background image

 

 

Floor protection 

The  floor  is  to  be  protected  from  the  radiant  heat  from 
the  area  of  the  viewing  window  (combustion  chamber). 
In  addition,  for  practical  reasons  associated  with 
cleaning  it  is  recommended  that  you  install  your  pellet 
stove on a fireproof base that extends beyond the device 
at the back and on the sides by at least 5 cm and at the 
front  by  at  least  50  cm. We  have  floor  protection  plates 
(underlay plates or U plates) in our range of accessories. 
If  required,  you  may  order  them  from  your  specialist 
stove dealer. As an alternative, a tile or stone floor is of 
course very suitable. 
 

Safety gaps (minimum gaps): 

During  installation  of  the  stove  it  is  absolutely  essential 
to  observe  the  official  fire  protection  regulations.  Ask 
your district heating inspector about this. 
 
The  following  must  be  maintained  as  the  minimum 
distances  from  flammable  or  temperature-sensitive 
materials  (e.g.  furniture,  wallpaper,  wooden  cladding) 
and from loadbearing walls. (See drawing): 

5 cm from the back wall 

10 cm from the side walls and 

80 cm in the direction of radiation. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 2: Safety gaps

 

 
The  chimney  (fireplace  or  flue)  must  for  example  be 
made of stainless steel or ceramics (glazed internally) so 
that  it  cannot  rot.  This  is  necessary  because  of  the  low 
temperature of flue gases from your pellet stove. 
Standard  trade  flue  tubes  may  be  used  for  the 
connection  to  the  fireplace.  Approved  Flex  steel  flues 
are also suitable. 

 
 
Since excess pressure may build up at the smoke outlet 
because  of  the  way  that  the  pellet  stove  works  with  an 
induced  draught  fan,  all  fume  outlet  pipes  as  far  as  the 
intake  to  the  fireplace  must  be  gas-tight.  It  is  also 
essential  to  ensure  that  the  flue  tube  does  not stick  out 
into  the  open  cross-section  of  the  chimney.  The  use  of 
wall  lagging  is  recommended  for  the  insertion  into  the 
chimney. (See Figure 3). 
With  longer  flue  gas  pipework,  horizontal  sections  and 
constrictions  must  be  avoided  and  specially  insulated 
flue  tubes  should  be  used.  Pipework  rising  in  the 
direction of the chimney is recommended. 

 

 

 

Figure 3:

 

Chimney connection

 

1 = Wall lagging 
2 = Gas-tight pipework 
3 = Underlay plate 
 

External air intake: 

In airtight buildings, whilst the pellet stove is operating, a 
reduction  in  the  oxygen  level  in  the  room  where  the 
stove  is  installed  may  occur,  so  adequate  ventilation 
must be ensured. For this the pellet stove offers you the 
option of operating independently of the air in the room. 
To  do  this,  connect  the  air  intake  elbow  located  on  the 
back  (diameter:  57  mm)  to  a  hose  or  a  similar  suitable 
air  duct.  The  end  of  the  air  duct  must  be  located  in  the 
open  air  or  in  a  well-ventilated  room  within  the  building. 
When  installing  the  pellet  stove  in  combination  with 
controlled residential room ventilation, the end of the air 
intake  duct  must  not  be  connected  to  the  ventilation 
system  in  an  adjacent  room  with  the  air  connection 
system.  To  ensure  sufficient  volume  of  air  intake,  the 
pipe should  not  be  longer than  about  3 m and not have 
too  many  bends.  This  pipe  should  have  a  minimum 
diameter  of  5  cm.  (The  bigger,  the  better).  If  the  pipe 
goes  to  the  open  air,  it  must  end  with  a  downward 

90° 

bend or with wind protection. (See Figure 4). 

 

Summary of Contents for HSP 2.17

Page 1: ...e cold combustion pot it must be cleaned See operating instructions If this is not done there will be more and more clinker Then the device will no longer be able to ignite properly Pellets may pile up in the combustion pot In extreme cases this can reach all the way back to the pellet chute Backfire in the pellet container and smouldering in the pellet tank might possibly result This will destroy...

Page 2: ...ey lock child safe 11 7 Operating the pellet stove 11 7 1 Fuel 11 7 2 Commissioning your pellet stove 12 8 Cleaning and maintenance work 12 8 1 Cleaning the surface 13 8 2 Cleaning the glass panel 13 8 3 Clean combustion chamber function instruction 13 8 4 Cleaning the combustion pot weekly 13 8 5 Cleaning the pellet container annual maintenance 14 8 6 Cleaning the flue gas passes annual maintenan...

Page 3: ... room enters the stove at the bottom of the cladding is heated and flows out again at the top in the area of the slats The proportion of radiant heat is given off by radiation in the area of the viewing window of the combustion chamber door and from the stove s metal surfaces 2 General instructions safety instructions Before commissioning the pellet stove read the entire installation and operating...

Page 4: ...cleaning staff should be informed and instructed regarding the possible unexpected heating up of the stove Placing non heat resistant objects on or near the heating device even when it is cold since it can ignite again by itself is forbidden Do not lay any laundry on the stove to dry Clotheshorses for drying clothes and the like must be positioned at sufficient distance from the heating device fir...

Page 5: ...ecause of the way that the pellet stove works with an induced draught fan all fume outlet pipes as far as the intake to the fireplace must be gas tight It is also essential to ensure that the flue tube does not stick out into the open cross section of the chimney The use of wall lagging is recommended for the insertion into the chimney See Figure 3 With longer flue gas pipework horizontal sections...

Page 6: ...ded into 20 zones is ended after reaching a precisely defined temperature on the flame temperature sensor and the control unit switches to Heating Mode operating status The duration of the Ignition phase may vary If during these time no flame is formed or the required temperature is not reached at the flame temperature sensor flue gas a safety shutdown is initiated Here the rotation speed of the i...

Page 7: ...is in a waiting position Before the stove can switch back from Standby operating status to the Ignition phase operating status two ignition conditions must be fulfilled 1 The room temperature must be at least 1 0ºC below the set target room temperature 2 The flue gas temperature measured with the thermosensor must be lower than 70 C It is only when both these ignition conditions have been fulfille...

Page 8: ...ere it was before the power cut Long power cut duration of the power cut longer than 30 seconds Once the electricity supply is restored the stove switches to Safety shutdown operating status A small amount of flue gas may escape during a power cut 6 Description of operator console keys 6 1 Operator console As can be seen in the figure the display is divided into five areas 6 2 Description of the s...

Page 9: ...n to switch the stove in operation Now the boot process begins with the launch zone 1 Off Menu Start zone 1 08 13 26 C 23 C 6 3 3 Setting target room temperature Procedure By pressing the middle button and you adjust the room temperature By pressing the OK button the set value is stored OK OFF 08 15 28 C 23 C 6 4 Main menu By pressing the right button the standard screen will appear This menu is a...

Page 10: ...e 4 With older stoves a higher value should be set over 3 so as to avoid excess condensation in the fireplace Procedure In the main menu place the cursor on Heating profile Press the right OK key Adjust the value with the two middle keys Then press the right OK key If you would like to quit this menu screen without saving press the left Back key 6 4 4 Desription ECO Mode OK No Yes Main menu ECO Mo...

Page 11: ...onds until Key lock activated is no longer shown on the display 7 Operating the pellet stove The pellet stove may only be heated by adults Make sure that children are never left alone with the pellet stove Do not leave the pellet stove unsupervised for a long period The pellet stove may only be used in accordance with these operating instructions Please observe the safety instructions set out in S...

Page 12: ... move cursor to Operating mode press the right key Select select the desired operating mode with the cursor press the right key Save Tip Only when commissioning place about 30 pellets in the burner This will speed up the ignition process General If the ignition phase could not be successfully run i e no flame generation or the required temperature could not be reached at the flue gas thermosensor ...

Page 13: ...mber the stove has to be switched to Off operating status If the combustion chamber is now cleaned then the Clean combustion chamber error message will thereafter be cleared automatically A precondition for the automatic clearance of this error message is that the combustion chamber door is open for longer than 60 seconds in Off operating status This time is required for cleaning the combustion ch...

Page 14: ...tive grille 1 Tank cover 2 8 6 Cleaning the flue gas passes annual maintenance First pull the stove away from the wall so as to create enough room to work at the back To clean the flue gas passes proceed as follows Disconnect the flue baffle 1 from the guide by lifting it Draw the right cladding 2 down out of the guide and place it down in the ash space Then the flue baffle can be removed and the ...

Page 15: ...15 2x 2x 3B 1 2 3A 3B 3A 3B Figure 8b Tilt out the front part ...

Page 16: ...ition again It is essential to replace defective seals Make sure of the electrical connections on the fan motor and their correct positions Figure 9 Induced draught fan 1 Screw 2 Blower motor 3 Seal 9 Description of the components 9 1 Storage container pellet tank 17 kg of wood pellets can be stored in the storage container This quantity permits constant operation for up to 30 hours 9 2 Screw conv...

Page 17: ... average ignition glow time is depending on pellet quality Figure 12 Electrical components 1 Flame temperature sensor 2 Overheat cutout 3 Bottom temperature sensor 4 Ignition 5 Screw conveyor motor 6 Control unit 7 Backup battery Figure 13 Stainless steel ignition 9 5 Control unit The microprocessor control unit ensures safe automatic operation of the pellet stove The control unit controls the int...

Page 18: ...e and hence the basis of the air volume required for the combustion of the energy level located in the grate Here the ACTUAL flame temperature is compared with the TARGET in combination with the processor regulated control unit and the appropriate combustion air volume required for the combustion of the energy level in the grate is supplied by means of the induced draught fan 9 9 Flue gas thermose...

Page 19: ...mm The flue tube must be connected to the fireplace in accordance with official regulations For questions in connection with this please contact your local chimneysweep Because of the way the pellet stove works with a combustion air fan high pressure is generated at the flue gas outlet and possibly in the fireplace This means that the flue gas pipes must be designed to be gas tight as far as their...

Page 20: ...kg Duration of burn with one charge min max about 10 hrs 30 hrs Permitted fuel Low dust wood pellets to Ö Norm Eco standard M 7135 DIN 51731 EN 14961 2 Diameter 6 mm Length max 30 mm Room heating capacity to Ö Norm M 7521 max 230 m 3 Room heating cap y to DIN 18893 constant heating 250m 3 145m 3 98m 3 Room heating cap y to DIN 18893 timed heating 165m 3 95m 3 65m 3 Electricity supply 230 V 50 Hz E...

Page 21: ...ction has initiated a safety shutdown Dirty heat exchanger Correction Set the heating profile as description Room temperature sensor is on the floor or on the wall hang the sensor free cleaning the flue gas passes Contact the service engineer Error number 5 Cause Flue gas temperature is starting to fall rapidly despite maximum heat output for a long period The following circumstances might lead to...

Page 22: ... not running at the correct rotation speed The following circumstances might lead to this Induced draught fan defective Connection cable from the rotation speed sensor Hallsensor is broken or poor contact in the connector on this connection cable Electricity supply to the fan motor interrupted Correction Contact the service engineer Error number 17 Cause The connection between the central unit and...

Page 23: ...stances might lead to this Too much fuel is being supplied to the burner Flue gas temperature sensor defective Correction Contact the service engineer Error number 23 Cause Flame temperature sensor defective or not connected Correction Contact the service engineer Error number 24 Cause Bottom flame temperature sensor defective or not connected Correction Contact the service engineer Error number 2...

Page 24: ...ctive Replace fuse F3 in the control unit T0 315 A No display showing 1 Loose or defective connection cable between operator console and control unit Check plugs and sockets otherwise call in the service engineer Fire burns with a tall yellow flame wood pellets piling up in the combustion pot and or the viewing panel is excessively sooty 1 The combustion air supply to the combustion pot is blocked...

Page 25: ...ner Flue gas escaping 1 Power cut Ventilate room 2 Flue tubes or chimney fireplace very dirty Clean flue tube or chimney fireplace 12 Type plate Symbol HAAS SOHN OFENTECHNIK GMBH Urstein Nord 67 A 5412 Puch Pellet Kaminofen Typenbezeichnung 713 07 Variante HSP 2 17 Wärmeleistungsbereich 1 8 8 2 kW Nennwärmeleistung 8 0 kW Zugelassener Brennstoff Holzpellets Ø 6mm DINplus ÖNorm M 7135 ENplus A1 Prü...

Page 26: ...gures 21 Replacement parts HSP 2 17 Figures 22 Replacement parts HSP 2 17 32 31 20 15 16 35 10 12 22 38 39 21 32 31 25 36 37 1 8 9 2 41 43 5a 6a 6b 4b 11 26 24 34 23 33 30 28 29 27 23 34 47 4a 4b 46 45 44 43 ...

Page 27: ...20 Draught baffle plate 21 0571207005701 Allen key 6 mm 43 9001700060005 Stand 22 0561008009641 Mains cable 23 0089500990000 Cable screw conveyor motor with capacitor Ignition 350 W 25 0561008005202 OC 24 0571207005840 Induced draught fan 26 0571207005820 Screw conveyor motor 27 0089500880005 Screw conveyor 28 0571207005030 Lower screw conveyor bearing 30 0089000340008 Motor plate 29 0571207007080...

Page 28: ...28 14 Circuit diagram ...

Page 29: ... 9 OC 35 36 Flue gas temperature sensor 37 38 Flame temperature sensor 39 40 Room temperature sensor 41 42 Bottom flame temperature sensor 43 44 Door contact switch 48 50 Flue gas fan rotation speed F1 Fuse T 3 15A ignition induced draught fan screw conveyor motor F2 Fuse T 3 15A reserve F3 Fuse T 0 315A operator console ...

Page 30: ...draught incorrectly carried out repair work or other in particular subsequent changes to the heating appliance or flue gas pipework stove pipe and chimney use of unsuitable fuels incorrect operation overloading the devices see the manufacturer s operating instructions wear on the parts made of iron or fire clay directly exposed to the flames in so far as they are not covered by the guarantee 1a in...

Page 31: ...tion stoves for wood and coal Slow combustion stoves and auxiliary ranges for wood coal and oil Fireplace inserts for wood Accessories for stoves and fireplaces Accessories for central oil supply HAAS SOHN Sales in Germany OFENTECHNIK GMBH HAAS SOHN Ofentechnik GmbH Urstein Nord 67 Zur Dornheck 8 A 5412 Puch D 35764 Sinn Fleisbach Email office haassohn com Email info haassohn com http www haassohn...

Reviews: