Programming Device & Troubleshooting
Door will not open
· Check On-Off switch for proper position
· Check LED status for LD 5, 6, and 7. If any of these LED’s are OFF, the door will not open.
They require a normally closed circuit.
· Launch a new setup – see page 26
· Check status of emergency input 12
· Door has traveled close past the 0 degree position
Door will not close
· Check status of LEDs” LD2, 3, 4, 8 on the I/O board.
· If any of the LED’s are ON, check the associated input
Door will not reach its full
open or closed position
· Check the mechanical stops on the operator for proper adjustment
Slow flashing red LED (LD2) at
the Adjustment Control Board
· Indicates a possible fault in the control.
o Check LED status for the other inputs. This will identify if any inputs are currently
active.
· Indicates a potential faulty setup.
o Loose or incorrect motor connection
o Possible loose chain tensioner - refer to Appendix for chain tensioner adjustment
procedures.
o Launch a new setup. If problem repeats and there are no other discrepancies noted,
replace the operator/control sub-assembly.
Door closes too fast at last 5 to
10 degrees of closing
· Ensure dip switch 8 is OFF.
· Ensure there is no binding of the door as it is closing through the last few degrees of
closing. If binding exists (from a tight bottom sweep, for example), correct the condition
and then re-launch a new setup.
Troubleshooting
Please note, some functions of the Hager 8300 operator require the use of an optional hand-held
programming device.
The following functions require use of this device for programming:
Logic Assignment For Inputs
Logic Assignment For Outputs
Opening & Closing Acceleration
Opening & Closing Deceleration
Opening & Closing Strength (obstruction force)
Opening & Closing Strength Duration (time duration for obstruction force)
Night-Time Hold Open Time
Delay On Activation (up to 4 seconds)
Electric Lock Interfacing
Master/Slave Configuration
Cycle Count – Maintenance Reset
7-Day Programmable Timer (With Daylight Savings Time)
Troubleshooting & Data Codes