BODYGUARD-T
Installation Instructions
I-EA00206
Rev 01, Rev Date: 05/08/2018
Page
8
of
12
Hager Companies 139 Victor Street, St. Louis, MO 63104 (800) 325-9995 www.hagerco.com
10. UNIVERSAL REMOTE CONTROL (cont.)
AUTOMATIC SET-UP
: When performing an automatic set-up (set-up key pressed twice), the sensor will begin to flash green during the door-
closed position, and will continue to do so until the door is activated to the open position. The LED will then go out and the door will close. The LED
will flash green again at the closed position until a set-up is complete. Upon the next activation, the sensor will launch another set-up for the open-
door position, and will begin normal operation thereafter.
QUIET MODE
: The QUIET mode uses a different pulsing pattern to avoid interference with other infrared systems. The NORMAL mode
transmits more energy and detects in a slightly crisper fashion. The NORMAL mode is recommended for installations with only one door.
Number Keys
Number keys (0 – 9) are used for
assigning a value for a given
function
Infrared Frequency
Mode
Frequency
1
Normal
Low
2
Normal
High
3
Quiet
Low
4
Quiet
High
See QUIET MODE
Interface
1: New Style
2: LO21 - Old Style (LO21, B, K, P, S, U,
LO-LINX, MC15, DP-HUB)
Unlock
Inquire
Lock
To UNLOCK the sensor:
Press the UNLOCK key once. Red LED
flashes slowly. If flashing fast, see Note
below.
To LOCK the sensor:
Press the LOCK key twice, OR press
once, then enter a 4-digit lock code. If less
than 4 digits, press lock again after the
last digit. LED goes out when complete.
To INQUIRE the sensor:
Unlock the sensor, press the desired
function key, and then press the INQUIRY
key – the number of green flashes
corresponds to the value.
Note: If the sensor is locked, and the code
is unknown, power the sensor off and then
back on. Press the UNLOCK key within 60
seconds. Re-lock with 0000. This is the
default code. The sensor will unlock with
one press of the unlock key when set to
0000.
Door Control
1: Normal
(LED in normal mode)
2: Door permanently open
(Red LED ON)
3: Door permanently closed
(Red LED OFF)
Output
Configuration
1: Normally Open Relay
2: Normally Closed Relay
Set-up
launch a quick set-up
restore factory defaults
launch a closed-door set-up
launch an open-door set-up
See AUTOMATIC SET-UP
Hold Time
0 (0.5s)
®
9 (9s)