05 Cool setpoint limit
This item is used to limit the temperature setting in cool mode. The
desired cool setting can never be set below this setting.
The default setting is 51.
06 Heat setpoint limit
This item is used to limit the temperature setting in heat mode. The
desired heat setting can never be set above this setting.
The default setting is 91.
07 Not used
08 Not used
09 Not Used
10 Not Used
11 Cooling minimum on/off time (minutes)
This item is used to limit the on and off times of the cooling system.
When the cooling system starts, it must remain on for the minimum
time set by this item. When the cooling system turns off, it must
remain off for a minimum time set by this item.
Setting
Cycles per hour (maximum)
5
6
6
5
7
4
8
3.7
10
3
The recommended setting is 8 minutes. A higher setting may be
appropriate for buildings with low heat loss/gain.
The default setting is 8.
14