38
39
PROGRAMMING
Architecture valid for HZI811
PROGRAMMING
*
only on automatic changeover switches
** only on controller.
Variables Characteristics
Setup
LCD
Denomination
Setting range
Default values
nt
Type of network
1BL, 2BL, 2NBL
3NBL, 4NBL,
41NBL, 42NBL
4NBL
Un
Network Nominal voltage
Phase-Neutral voltage for 1BL & 41NBL
Phase-Phase voltage for others
100 to 480 V
400 V
ScE*
Source 1 - Switch I or II configuration
Source 1 (controlled and displayed) linked to switch I or II
(depending on cabling)
I or II
I
Fn
Network nominal Frequency
50 or 60 Hz
50 Hz
Gen
Genset start signal state
Normally opened or closed
NO, NC
NO
Pri
Network priority selection
Keypad selection (1 or 2)
Also possible via external contact
Using option, 0: no priority
1, 2, 0
1
Mtf
Manual Retransfer
Activation of the feature
Yes, No
No
LoG
Type of control logic selection
Impulse, contactor or breaker**
IMP, CON, brE**
IMP
AC**
Number of position auxiliary contacts used, depending on
transfer device type (switch, contactor, breaker)
0, 2, 3
2
rn1**
Allows 0 position command after loss of main source (source 1)
Yes, No
No
rn2**
Allows 0 position command after loss of emergency source
(source 2)
Yes, No
No
CrS
Number of permutation counter Reset
Yes, No
No
CP
Programming code modification
Possible to change the code
0001 to 9999
1000