44
45
PROGRAMMING
CONTROL AND TEST MODES
>
Step 1: Press “right” push button to make first variable blinking (LS)
>
Step 2: press push buttons “top” and “bottom” to modify the
variable
>
Step 3: Press “validation”
>
Step 4: Press “bottom” push button to access timer
value configuration
Load shedding configuration
LS variable allows associated LS timer configuration.
Example: load shedding configuration
LS
Output
Associated funciton
Setting range
Default value
O1 to O2
LS
0 to 60 s (≤ DTT)*
2
* In case of DTT variable configuration below LS, LS will be automatically set to to DTT value.
)XQFWLRQ
WLPHU
It is possible to start test sequences or to control electrically the changeover system from keypad.
Control Mode
Access code is displayed directly
Test Mode
>
It is possible to test leds and LCD without entering any code by pressing directly
>
Test on load or test off load access codes are displayed after pressing
or
>
Enter the code 4000 using “left”, “right”, “top” and “bottom” push buttons
>
Press “validation” push button to enter
>
Step 1: Press “mode” push button to make test or control led blinking
>
Step 2: Press “validation” push button to make control or test led become fixed
Enter Control or Test modes
>
Direct access by pressing
and
>
To start a test (off load or on load) or to control the changeover switch electrically, press
,
and
Control or Test modes use
>
Press “ESC” push button
The new operational mode (automatic or manual) depends on information from master.
Exit control or test modes