12
5.6. Extended setting mode
During regulator operation it is possible to change parameters available through “Actual regulator
at page 9). Rest of regulator parameters are available through “Extended
In this mode regulator does NOT communicate, does NOT do any measurements
and does NOT service output relays. To leave this mode press „ESC“ key and open jumper
nearby keys. To enter into Extended setting mode do following steps
:
1. disconnect power supply
2. demount four screws in the corners of the box and remove the lid
3. closed jumper placed nearby keys
4. press „
“ and „
“ keys together and keep them down
5. connect power supply to regulator – you should see message „
SEL
“ on the top line of LCD and
on the bottom line you should see number of Firmware version (e.g. 0404)
6. release „
“ and „
“ keys – you are into “Extended setting mode” now
Use „
▲
“ and „
▼
“ keys to inspect each items. If you want to change some shown item then press
„
SET
“ key, item starts blink. Now you can edit setting with using „
▲
“ and „
▼
“ keys. To store preset
value press „
SET
“ key. Press „
ESC
“ key to leave editing (changing) without save – last stored value
is kept.
Acoustic alarm assign to Relay1
acoustic indication of Relay1 is OFF
close of Relay1 contact starts acoustic indication
Acoustic alarm assign to Relay2
acoustic indication of Relay2 is OFF
close of Relay2 contact starts acoustic indication
Acoustic alarm deactivation
activated acoustic alarm is possible to
deactivate by pressing „
ESC
“ key
acoustic alarm is still activated for all time and
it is impossible to deactivate it