Heat recovery operation:
If
the luminosity level is sufficient (more than 40 Klux for more than one minute)
and
the sun is shining on the facade
and
the
outdoor temperature is less than 12 °C
and
the indoor temperature is less than 22 °C for facade 1:
-
Heat recovery is activated. The shutters and blinds open completely.
Warning
: This function should not be used for
openings that are part of the anti-intrusion system.
If
the luminosity level is insufficient (less than 40 Klux for more than 10 minutes)
or
the sun is not shining on the facade
or
the
outdoor temperature is greater than 28 °C
or
the indoor temperature is greater than 25 °C for facade 1:
-
Heat recovery is disabled. The shutters and blinds close completely.
The
Heat recovery/protection deactivation
object allows for the heat recovery or protection to be disabled for the 4 facades.
The deactivation control can be in the form of a supervision system or push button. This object is common to the 4 facades.
If the use of heat recovery or protection is confirmed in the settings, then the deactivation control operates as follows:
-
If the
heat recovery/protection deactivation
object receives the value 0, the heat recovery or protection is disabled.
-
If the
heat recovery/protection deactivation
object receives the value 1, the heat recovery or protection is activated.
The
heat recovery/protection deactivation status
object transmits the
heat recovery/protection deactivation
object status.
The
heat recovery/protection status
object indicates:
-
whether the heat protection function is active (example: very sunny day in summer).
-
whether the heat recovery function is active (example: very sunny day in winter).
-
whether one of the 2 functions is inactive (bit = 0).
Communication objects:
Parameter
Description
Value
Use of heat recovery
automatic control
Automatic control of heat recovery is:
Not active
No*
Active
Yes
Parameter
Description
Value
Heat recovery conditions
This parameter defines the conditions for heat recovery
to be activated.
The value of this setting is fixed.
Sun on the facade
Luminosity > 40 klux
Outdoor < 12 °C or (facade 1) indoor <
22 °C*
33 - Heat protection/recovery deactivation - Input
(1 Bit - 1.003 DPT_Enable)
34 - Heat protection/recovery deactivation status - Output
(1 Bit - 1.003 DPT_Enable)
35 - Heat protection/recovery status - Output
(1 Bit - 1.011 DPT_State)
3
6 - Indoor temperature for facade 1 - Input
(2 Byte - 9.001 DPT_Value_Temp)