5.5.  Regulator setting change 

5.5.1. Setting with PC and TSensor software 

User’s  software 

TSensor 

provides 

setting  of  all  regulator  parameters. 

The  program  is 

available free to download at web page 

www.

guilcor

.com

. Run the TSensor

 

program and follow

the  program  instructions.  Regulator  includes  hardware  write  protection  of  internal  setting  ,  new 
setting is possible to write only while: 

1. during write period press „

SET

“ key – do requested setting in TSensor software, press „

SET

key on regulator and keep it down, then click on the button „

Save Changes

“ into TSensor

software and after end of write release „

SET

“ key, or

2. jumper placed nearby keys is closed (jumper is accessible after demounting of four screws in

the  corners  of  the  box  and  removing  the  lid  ).  This  jumper  is  suitable  e.g.  until  device
adjustment  is  in  process  and  regulator  is  placed  into  calibration  box  and  keys  are  not
accessible.  Don’t  forget  to  remove  (open)  jumper  after  procedure  finish  (restore  write
protection)

TSensor software supports to make the adjustment of the regulator too. This procedure is described 

at file „

Calibration manual.pdf

“  which is installed commonly with the software. 

5.5.2. Setting with using regulator keys 

If „Actual regulator preset” is displayed (see chapter 

“Actual regulator preset”

 at page 9), it is 

possible to enter into edit mode and edit displayed value by pressing „

SET

“  key. Then you are asked 

for valid password (PASS). You can edit selected value if right password is entered. During value 
editing there is range check executed and edited value is still compared with limits for corresponding 
value (range). If inserted value is higher or lower then edited number is automatically changed to its 
maximum / minimum value – for possible range see chapter „Technical parameters“ at page 23. Value 
can be changed with using „

“ and „

“ keys. Edited value is switched in “round” -9, -8, -7, …-2, -1, 

0, 1, 2, …8, 9. To edit next number digit press „

SET

“ key, for moving back to previous digit press 

ESC

“ key. Edited value is stored by next „

SET

“ key pressing. It is possible to cancel editing by 

pressing „

ESC

“ key if necessary. If valid password is once inserted right, then there is possible to edit 

next items without asking for password insertion again, till “Actual regulator preset” is left (till actual 
measured values are shown). With new entering  into edit mode it is  necessary to  enter Password 
again. Default password setting is preset from manufacturer to 0000, password change is possible 
into „Extended setting”. During edit mode regulator still works and changes are valid immediately 
after its storing – it is NOT necessary to restart regulator. 

5.5.3. Setting with using of Modbus communication protocol 

See chapter 

Output relay alarm condition configuration with using of Modbus communication 

protocol 

2

 “ at page 18. 

Summary of Contents for AR006711

Page 1: ...CO2 concentration temperature humidity and other calculated humidity variables regulator with RS232 serial output AR006712 AR006711 AR006713 Instruction Manual...

Page 2: ...1 MODBUS RTU 17 6 1 1 Supported functions 17 6 1 2 Jumper 17 6 1 3 Modbus registers of the regulator 17 6 1 4 Far controlling of output relays status 18 6 1 5 Output relay alarm condition configuratio...

Page 3: ...bles if the device is under electric voltage Do not use the instrument without the cover Do not use the instrument if it does not work correctly If the instrument seems not to work correctly have it c...

Page 4: ...l line LCD It is also possible to display both readings with cyclic overwriting in 4 seconds interval Display can be also switched OFF totally On the left LCD side there are placed three LEDs for CO2...

Page 5: ...amatically increase response time to relative humidity change If water condensation occurs for longer time it can cause sensor damage Similar effect can occur under water aerosol conditions The commun...

Page 6: ...6 AR006711 AR006713...

Page 7: ...7 4 Typical application wiring connection of terminals...

Page 8: ...elay for while must be preset condition true before relay close its contact and hysteresis for return to open status For binary inputs if it is preset to HI then output relay is closed when input cont...

Page 9: ...is internal check in progress and takes about 20 s During this time LCD display shows instead of CO2 concentration value Parameter setting description is into chapter Regulator setting change at page...

Page 10: ...en close output relay High limit HI the relay closes when measured value exceeds preset high limit for longer time than preset delay time Relay goes open when measured value decrease under high limit...

Page 11: ...t is possible to enter into edit mode and edit displayed value by pressing SET key Then you are asked for valid password PASS You can edit selected value if right password is entered During value edit...

Page 12: ...u should see message SEL on the top line of LCD and on the bottom line you should see number of Firmware version e g 0404 6 release and keys you are into Extended setting mode now Use and keys to insp...

Page 13: ...On Change of Password for setting through keys PASS This item shows actual password setting It is possible to change it after SET key pressing It is number from range 19999 to 19999 Choice of communic...

Page 14: ...rrent value without averaging FAST mode CO2 zone level indication setup Whole measuring range can be divided into three areas Each active area there is indicated by green yellow or red LED depends on...

Page 15: ...t after SET key pressing show value on LCD don t show value on LCD Show computed value at LCD display This item provides to choice if actual computed value may be displayed at LCD display or not There...

Page 16: ...ty 2 stop bits value assigned to Relay1 and Relay2 none password for setting through keys 0000 display on value shown at first LCD line temperature CO2 by device type value shown at second LCD line re...

Page 17: ...ected the function of jumper is as follows Jumper opened device memory is protected from writing from device side it is only enabled to read measured value writing to memory is disabled no change of s...

Page 18: ...e are stored also in Float format which is not directly compatible with IEEE754 6 1 4 Far controlling of output relays status 2 There is possible to control output relay status open close with using o...

Page 19: ...nable for this time device s keyboard is blocked if key is pressed message BLOC is shown R W Value assigned to output Relay1 by value 0x0045 69 0 Off 1 temperature 2 relative humidity 3 atmospheric pr...

Page 20: ...115200Bd parameters of communication link are 1 start bit eight bit data word LSB first 1 stop bit without parity 6 2 1 Jumper Jumper placed nearby keys is accessible after demounting of four screws i...

Page 21: ...calculate values It is a serious error contact distributor of the device to fix Error 1 measured or calculated value except concentration of CO2 is over upper limit of allowed full scale range There i...

Page 22: ...some wrong setting mismatch This error appears if incorrect writing procedure to device s memory occurred Error 9 inserted password is not valid there is shown for short time message Err9 on LCD disp...

Page 23: ...2A 60 W 62 5 VA EMC EN 61326 1 EN 55011 10 1 2 AR006712 CO2 regulator Concentration of CO2 Accuracy 100 ppm 5 of measuring value at 25 C 77 F and 1013 hPa Range 0 to 10000 ppm Temperature dependence...

Page 24: ...m CO2 C in the range 0 to 50 C 32 to 122 F Long term stability typ 20 ppm year Resolution 1 ppm Measuring temperature and humidity range is limited in accordance with the graph below Response time mea...

Page 25: ...temperature Range 60 to 80 C 76 to 176 F Accuracy 1 5 C 2 7 F at ambient temperature T 25 C 77 F and relative humidity RH 30 for more details see graphs below Absolute humidity Range 0 to 400 g m3 Acc...

Page 26: ...idity and temperature restriction 10 2 Operating conditions Operating temperature and relative humidity electronics AR006712 30 to 80 C 22 to 176 F electronics AR006711 AR006713 measuring end of stem...

Page 27: ...s not allowed to operate the device under conditions other than specified in technical parameters Devices are not designed for locations with chemically aggressive environment Temperature and humidity...

Page 28: ...ervice is provided by distributor For contact see warranty certificate You can use discussion forum at web address http www guilcor com 11 Appendix A Connection of external power relay Coil data chart...

Reviews: