishing the electric work, perform test run. According to the main points in Figure II making the
chosen switch No. accordant. And confirm if it reaches the needed air volume.

Note:

1) When operating the fan controller, it is possible to touch the electric charging part, so do cut off the
power supply.

2) Do not set the dial at the position less than 1.

3) The figure circled in Figure II indicate the capacity number of fan controller. The non-listed capacity
number may exceed the permitted operation capacity range, so it is impossible to operate.

4) When delivering from factory, the capacity number of fan controller is set at ìNo.5î.

Rotate this switch

(capacity number
setting:
No. 1 ~ No. 8)

Once the fan controller
has trouble, this linker
can perform emergency
assistant control. When
this linker is connected
to the linker from the
PCB, it can operate with
total load.

When this linker is
connected to the linker
from the PCB, through
the fan speed adjustment
panel to adjust speed.

High

Condition of standard air volume

Low

(air volume 100Pa)

Outer static pressure Pa

Example of
duct

Lower limit

Upper limit

Standard air volume

(m

3

/min)

The example of the method of choosing capacity number:

1) If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m

3

/min

as working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number
of fan controller is No. 2.

2) If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m

3

/min as

working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number
of fan controller is No. 4.

INSTALLATION MANUAL FOR INDOOR UNIT

200

150

100

50

0

26

30

34 35

40

43

*

*

*

*

*

*

*

*

* *

*

*

*

*

Figure 1

Figure 2

Summary of Contents for AD96NAHAEA

Page 1: ...INSTRUCTION MANUAL No 0010575976 DUCT TYPE AIR CONDITIONER AD96NAHAEA AU96NATAEA...

Page 2: ...10 CARE AND MAINTENANCE 11 FOR PREPARATION OF HEATING 12 IS THE UNIT INSTALLED CORRECTLY 13 INSTALLATION MANUAL FOR INDOOR UNIT 13 21 SAFETY PRECAUTIONS 3 5 PARTS AND FUNCTIONS 6 CAUTIONS 2 INSTALLAT...

Page 3: ...an appropriate anti pollution method of disposal Disposal of the packaging of your new air conditioner All the packaging materials employed in the package of your new air conditioner may be disposed w...

Page 4: ...ident by some improper handing Do not install nearby the place where may have leakage of flammable gas Depending on the place of installation a circuit breaker may be necessary Drain pipe should be ar...

Page 5: ...of such equip ment which generates steam condensed water may drip during cooling operation or it could cause a fault current or short circuit When operating the system simultaneously with a combustio...

Page 6: ...2 All the cables shall have got the European authentication certificate During installa tion when the connecting cables break off it must be assured that the grouding wire is the last one to be broken...

Page 7: ...PARTS AND FUNCTIONS 6 Indoor Unit Air outlet Air inlet Air inlet Duct Duct Drainpipe Air outlet Air inlet...

Page 8: ...r inlet or outlet Cooling is not sufficient Isn t sun shine invading direct Isn t any unexpected heating load generated Isn t the room much crowded Isn t the swing louver horizontal At HEATING mode If...

Page 9: ...ched into the FAN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it is sometimes automatically switched to the FAN mode but it will soon return to the co...

Page 10: ...o not open the inlet grill until fan stops completely Fan will continue rotating for a while by the law of inertia after operation is being stopped CAUTION Pre Season Care See that there are no obstac...

Page 11: ...ver to ordinary heating operation WARMING OPERATION Heat pump type warming Defrosting operation Atmospheric temperature and warming capacity Period of warm up With the heat pump type warming the mecha...

Page 12: ...t spring area etc The place where salt breeze blows Seaside etc The place where dense soot smoke exists The place where humidity is extraordina rily high The place where near the machine which radiate...

Page 13: ...fficiently support heavy weight When strength is insufficient injury can result from a falling of the unit Execute the prescribed installation construction to prepare for earthquakes and the strong wi...

Page 14: ...ape 2 Choose installation place 1 The chosen installation place should meet the following requirements and get the user s consent Place ensures ideal airflow distribution The passage of airflow has no...

Page 15: ...ult to the builder 3 Hanger bolts installation Use care of the piping direction when the unit is installed Hanging bolt M10 Hole in anchor Hole in plug Insert Concrete Use M10 screw bolt In order to b...

Page 16: ...ccessory Pipe cover small for insulation accessory Clamp accessory Adhesion For drain pipe use hard PVC general purpose pipe VP 25 I D 1 which can be purchased locally When connecting insert a PVC pip...

Page 17: ...rt the drain hose directly into drainage where the gas with sulfur may be generated Backwater bend Because the drain spout is at the position which negative pressure may occur So with the rise of wate...

Page 18: ...pedance of the duct is 1Pa m when the dimension of one side of the air duct is fixed as 250mm as shown below Note 1Pa m 0 1mmAg m The chosen chart of simple duct m 3 h m 3 n 100 200 300 400 500 600 10...

Page 19: ...is because of the irregular outer air mass strong wind and sunshine the humidity is increased There may be water drop on the outside of duct For cement and other new constructions even if not taking c...

Page 20: ...capacity number of fan controller is set at No 5 Rotate this switch capacity number setting No 1 No 8 Once the fan controller has trouble this linker can perform emergency assistant control When this...

Page 21: ...t may damage nut leading to leakage Check if the connection pipe leaks then do heat insulation treatment as below figure shown Only use seal cushion to bind the joint part of air pipe and heat insulat...

Page 22: ...s of the wires Use copper conductor only Select wire sizes and circuit protection from table below This table shows 20 m length wires with less than 2 voltage drop 2 Wiring connection Make wiring to s...

Page 23: ...ower than the top of the unit 1 Handing As there is no protective package for the outdoor unit so the following points merit attention 1 When forklift is used insert the fork into the holes in the bas...

Page 24: ...ation make sure that there is no refrigerant leakage Refrigerant if meeting with heaters and stoves ect in the room may produce hazardous gas Connection of refrigerant pipe 1 The joints of the refrige...

Page 25: ...or unit Diag2 Outdoor unit is above the indoor unit Liuid check ring Accumulator set 1 per 6 meters 6 During welding the gas pipe valve must be cooled down with a wet cotton cloth During welding of th...

Page 26: ...Nitrogen bottle VL VH Gauge distributor High pressure gauge Low pressure gauge Three way valve fully closed gas side Solder joint Solder joint Tightly closed Indoor unit Indoor Outdoor Access hole Co...

Page 27: ...3 minutes under 1 5MPa 15kg cm2g Serious leakage may be found Step 3 Charge for more than 24 hours under 3 0MPa 3 0kg cm2g Small leakage may be found Check for pressure decrease Without pressure decr...

Page 28: ...ory charge the refrigerant not including the construction procedure charged parts The calculation of the refrigerant charging When the connection pipe L 5 meters not need to add refrigerant If the con...

Page 29: ......

Reviews: