applications.  The  dual  wavelength  NDIR  CO2  sensing  procedure  compensates  automatically  for 
ageing effects. The CO2 module is highly resistant to pollution and offers maintenance free operation 
and  outstanding  long  term  stability.  Measured  values  can  be  read  in  „SLOW  mode“  (filtered, 
averaged) or in „FAST mode“ (current values without averaging). SLOW mode has advantages in 
applications like climate control because of filtering short time peaks. As an example exhaled air 
from an employee passing the sensor could affect the climate control negatively with a short response 
time  because  the  control  would  trigger  a  change  of  the  ventilation  based  on  this  one-time 
measurement. On the contrary in „FAST mode“ no software filter is used for calculating the output 
value. This fact adds a noise of typ. ±30ppm which has to be considered in terms of accuracy. Of 
principle  measurement  is  the  measured  value  of  CO

2

  concentration  depends  on  the  value  of  air 

pressure - altitude at the installation site. For this reason, it is suitable for accurate measurement to 
set the altitude of the installation site by TSensor software. 

After power up there is internal check in progress and takes about 20 s. During this time LCD 

display shows (----) instead of CO

2

 concentration value. 

 Parameter setting description is into chapter 

“Regulator setting change

  

at page 11. 

5.4.  Actual regulator preset 

It  is  possible  to  display  actual  regulator  preset  on  its  LCD  display  by 

pressing of „

“  key.  If  „Output  relay  alarm  condition  configuration with 

using  of  Modbus  communication  protocol“  is  active  (see  chapter 

6.1.4

  at 

page 18), then device’s LCD display shows text „bloc“. It means, device’s 
keyboard is disabled for time of remote control (setting change), see chapter 

6.1.5

  at  page  18.  LCD  shows  information  about  Relay1  and  then  Relay2 

setting step by step. Information about Relay1 are indicated with symbol „

“, for Relay2 

with  symbol  „

“  (at  right  top  corner  of  LCD).  It  is  possible  to  edit  parameters  after 

pressing „

SET

“ key and entering of correct password „

PASS

“ – see chapte

Change of “Password 

for setting through keys” (PASS)

 at page 13. Following examples are for Relay1 setting, similarly are 

displayed  values  for  Relay2.  Pressing  of  „

ESC

“  key  ends  this  mode  and  switch  to  actual  value 

displaying, the same occur if more than 20 s is not pressed any key. 

5.4.1. Value assigned to output relay 

None, relay is still off 

Temperature at °C 

Relative humidity 

Computed value – dew point temperature 

CO

2

 concentration 

Far condition 0 

Summary of Contents for AR006711

Page 1: ...CO2 concentration temperature humidity and other calculated humidity variables regulator with RS232 serial output AR006712 AR006711 AR006713 Instruction Manual...

Page 2: ...1 MODBUS RTU 17 6 1 1 Supported functions 17 6 1 2 Jumper 17 6 1 3 Modbus registers of the regulator 17 6 1 4 Far controlling of output relays status 18 6 1 5 Output relay alarm condition configuratio...

Page 3: ...bles if the device is under electric voltage Do not use the instrument without the cover Do not use the instrument if it does not work correctly If the instrument seems not to work correctly have it c...

Page 4: ...l line LCD It is also possible to display both readings with cyclic overwriting in 4 seconds interval Display can be also switched OFF totally On the left LCD side there are placed three LEDs for CO2...

Page 5: ...amatically increase response time to relative humidity change If water condensation occurs for longer time it can cause sensor damage Similar effect can occur under water aerosol conditions The commun...

Page 6: ...6 AR006711 AR006713...

Page 7: ...7 4 Typical application wiring connection of terminals...

Page 8: ...elay for while must be preset condition true before relay close its contact and hysteresis for return to open status For binary inputs if it is preset to HI then output relay is closed when input cont...

Page 9: ...is internal check in progress and takes about 20 s During this time LCD display shows instead of CO2 concentration value Parameter setting description is into chapter Regulator setting change at page...

Page 10: ...en close output relay High limit HI the relay closes when measured value exceeds preset high limit for longer time than preset delay time Relay goes open when measured value decrease under high limit...

Page 11: ...t is possible to enter into edit mode and edit displayed value by pressing SET key Then you are asked for valid password PASS You can edit selected value if right password is entered During value edit...

Page 12: ...u should see message SEL on the top line of LCD and on the bottom line you should see number of Firmware version e g 0404 6 release and keys you are into Extended setting mode now Use and keys to insp...

Page 13: ...On Change of Password for setting through keys PASS This item shows actual password setting It is possible to change it after SET key pressing It is number from range 19999 to 19999 Choice of communic...

Page 14: ...rrent value without averaging FAST mode CO2 zone level indication setup Whole measuring range can be divided into three areas Each active area there is indicated by green yellow or red LED depends on...

Page 15: ...t after SET key pressing show value on LCD don t show value on LCD Show computed value at LCD display This item provides to choice if actual computed value may be displayed at LCD display or not There...

Page 16: ...ty 2 stop bits value assigned to Relay1 and Relay2 none password for setting through keys 0000 display on value shown at first LCD line temperature CO2 by device type value shown at second LCD line re...

Page 17: ...ected the function of jumper is as follows Jumper opened device memory is protected from writing from device side it is only enabled to read measured value writing to memory is disabled no change of s...

Page 18: ...e are stored also in Float format which is not directly compatible with IEEE754 6 1 4 Far controlling of output relays status 2 There is possible to control output relay status open close with using o...

Page 19: ...nable for this time device s keyboard is blocked if key is pressed message BLOC is shown R W Value assigned to output Relay1 by value 0x0045 69 0 Off 1 temperature 2 relative humidity 3 atmospheric pr...

Page 20: ...115200Bd parameters of communication link are 1 start bit eight bit data word LSB first 1 stop bit without parity 6 2 1 Jumper Jumper placed nearby keys is accessible after demounting of four screws i...

Page 21: ...calculate values It is a serious error contact distributor of the device to fix Error 1 measured or calculated value except concentration of CO2 is over upper limit of allowed full scale range There i...

Page 22: ...some wrong setting mismatch This error appears if incorrect writing procedure to device s memory occurred Error 9 inserted password is not valid there is shown for short time message Err9 on LCD disp...

Page 23: ...2A 60 W 62 5 VA EMC EN 61326 1 EN 55011 10 1 2 AR006712 CO2 regulator Concentration of CO2 Accuracy 100 ppm 5 of measuring value at 25 C 77 F and 1013 hPa Range 0 to 10000 ppm Temperature dependence...

Page 24: ...m CO2 C in the range 0 to 50 C 32 to 122 F Long term stability typ 20 ppm year Resolution 1 ppm Measuring temperature and humidity range is limited in accordance with the graph below Response time mea...

Page 25: ...temperature Range 60 to 80 C 76 to 176 F Accuracy 1 5 C 2 7 F at ambient temperature T 25 C 77 F and relative humidity RH 30 for more details see graphs below Absolute humidity Range 0 to 400 g m3 Acc...

Page 26: ...idity and temperature restriction 10 2 Operating conditions Operating temperature and relative humidity electronics AR006712 30 to 80 C 22 to 176 F electronics AR006711 AR006713 measuring end of stem...

Page 27: ...s not allowed to operate the device under conditions other than specified in technical parameters Devices are not designed for locations with chemically aggressive environment Temperature and humidity...

Page 28: ...ervice is provided by distributor For contact see warranty certificate You can use discussion forum at web address http www guilcor com 11 Appendix A Connection of external power relay Coil data chart...

Reviews: