* Default value
TXE530
61
6LE001714A
If
the luminosity level is insufficient (less than 40 Klux for more than 10 minutes)
or
the sun is not shining on the facade
or
the
outdoor temperature is less than 28 °C
and
the indoor temperature is less than 25°C for facade 1 for more than 15 minutes:
-
The heat protection is deactivated. The shutters and blinds remain in position.
Heat recovery
To save energy, the heat recovery system contributes to heating up the room by using the sun's energy.
It depends on:
-
the luminosity on the facade
-
the position of the sun on the facade
-
the outdoor temperature on all of the facades
-
or the indoor temperature on the facade 1
Heat recovery operation:
If
the luminosity level is sufficient (more than 40 Klux for more than one minute)
and
the sun is shining on the facade
and
the
outdoor temperature is less than 12 °C
and
the indoor temperature is less than 22 °C for facade 1:
-
Heat recovery is activated. The shutters and blinds open completely.
Warning
: This function should not be used for
openings that are part of the anti-intrusion system.
If
the luminosity level is insufficient (less than 40 Klux for more than 10 minutes)
or
the sun is not shining on the facade
or
the
outdoor temperature is greater than 28 °C
or
the indoor temperature is greater than 25 °C for facade 1:
-
Heat recovery is disabled. The shutters and blinds close completely.
Parameter
Description
Value
Heat protection
The heat protection automatic control is:
Not active
No*
Active
Yes
Parameter
Description
Value
Heat recovery
Automatic control of heat recovery is:
Not active
No*
Active
Yes
Summary of Contents for TXE530