vt100
enters cmd group "vt100"
vt100 echo set {OFF=0|ON=1}
sets console echo state
vt100 echo show
show s console echo state
vt100 numeric set {OFF=0|ON=1}
sets numeric mode
vt100 numeric show
show s numeric mode state
vt100 reset
resets terminal
Notes
1. Legacy - The command has been replaced by a newer version
2. Command can be entered on any level
3. The output may show 2 lines - the 1st line shows the actual state, the 2nd line the
status after reboot
4. The output may show several lines
5. Please see the
Energy Sensor Table
for the right energy index
6. Please see the
External Type and External Sensor Field Tables
for the correct
sensor index
Energy Sensor Table "{energy_sensor}"
Index
Description
Unit
0
Forward Active Energy
Wh
1
Power Active
W
2
Voltage
V
3
Current
A
4
Frequency
0.01 hz
5
Power Factor
0.001
6
Power Angle
0.1 degree
7
Power Apparent
VA
8
Power Reactive
VAR
9
Forward Active Energy Resettable
Wh
10
Forward Reactive Energy
VARh
11
Forward Reactive Energy Resettable
VARh
12
Reset Time - sec. since last Energy Counter Reset
s
13
Reverse Active Energy
Wh
14
Reverse Reactive Energy
VARh
15
Reverse Active Energy Resettable
Wh
16
Reverse Reactive Energy Resettable
VARh
17
Absolute Active Energy
Wh
18
Absolute Reactive Energy
VARh
19
Absolute Active Energy Resettable
Wh
20
Absolute Reactive Energy Resettable
VARh
External Sensor Type Table "{sen_type}"
Constants "{7x01=0|7x04=0|7x02=1|7x05=1|7x06=2}"
Index
Description
Products
0
Temperature
7001, 7101, 7201
0
Temperature
7004, 7104, 7204
1
Temperature, Humidity
7002, 7102, 7202
1
Temperature, Humidity
7005, 7105, 7205
2
Temperature, Humidity, Air Pressure
7006, 7106, 7206