KEYPAD WIRING

See Fig. 3 for an example of a basic door installation.  The keypad is mounted 
adjacent to the door.  An electric door strike is mounted in the door jamb to 
release the door lock.  A door contact switch is mounted on top of the door 
jamb for detecting when the door is open.

Use the following steps to wire the keypad.  Refer to the wiring diagram 
shown in Fig. 4 to assist in the wiring.

Note: For lock power, use 18 AWG wire or larger (depending on load).  Use 
22 AWG or larger for signal connections. Refer to lock manufacturer

documentation for lock power requirements.

Output Connection

Install a low-voltage fail-secure electric door strike at the door to be controlled. 
Route 2 wires from the door strike to the keypad. Connect an MOV across the 
coil wires of the strike. Connect the (+) door strike wire to the keypad

s MAIN 

RELAY N.O wire (yellow). Connect the other door strike wire to the keypad

PWR(-) wire (black).  Connect the keypad

s MAIN RELAY COM wire (white) 

to the keypad

s  PWR(+) wire (red) .

Power Connection

Connect the power supply

s output terminals to the keypad

s PWR(+) wire 

(red) and PWR(-) wire (black). If using a DC supply, observe wiring polarity. If 
an  AC transformer is being used, polarity does not mater.

Caution:  If the unit is AC powered, make sure the secondary of the 
system transformer is isolated from earth ground.

Earth Ground

To avoid damage to the unit from static discharges, this unit must be 
connected to a proper earth ground.  Connect the green earth ground wire to 
a good earth grounding point.  Suggested wiring size is 18 AWG for earth 
ground.

Fig. 5  Using Solid State Outputs

Fig. 3  Basic Door Installation  

OUTPUT #3 LIGHTS AN LED
OUTPUT #4 LIGHTS AN LED AND SOUNDS A BEEPER

EXAMPLE #1:

POWER
SUPPLY

+

LED

LED

BLUE

PINK/SALMON

1K

Ω

1K

Ω

-

+

OUTPUT #3

OUTPUT #4

ELECTRONIC 

BEEPER

OUTPUT #3 LIGHTS A LAMP POWERED FROM AN EXTERNAL SOURCE
OUTPUT #4 TRIGGERS A NORMALLY OPEN ALARM PANEL ZONE

EXAMPLE #2:

BLUE

PINK/SALMON

OUTPUT #3 COM

OUTPUT #4 COM

POWER 

SOURCE

OUTPUT #3

END OF LINE 

RESISTOR

ALARM PANEL

NO ZONE

COMMON

LOW 

VOLTAGE 

LAMP

-

+

BLACK

BLACK

OUTPUT #4

EACH 

OUTPUT 

100 mA 

MAXIMUM

W

ir

e

P

ig

ta

il

W

ir

e

P

ig

ta

il

Fig. 4  Basic Door Installation Wiring

Sense Input

RE 

Note:  The SENSE input (gray wire) can be programmed as either a door 

sense or inhibit input.  Both features cannot be used at the same time. If you 
are not using the sense input, program this input for inhibit.

Door Sense: (Detect forced entry or door ajar conditions) Install a 

normally 

closed 

door switch on the door and route two wires from the switch to the 

keypad.  Connect the door switch to the keypad

s SENSE wire (gray/ E8) and 

COM wire (any black wire).  
                      
Inhibit: (Disable access) If an inhibit switch or timer is going to be used for 
temporarily disabling the keypad, route two wires from the switch or timer to 
the keypad.  Connect the inhibit switch/timer

normally open 

contacts to the 

keypad

s SENSE (gray/ E8) and COM (black wires) terminal.

Request-to-Exit Input   

(wiring shown on page 3, fig. 4)

If a request-to-exit pushbutton is going to be used, route two wires from the 
keypad box to a normally open pushbutton mounted on the secure side of the 
door.  Connect the wires to the pushbutton and to the keypad

s REX wire 

(violet/ E6) and COM (black wires) terminals.

Solid State Outputs

The two solid state outputs (Outputs #3 & #4) can be programmed to activate 
during various conditions.  These 

open collector

” 

outputs can be used to 

activate indicators or sounders.  See fig. 5 for wiring examples using the solid 
state outputs.

TO POWER SUPPLY

KEYPAD POWER

12 or 24 VOLTS

AC OR DC

}

+

-

RED

BLACK

AUXILIARY 

RELAY

2 AMPS @ 28VDC 

MAX

}

NC

NO

COM

ORANGE

WHITE

BLACK

FAIL SECURE CONNECTION

FAIL SAFE CONNECTION

MAIN RELAY

5 AMPS @ 28VDC 

MAX

}

NC

COM

NO

ORANGE

WHITE

YELLOW

BLACK

PINK/SALMON

GREEN

GRAY

BLACK

VIOLET

BLACK

BLUE

 DOOR POSITION 

SWITCH

[N/C]

REQUEST-TO-EXIT 

SWITCH

[N/O]

COMMON

OUTPUT #4

OUTPUT #3

NOT USED

COMMON

SENSE

REQUEST TO EXIT

COMMON

WIRE PIGTAIL

E

1

E

8

E

7

E

6

E

5

E

4

E

3

E

2

C

NO

C

NC

NO

AUXILIARY OUTPUTS

100mA MAX TO COMMON

{

*

*

Grn Wire
To Earth 
Ground

2916P

Keypad

Electric Strike

Door Sensor Switch

2 wires for
door sensor

2 wires 

for strike

2 wires for
power supply

earth
ground

Summary of Contents for 2916P

Page 1: ...nhibit the input can be wired to a normally open service switch or automatic timer that will disable access while the switch is closed The REQUEST TO EXIT input can be wired to a normally open pushbut...

Page 2: ...ust first enter programming mode to perform any function The yellow indicator will blink slowly showing that the 2916P is in programming mode Use the option codes to program each function After the ne...

Page 3: ...4 TRIGGERS A NORMALLY OPEN ALARM PANEL ZONE EXAMPLE 2 BLUE PINK SALMON OUTPUT 3 COM OUTPUT 4 COM POWER SOURCE OUTPUT 3 END OF LINE RESISTOR ALARM PANEL NO ZONE COMMON LOW VOLTAGE LAMP BLACK BLACK OUT...

Page 4: ...Relay 2 Auxiliary Relay 3 Both Relays 10 Relay 1 toggled 20 Relay 2 toggled 30 both Relays toggled 12 Relay 1 toggled Relay 2 timed open 21 Relay 1 timed open Relay 2 toggled The yellow indicator will...

Page 5: ...4 1 Main Relay 2 Auxiliary Relay 3 Output 3 4 Output 4 0 No Output Lockout Disable Select Alarm Shunt Output Default No Output Sets which output activates during the time access is granted Use this ou...

Page 6: ...Sounds During Main Relay Default No Selects whether or not the keypad beeps during Main Relay activation Press 41 Sound Sound 1 for Yes 0 for No Solid state Output 4 On time Default 02 Seconds Sets t...

Page 7: ...Always visit www hagerco com for the latest Installation Instructions HAGER COMPANIES 139 Victor Street St Louis MO 63104 800 325 9995 5 750 1 375 3 000 MOUNTING TO SINGLE GANG RECESSED OUTLET BOX 2X...

Page 8: ...Rev 6 Rev Date 5 29 19 Always visit www hagerco com for the latest Installation Instructions HAGER COMPANIES 139 Victor Street St Louis MO 63104 800 325 9995 OPTIONAL SHROUD SURFACE MOUNT WITH OPTION...

Reviews: