background image

6L

E

00

04

36

A

   

20

10

25

5

30

15

°

C

   

EK004, 25507

§

Room thermostat with 

1 NO contact

User instructions

The thermostat can be installed either surface

mounted or on a flush box 60 mm. 

Cables should arrive from the back.  

- take off the front cover 

¿

- fix the product’s base 

through the fixing 

  holes 

¡

- connect the wires on the terminals 

¬

- put back the front cover 

¿

ƒ 

indicating light to signal heating.

Technical specifications  

Electrical characteristics :

-  supply : 230V 

±15% 50/60 Hz

-  output : 1 NO contact 

   8 A - 250 V 

AC1

-  consumption : 0,5 VA

Functional characteristics : 

-  ON/OFF regulation

-  static differential < 1K

-  dimensions : 80 x 80 x 30

Environment

-  operating temperature : 0 °C to +50 °C

-  storage temperature : -10 °C to +65 °C 

-  protection degree : IP 30.

- ecodesign class : 1

Connection

flexible : 1 

to 2,5 

rigid :     1,5 

to 4 

Electrical connection 

Product presentation 

Installation 

The EK004, 25507 is an electronic room ther-

mostat particularly suitable for heating and / or

air conditioning control.

Temperature’s range limitation 

It is possible to limit mechanically the temperature’s

range (between 10° to 20° C for example) or even to

lock the temperature range at a fixed temperature

(20 °C for example).
For that :

1.  Take the two range limiting nibs which are found 

    in the thermostat base.

4. Put back the knob and check that the temperature’s

   range is limited to the requested values.

2. Locate the knob to indicate a precise value (20 °C

   for example) and remove it.

3. Place the two range limiting nibs.

Installation of the EK004, 25507 

thermostat 

Install the thermostat at 1,50 m from the floor, on

the internal wall

avoiding external influences :

(

¿

extraction fan, 

¡

external wall, 

¬

sunlight) and

internal influences : (

ƒ

lighting devices, 

chimney,

electrical heater).

Seal the conduit to avoid any draught coming from it.

A

external influences

B

internal influences

Ex : to lock the temperature’s range at 20 °C

A warranty period of 24 months is offered on hager products,

from date of manufacture, relating to any material of manufactu-

ring defect. If any product is found to be defective it must be re-

turned via the installer and supplier (wholesaler). The warranty is

withdrawn if :

-  after  inspection  by  hager  quality  control  dept  the  device  is

found to have been installed in a manner which is contrary to IEE

wiring regulations and accepted practice within the industry at

the time of installation.

- the procedure for the return of goods has not been followed.

Explanation of defect must be included when returning goods.

Warranty

GB

Adjustable temperature’s range :

Some days after the installation, measure the 

room temperature with a reference thermo-

meter.

Draw back the knob and locate it to reach 

the same value of the reference thermometer.

   

   

20

10

25

5

30

15

C

   

   

20

10

25

5

30

15

C

3

4

1

2

5

2

2

2

1
2

6
7

   

20

10

25

5

30

15

C

   

1

2

3

4

5

7

6

B

A

EK004, 25507

1,50 m

6

2

1

7

L

N

Heating

L

   

   

Mechanical stop

"

Reviews: