24
Address [DEC] Address [HEX]
Value
Type
39970
0x9C22
1st two digits from serial number
BCD
39971
0x9C23
2nd two digits from serial number
BCD
39972
0x9C24
3rd two digits from serial number
BCD
39973
0x9C25
4th two digits from serial number
BCD
39974
0x9C26
Device type
uInt
39975 – 39978 0x9C27 – 0x09C2A Actual measured value on channel
Int*10
39980 – 39983 0x9C2C – 0x9C2F Unit on the channel
Ascii
39985 – 39988 0x9C31 – 0x9C34 Channel alarm state
uInt
39990 – 39999 0x9C36 – 0x9C3F Unused
n/a
40000
0x9C40
Channel 1 temperature
Int*10
40001
0x9C41
Channel 1 alarm status
Ascii
40002
0x9C42
Channel 1 upper limit
Int*10
40003
0x9C43
Channel 1 lower limit
Int*10
40004
0x9C44
Channel 1 hysteresis
Int*10
40005
0x9C45
Channel 1 delay
uInt
40006
0x9C46
Channel 2 temperature
Int*10
40007
0x9C47
Channel 2 alarm status
Ascii
40008
0x9C48
Channel 2 upper limit
Int*10
40009
0x9C49
Channel 2 lower limit
Int*10
40010
0x9C4A
Channel 2 hysteresis
Int*10
40011
0x9C4B
Channel 2 delay
uInt
40012
0x9C4C
Channel 3 temperature
Int*10
40013
0x9C4D
Channel 3 alarm status
Ascii
40014
0x9C4E
Channel 3 upper limit
Int*10
40015
0x9C4F
Channel 3 lower limit
Int*10
40016
0x9C50
Channel 3 hysteresis
Int*10
40017
0x9C51
Channel 3 delay
uInt
40018
0x9C52
Channel 4 temperature
Int*10
40019
0x9C53
Channel 4 alarm status
Ascii
40020
0x9C54
Channel 4 upper limit
Int*10
40021
0x9C55
Channel 4 lower limit
Int*10
40022
0x9C56
Channel 4 hysteresis
Int*10
40023
0x9C57
Channel 4 delay
uInt
Description:
Int*10
registry is in format integer*10 – 16 bits
uInt
registry range is 0-65535
Ascii
character
BCD
registry is coded as BCD
n/a
item is not defined, should be read
Possible alarm states:
no
no alarm
lo
value is lower than set limit
hi
value is higher than set limit