For communication with device  which measure more than one value, there is necessary to add at 

the  end  of  command,  number  of  communication  channel,  where  the  measured  value  is  mapped. 
Command for value reading is 

#AAx(CRC) CR

, where 

AA

 is device address and 

x

 is number of 

communication channel by next table: 

Measured value 

Number of communication channel 

temperature 

relative humidity 

computed value 

barometric pressure (CO

2

 concentration) 

status word (described below)* 

Relay1 status [0/1] 

Relay2 status [0/1] 

* Status word: 16b value return, bite description:

Bit0 

0/1 

jumper open/closed 

Bit1 

-

unused

Bit2 

always 0 

Bit3 

0/1 

Relay1 open/closed 

Bit4 

0/1 

Relay2 open/closed 

Bit5 

0/1 

internal acoustic alarm status 

Bit6 -15  - 

unused 

7. Error States of the device

Device  continuously  checks  its  state  during  operation.  In  case  error  is  found  LCD  displays

corresponding error code: 

Error 0 

- first  line  of  LCD  displays  „Err0“.  Check  sum  error  of  stored  setting  inside  device’s 

memory.  This  error  appears  if  incorrect  writing  procedure  to  device’s  memory  occurred  or  if 
damage of calibration data appeared. At this state device does not measure and calculate values. It 
is a serious error, contact distributor of the device to fix. 

Error 1 - 

measured or calculated value (except concentration of CO

2

) is over upper limit of allowed 

full scale range. There is a reading „Err1“ on LCD display. Value read from the device is +999.9. 
This state appears in case of: 

Measured temperature is higher than approximately 600°C (i.e. high non-measurable resistance
of temperature sensor, probably opened circuit).

Relative humidity is higher than 100%, i.e. damaged humidity sensor, or humidity calculation
of humidity is not possible (due to error during temperature measurement).

Computed  value  –  calculation  of  the  value  is  not  possible  (error  during  measurement  of
temperature or relative humidity or value is over range).

The value of CO

2

 

concentration 9999 ppm is correct value! 

Error 2 - 

there is a reading „Err2“ on LCD display. Measured or calculated value is below lower 

limit of allowed full scale range or CO

2

 concentration measurement error occurred. Value read 

from the device is -999.9. This state appears in case of: 

Measured temperature is lower than approximately -210°C (i.e. low resistance of temperature
sensor, probably short circuit).

Relative humidity is lower than 0%, i.e. damaged sensor for measurement of relative humidity,
or calculation of humidity is not possible (due to error during temperature measurement).

Summary of Contents for AR006711

Page 1: ...CO2 concentration temperature humidity and other calculated humidity variables regulator with RS232 serial output AR006712 AR006711 AR006713 Instruction Manual...

Page 2: ...1 MODBUS RTU 17 6 1 1 Supported functions 17 6 1 2 Jumper 17 6 1 3 Modbus registers of the regulator 17 6 1 4 Far controlling of output relays status 18 6 1 5 Output relay alarm condition configuratio...

Page 3: ...bles if the device is under electric voltage Do not use the instrument without the cover Do not use the instrument if it does not work correctly If the instrument seems not to work correctly have it c...

Page 4: ...l line LCD It is also possible to display both readings with cyclic overwriting in 4 seconds interval Display can be also switched OFF totally On the left LCD side there are placed three LEDs for CO2...

Page 5: ...amatically increase response time to relative humidity change If water condensation occurs for longer time it can cause sensor damage Similar effect can occur under water aerosol conditions The commun...

Page 6: ...6 AR006711 AR006713...

Page 7: ...7 4 Typical application wiring connection of terminals...

Page 8: ...elay for while must be preset condition true before relay close its contact and hysteresis for return to open status For binary inputs if it is preset to HI then output relay is closed when input cont...

Page 9: ...is internal check in progress and takes about 20 s During this time LCD display shows instead of CO2 concentration value Parameter setting description is into chapter Regulator setting change at page...

Page 10: ...en close output relay High limit HI the relay closes when measured value exceeds preset high limit for longer time than preset delay time Relay goes open when measured value decrease under high limit...

Page 11: ...t is possible to enter into edit mode and edit displayed value by pressing SET key Then you are asked for valid password PASS You can edit selected value if right password is entered During value edit...

Page 12: ...u should see message SEL on the top line of LCD and on the bottom line you should see number of Firmware version e g 0404 6 release and keys you are into Extended setting mode now Use and keys to insp...

Page 13: ...On Change of Password for setting through keys PASS This item shows actual password setting It is possible to change it after SET key pressing It is number from range 19999 to 19999 Choice of communic...

Page 14: ...rrent value without averaging FAST mode CO2 zone level indication setup Whole measuring range can be divided into three areas Each active area there is indicated by green yellow or red LED depends on...

Page 15: ...t after SET key pressing show value on LCD don t show value on LCD Show computed value at LCD display This item provides to choice if actual computed value may be displayed at LCD display or not There...

Page 16: ...ty 2 stop bits value assigned to Relay1 and Relay2 none password for setting through keys 0000 display on value shown at first LCD line temperature CO2 by device type value shown at second LCD line re...

Page 17: ...ected the function of jumper is as follows Jumper opened device memory is protected from writing from device side it is only enabled to read measured value writing to memory is disabled no change of s...

Page 18: ...e are stored also in Float format which is not directly compatible with IEEE754 6 1 4 Far controlling of output relays status 2 There is possible to control output relay status open close with using o...

Page 19: ...nable for this time device s keyboard is blocked if key is pressed message BLOC is shown R W Value assigned to output Relay1 by value 0x0045 69 0 Off 1 temperature 2 relative humidity 3 atmospheric pr...

Page 20: ...115200Bd parameters of communication link are 1 start bit eight bit data word LSB first 1 stop bit without parity 6 2 1 Jumper Jumper placed nearby keys is accessible after demounting of four screws i...

Page 21: ...calculate values It is a serious error contact distributor of the device to fix Error 1 measured or calculated value except concentration of CO2 is over upper limit of allowed full scale range There i...

Page 22: ...some wrong setting mismatch This error appears if incorrect writing procedure to device s memory occurred Error 9 inserted password is not valid there is shown for short time message Err9 on LCD disp...

Page 23: ...2A 60 W 62 5 VA EMC EN 61326 1 EN 55011 10 1 2 AR006712 CO2 regulator Concentration of CO2 Accuracy 100 ppm 5 of measuring value at 25 C 77 F and 1013 hPa Range 0 to 10000 ppm Temperature dependence...

Page 24: ...m CO2 C in the range 0 to 50 C 32 to 122 F Long term stability typ 20 ppm year Resolution 1 ppm Measuring temperature and humidity range is limited in accordance with the graph below Response time mea...

Page 25: ...temperature Range 60 to 80 C 76 to 176 F Accuracy 1 5 C 2 7 F at ambient temperature T 25 C 77 F and relative humidity RH 30 for more details see graphs below Absolute humidity Range 0 to 400 g m3 Acc...

Page 26: ...idity and temperature restriction 10 2 Operating conditions Operating temperature and relative humidity electronics AR006712 30 to 80 C 22 to 176 F electronics AR006711 AR006713 measuring end of stem...

Page 27: ...s not allowed to operate the device under conditions other than specified in technical parameters Devices are not designed for locations with chemically aggressive environment Temperature and humidity...

Page 28: ...ervice is provided by distributor For contact see warranty certificate You can use discussion forum at web address http www guilcor com 11 Appendix A Connection of external power relay Coil data chart...

Reviews: