hager BODYGUARD-T Installation Instructions Manual Download Page 3

 

 

BODYGUARD-T  

 

 

Installation Instructions 

 

 

 

I-EA00206

 

Rev 01, Rev Date: 05/08/2018 

 

 Page 

3

 of 

12 

 

Hager Companies  139 Victor Street, St. Louis, MO 63104   (800) 325-9995   www.hagerco.com 

4. MECHANICAL INSTALLATION (cont.) 

PLACEMENT OF SENSOR 

Remember these guidelines when installing a Bodyguard-T: 

ü

 

The Bodyguard-T should be mounted at a height range of 6’ 6” – 8’. Maximum mounting height is 9’. 

ü

 

The Bodyguard-T should be mounted above the door on the swing side. 

ü

 

The Bodyguard-T shall be mounted flush with the bottom of the automatic door header. This is absolutely necessary to allow the detection 
pattern to reach back through the threshold area when the Bodyguard-T is in the open-door position. 

ü

 

For SINGLE DOOR APPLICATIONS, the Bodyguard-T should be mounted at the center 
of the door opening. However, if this is not possible, the unit may be installed off-center. 
In such cases, pattern location will have to be altered for proper placement of the field of 
detection.  Try to avoid mounting locations that may pose potential problems (e.g. directly 
over a door arm). 

 

ü

 

For DOUBLE-EGRESS APPLICATIONS, one Bodyguard-T should be mounted over each 
swing-path.  There should be at least 40” of separation between the two sensors when 
measured between the center line of each sensor.  See image to right. 

ü

 

If the Bodyguard-T sensor is the only sensor being used for safety at the swing side of the 
door,  to  be  in  compliance  with  ANSI  156.10,  a  lockout  safety  beam  or  door-mounted, 
safety side SuperScan(s) is needed in addition to the Bodyguard-T sensor. 

CAUTION:  FOR ALL APPLICATIONS, REFER TO THE PATTERN CHARTS FOR 
WIDTH AND DEPTH IN THE APPLICABLE SECTION OF THIS GUIDE.  PATTERNS 
SHALL BE ADJUSTED TO ACHIEVE MAXIMUM DETECTION ZONES, AND SHALL 
BE IN COMPLIANCE WITH ALL APPLICABLE SAFETY STANDARDS (i.e. ANSI A156.10). 

INSTALLATION 

NOTE: Hager  recommends  the  use  of  a  Bodymount  for  most  Bodyguard-T  applications.    The  Bodymount  is  a  3”  standoff  that  allows  the 

Bodyguard-T to be slightly distanced from the face of the closed door.  This helps to prevent ghosting caused by slight door movement 
while closed, and  also  prevents  ghosting when SuperScan sensors are  used  (as the SuperScan extrusions at the top  of the  door  are 
extremely close to the sensor while the door is closed). 
 

1. 

The extrusion has pre-drilled mounting holes at each end. 

2. 

Hold the Bodyguard-T up to the pre-determined location and attach using the 2 self-drilling screws that are included with the package 
(image below, left).  It may be necessary to drill a pilot hole (image below, right) in the header for ease of screw installation.  Ensure 
that Bodyguard-T is mounted securely at each end. 

3. 

If the Bodyguard-T is mounted directly to door header, and cabling is to pass directly into header, drill a ¼” hole next to the Bodyguard-
T’s left side endcap to allow wire passage into header.  The wire passage hole should be in a location that aligns with the cut out in the 
endcap. 

 

 

Wall Switch 

Wall Switch 

Bodyguard 

Bodyguard 

20” min 

20” min 

Pre-Drilled Mounting Holes 

(approx. 9 ¾” apart) 

Summary of Contents for BODYGUARD-T

Page 1: ... buttons contained on the PC board within the unit With these two buttons the Bodyguard T s field of detection can be altered without the use of the hand held remote If a complete door mounted sensor SuperScan system is not used in addition to the Bodyguard T Hager recommends the use of a lockout safety beam to allow safety signaling if the zone is entered during a door closing cycle NOTE If utili...

Page 2: ...moving door parts will not catch any wires and cause damage to equipment 4 MECHANICAL INSTALLATION TIPS The sensor must be firmly fastened to prevent vibration The sensor must not have any unwanted objects likely to move or vibrate in its path The sensor should be mounted flush with bottom of door header PREPARATION To prepare the Bodyguard T for mounting to the header perform the following 1 Remo...

Page 3: ...h ANSI 156 10 a lockout safety beam or door mounted safety side SuperScan s is needed in addition to the Bodyguard T sensor CAUTION FOR ALL APPLICATIONS REFER TO THE PATTERN CHARTS FOR WIDTH AND DEPTH IN THE APPLICABLE SECTION OF THIS GUIDE PATTERNS SHALL BE ADJUSTED TO ACHIEVE MAXIMUM DETECTION ZONES AND SHALL BE IN COMPLIANCE WITH ALL APPLICABLE SAFETY STANDARDS i e ANSI A156 10 INSTALLATION NOT...

Page 4: ...nated at the control OR use the 7 pin terminal See diagram below The monitoring DIP switch must be turned OFF to function while in a non monitored status see page 7 If wiring the Bodyguard T to a Hager module such as an LO21 or an MC15 refer to the schematic for the respective module 2 Once wired feed the opposite end of the cable through the previously drilled wire passage hole MECHANICAL INSTALL...

Page 5: ... that extends out from the face of the safety side of the door In this case the 0º setting would improve the location of the detection field across the threshold area of the doorway It is recommended that for most applications the unit be powered and walk tested at the pre set 5º angle After walk testing if the detection field needs to be changed proceed with changes to the angle setting as shown ...

Page 6: ...two wires are swapped the Bodyguard T will NOT work correctly b Check to ensure that the voltage from the motor at the red and black wire of the lockout has at least 10 VDC A voltage that is too low may not be recognized by the lockout 2 If the door goes to the open position and a set up is completed successfully but then the door begins to close and immediately recycles open it is possible that t...

Page 7: ...en The following functions may be independently adjusted for each door position Sensitivity Pattern Width Pattern Depth 2 The following functions apply to both door closed and door open positions Automatic Learn Time Immunity Frequency Output Configuration Door Control Mode Hold Time Interface Type 3 The Immunity modes include Medium Rain and High Snow During these modes learn time of the sensor w...

Page 8: ... function Infrared Frequency Mode Frequency 1 Normal Low 2 Normal High 3 Quiet Low 4 Quiet High See QUIET MODE Interface 1 New Style 2 LO21 Old Style LO21 B K P S U LO LINX MC15 DP HUB Unlock Inquire Lock To UNLOCK the sensor Press the UNLOCK key once Red LED flashes slowly If flashing fast see Note below To LOCK the sensor Press the LOCK key twice OR press once then enter a 4 digit lock code If l...

Page 9: ...eft Wide 8 Asymmetric Right Wide 9 Center Narrow See notes for PATTERN WIDTH or DEPTH below Pattern Depth 1 Deep threshold ON 2 Medium threshold ON open 3 Limited threshold ON 4 Deep threshold OFF 5 Medium threshold OFF closed 6 Limited threshold OFF See THRESHOLD note below See PATTERN WIDTH or DEPTH note below Sensitivity Door Open Closed 0 min 9 max default 7 for door open default 6 for door cl...

Page 10: ...iately flash red followed by a sequence of green flashes The red flashes indicate the parameter and the green flashes indicate the setting of the particular parameter NOTE Pressing PB1 will toggle between the parameters and pressing PB2 will toggle between the range of adjustments for that particular setting Once you achieve the highest adjustment the value will roll over to the lowest setting upo...

Page 11: ...BODYGUARD T Installation Instructions I EA00206 Rev 01 Rev Date 05 08 2018 Page 11 of 12 Hager Companies 139 Victor Street St Louis MO 63104 800 325 9995 www hagerco com 12 PATTERNS WIDTH DEPTH ...

Page 12: ...e system Installers and service personnel are responsible for executing a risk assessment following each installation service performed ensuring that the sensor system installation is compliant with local national and international regulations codes and standards Once installation or service work is complete a safety inspection of the door gate shall be performed per the door gate manufacturer rec...

Reviews: