1 .4.3 Indoor DC fan motor fault
Indoor display E14
Method of DC fan motor is detected by checking the fan running condition and so on
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
DC fan motor protection dues to the DC fan motor faulty
Causes
DC fan motor protection dues to faulty PCB
Troubleshooting
* Caution Be sure to turn off power switch before connect or disconnect connector,
or parts damage
may be occurred.
Service diagnosis
Domestic air conditioner
37
when the detected rotation feedback signal don’t received in 2 minutes
Check whether
terminals on indoor
pcb is well
Pull out the terminals on
the indoor mainboard and
reinsert them.
Turn off power switch,and pull out the fan motor.
Measure the resistanc es between bal c k l i ne (0V)and whi te
line(15V) ,balck line (0V)and red line(310V) of indoor fan motor .
The
resistances range is
between 30K
Ω
with
2M
Ω
The
indoor fan
motor is damaged
and need replace
NO
YES
NO
YES
the indoor pcb is damaged
and need replace
Summary of Contents for 2U40S2SM1FA
Page 11: ...Pinping diagrams Domes t ic air condit ioner 4 Pinping diagrams 9 ...
Page 12: ...Operation range Domestic air conditioner 5 Operation range 10 10 0 21 27 35 20 40 60 43 20 40 ...
Page 15: ...wiring diagram Domestic air conditioner PCB 1 13 NOTE J3 OFF STATUS ...
Page 16: ...wiring diagram 14 Domestic air conditioner PCB 2 ...
Page 33: ...Dimensional drawing 31 Domestic air conditioner 8 Dimensional drawings 9 Center of gravity ...
Page 63: ...Domestic air conditioner Sincere Forever ...
Page 64: ...Wall Mounted Type DC Inverter FREE MATCH N Series 2U40S2SM1FA Model No ...