2950 Series Magnetic Locks

Installation Instructions

I-EA00063

Rev 2, Rev Date: 12/12/13

Always visit www.hagerco.com for the latest Installation Instructions

HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 • (800) 325-9995

IMPORTANT NOTES

INDOOR USE ONLY

Do not run power wires and signal wires in the same cable or conduit.

Do not install a diode in parallel with any magnetic lock.  A diode

will cause a delay when releasing the door and residual

magnetism to occur.

Although Hager recommends the use of a DC power supply, a transformer with 

an adjacent mounted full wave bridge rectifier

may be used.  A significant voltage drop will occur when using a

full wave bridge rectifier.

Any low voltage condition will cause erratic operation of the

optional bond sensor.

When using a full wave bridge rectifier, all access controls and/or release 

contacts must be located between the Emlock and rectifier

to ensure quick release.

ELECTRICAL INSTALLATION

1. Use jacketed cable for all wire runs.  Refer to the Hager wire

    gauge chart for proper lock power wire size (18 AWG

    gauge minimum).

2. Use only shielded cable for all signal wires.  22 AWG gauge

    (minimum) may be used for signal wires up to 1,000 feet.

3. All wires 

must

 be colored coded.

4. Use properly fused power source only.  See Electrical

    Specifications.

5. Make all MagLock terminal connections according to 

    Figure 3A.

N/C ORG COVER OFF

N/O YEL COVER ON

COM WHT

ATS

TIME

TIME ADJ.

MBS

2950 SERIES CONNECTIONS

LOCK PWR

-

+

NC

OPEN

COM

NO

CLOSED -

-

DPS

NC

UNLOCKED

COM

NO

LOCKED -

-

MBS

ELECTROMAGNET

PLUG CONNECTION

FIG. 3A

MBS PLUG IN

EMLOCK

E4

E3

E2

E1

J1

ELECTRICAL SPECIFICATIONS

Voltage kickback protection standard

SERIES

INPUT VOLTAGE (VDC)

POWER CONSUMPTION (mA)

COIL RESISTANCE (OHMS)

HOLDING FORCE (LBS)

12/24

700/350

1650

35  (PER COIL)

*

12/24

250/125

1200

100  (PER COIL)

*

*NOTE:

  For a proper coil resistance reading, turn off the DC voltage.  Use an ohmmeter and measure

the resistance between the pins of the plug connector positions E1-E2 and E3-E4

2951/2952

2953/2954

All switches rated @ 250 mA @ 30 VDC

AVAILABLE OPTIONS

ATS -

MBS -

DPS -

Time -

Anti-Tamper Switch (2-679-0112)

Magnetic Bond Sensor (2-679-0111)

Door Position Switch (2-679-0110)

TIME DELAY (1-30 sec) (2-679-0109)

SPDT, DRY,

SPDT, DRY,

SPDT, DRY,

20 mA

Page 2 of 3