22
Technical changes reserved
Connecting and powering the HTD210H Panel display
1 Powering the Panel display via the COM module
1
CIP connector of the CIP-Adaptor to
connect with Panel display
5
Power supply HTG911H
2
CIP connector of the CIP-Adaptor to
connect with COM module
6
HTD210H Panel display
3
CIP-Adaptor to connect with COM
module
7
CIP-Aadaptor to connect with Panel
display
4
COM module
8
Energy MCCB
Step
Action
1
Make sure the COM module is connected to the MCCB. If not, insert the CIP
connector of the second CIP Adaptor into the free CIP socket.
NOTICE
Risk of damaging plug and socket.
- Observe the orientation of the connector.
2
Lead the second CIP Adaptor outside the MCCB.
3
Close the front cover of the MCCB.
4
Insert the RJ9 Plug of the second CIP Adaptor into the COM socket of the COM
module (HTC310H/HTC320H).
5
Make sure that the COM module (HTC310H/HTC320H) is connected to a 24 V
DC power supply. If this is not the case, connect the recommended Power supply
HTG911H to the 24 V DC terminal of the COM module.