2950 Series Magnetic Locks
Installation Instructions
I-EA00063
Rev 2, Rev Date: 12/12/13
Always visit www.hagerco.com for the latest Installation Instructions
HAGER COMPANIES 139 Victor Street, St. Louis, MO 63104 • (800) 325-9995
IMPORTANT NOTES
INDOOR USE ONLY
Do not run power wires and signal wires in the same cable or conduit.
Do not install a diode in parallel with any magnetic lock. A diode
will cause a delay when releasing the door and residual
magnetism to occur.
Although Hager recommends the use of a DC power supply, a transformer with
an adjacent mounted full wave bridge rectifier
may be used. A significant voltage drop will occur when using a
full wave bridge rectifier.
Any low voltage condition will cause erratic operation of the
optional bond sensor.
When using a full wave bridge rectifier, all access controls and/or release
contacts must be located between the Emlock and rectifier
to ensure quick release.
ELECTRICAL INSTALLATION
1. Use jacketed cable for all wire runs. Refer to the Hager wire
gauge chart for proper lock power wire size (18 AWG
gauge minimum).
2. Use only shielded cable for all signal wires. 22 AWG gauge
(minimum) may be used for signal wires up to 1,000 feet.
3. All wires
must
be colored coded.
4. Use properly fused power source only. See Electrical
Specifications.
5. Make all MagLock terminal connections according to
Figure 3A.
N/C ORG COVER OFF
N/O YEL COVER ON
COM WHT
ATS
TIME
TIME ADJ.
MBS
2950 SERIES CONNECTIONS
LOCK PWR
-
+
NC
OPEN
COM
NO
CLOSED -
-
DPS
NC
UNLOCKED
COM
NO
LOCKED -
-
MBS
ELECTROMAGNET
PLUG CONNECTION
FIG. 3A
MBS PLUG IN
EMLOCK
E4
E3
E2
E1
J1
ELECTRICAL SPECIFICATIONS
Voltage kickback protection standard
SERIES
INPUT VOLTAGE (VDC)
POWER CONSUMPTION (mA)
COIL RESISTANCE (OHMS)
HOLDING FORCE (LBS)
12/24
700/350
1650
35 (PER COIL)
*
12/24
250/125
1200
100 (PER COIL)
*
*NOTE:
For a proper coil resistance reading, turn off the DC voltage. Use an ohmmeter and measure
the resistance between the pins of the plug connector positions E1-E2 and E3-E4
2951/2952
2953/2954
All switches rated @ 250 mA @ 30 VDC
AVAILABLE OPTIONS
ATS -
MBS -
DPS -
Time -
Anti-Tamper Switch (2-679-0112)
Magnetic Bond Sensor (2-679-0111)
Door Position Switch (2-679-0110)
TIME DELAY (1-30 sec) (2-679-0109)
SPDT, DRY,
SPDT, DRY,
SPDT, DRY,
20 mA