2950 Series Magnetic Locks

Installation Instructions

I-EA00063

Rev 2, Rev Date: 12/12/13

Always visit www.hagerco.com for the latest Installation Instructions

HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 • (800) 325-9995

AWG WIRE CHART

To determine the correct wire gauge to use on “one circuit” the following information is required:

1.  The quantity, voltage, and current draw of all lock(s) to be used.

2.  The distance in feet from the power supply to the furthest lock.

Add together the current draw (amps) of all locks on the same circuit.  Cross reference the total amps with the distance between the power source and 

the furthest lock to determine the wire gauge required. All wiring must be installed in accordance with all state and local codes.

Minimum 

Wire 

Gauge for 

12 Volts 

AC or DC 

AMPS

0.25

0.50

0.75

1.00

1.50

2.00

2.50

         DISTANCE IN FEET FROM POWER SOURCE TO FARTHEST LOCKING DEVICE

25

50

75

100

150

200

250

300

400

500

1000

18

18

18

18

18

16

16

14

14

12

18

18

18

16

16

14

12

18

18

16

14

12

12

18

16

14

14

12

18

14

12

12

16

14

12

16

12

         

Minimum 

Wire 

Gauge for 

24 Volts 

AC or DC

AMPS

 

0.25

0.50

0.75

1.00

1.50

2.00

2.50

25

50

75

100

150

200

250

300

400

500

1000

18

18

18

18

18

18

18

18

16

16

16

18

18

18

18

18

16

16

14

14

12

18

18

18

18

16

14

14

12

12

18

18

16

16

14

14

12

12

18

18

16

14

14

12

18

16

14

14

12

18

16

14

12

DISTANCE IN FEET FROM POWER SOURCE TO FARTHEST LOCKING DEVICE

              TROUBLE SHOOTING              

PROBLEM

Mag Lock releases slowly.

(residual magnetism)

Poor holding force.

No holding force. 

Door does not lock.

CAUSE

Control switch wired on AC side of power source.

Field installed diode in parallel with power input.

Armature installed rigidly.

Low voltage.

AC voltage input.

(Emlock will make a humming noise)

No power.

Input polarity reversed.

Open circuit in Emlock coil.

Magnet coil short.

SOLUTION

Control switch must be wired on DC side of power supply.

When an AC transformer and rectifier are used, the control 

switch must be wired between the rectifier and the MagLock.

Remove diode.

Armature must pivot loosely from its center mounting point to 

permit full armature contact.

Check for proper voltage at the MagLock input.  If low, 

determine if the correct wire gauge is being used to prevent 

excessive voltage drop.

Check power supply load capacity.  It must meet or exceed the 

combined current rating of all locks on the circuit.

MagLocks require DC input voltage.  When AC voltage from a 

transformer is used, a full wave bridge rectifier must be 

installed to convert the AC voltage to DC voltage.

Check the voltage at the MagLock.  If the voltage is low or 

zero, double check all wire connections and the power supply.

Check voltage polarity.  Terminal (-) is: Negative.  Terminal 

(+) is: Positive.

Check coil continuity with OHM meter.  If reading is high or 

open, replace the magnet coil.  See Fig. 3A and the Resistance 

Specifications.

Coil shorts or incorrect wiring will blow fuses. Measure the coil 

for correct resistance. See Fig. 3A and the Resistance 

specifications.

Page 3 of 3