Service diagnosis
Domestic air conditioner
10Service Diagnosis
10.1 Caution for Diagnosis
The operation lamp flashes when any of the following errors is detected.
1. When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions,
disabling equipment operation.
2. When a signal transmission error occurs between the indoor and outdoor units. In either case, conduct the
diagnostic procedure described in the following pages.
10.2 Parameter of primary electronic appliance
e
r
u
t
c
i
P
r
e
t
e
m
a
r
a
P
e
m
a
N
O
N
1
Compressor
Rated voltage:220-230V
Rated current:8.4A
Rated frequency:50/60Hz
Resistance:0.93
2
Fan motor
Rated voltage: DC 224-336V
Rated current:0.236-0.288A
Rated frequency:50/60Hz
Rated power:41W
3
Reactor
Rated voltage:24.5V±10%
Rated current:15A
Rated frequency:50Hz
Rated inductance:5.2mH±10%
4
4-way valve
Rated voltage:220-240V
Rated frequency:50/60Hz
Power :4.5/3.5W
32
Summary of Contents for 2U40S2SM1FA
Page 11: ...Pinping diagrams Domes t ic air condit ioner 4 Pinping diagrams 9 ...
Page 12: ...Operation range Domestic air conditioner 5 Operation range 10 10 0 21 27 35 20 40 60 43 20 40 ...
Page 15: ...wiring diagram Domestic air conditioner PCB 1 13 NOTE J3 OFF STATUS ...
Page 16: ...wiring diagram 14 Domestic air conditioner PCB 2 ...
Page 33: ...Dimensional drawing 31 Domestic air conditioner 8 Dimensional drawings 9 Center of gravity ...
Page 63: ...Domestic air conditioner Sincere Forever ...
Page 64: ...Wall Mounted Type DC Inverter FREE MATCH N Series 2U40S2SM1FA Model No ...