Device MIB 1104
Below is a table of all device-specific OID 's which can be accessed via SNMP. In the
numerical representation of the OID the prefix " 1.3.6.1.4.1.28507 " (Gude Enterprise
OID) was omitted at each entry in the table to preserve space. The example for a com-
plete OID would be "1.3.6.1.4.1.28507.68.1.1.1.1". A distinction is made in SNMP OID 's
in between tables and scalars. OID scalar have the extension ".0" and only specify a
value. In SNMP tables the "x" is replaced by an index (1 or greater) to address a value
from the table.
Name
OID
Type
Acc.
Description
epc1104TrapCtrl
.68.1.1.1.1.0
Integer32
RW
0 = off 1 = Ver. 1 2 = Ver. 2c 3 = Ver. 3
epc1104TrapIPIndex
.68.1.1.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each receiver slot.
epc1104TrapAddr
.68.1.1.1.2.1.2.x
OCTETS
RW
DNS name or IP address specifying one Trap receiver slot. A port can
optionally be specified: 'name:port' An empty string disables this slot.
epc1104portNumber
.68.1.3.1.1.0
Integer32
RO
The number of Relay Ports
epc1104PortIndex
.68.1.3.1.2.1.1.x
Integer32
RO
A unique value, greater than zero, for each Relay Port.
epc1104PortName
.68.1.3.1.2.1.2.x
OCTETS
RW
A textual string containing name of a Relay Port.
epc1104PortState
.68.1.3.1.2.1.3.x
INTEGER
RW
current state a Relay Port
epc1104PortSw itchCount
.68.1.3.1.2.1.4.x
Integer32
RO
The total number of sw itch actions ocurred on a Relay Port. Does not
count sw itch commands w hich w ill not sw itch the ralay state, so just
real relay sw itches are displayed here.
epc1104PortStartupMode
.68.1.3.1.2.1.5.x
INTEGER
RW
set Mode of startup sequence (off, on , remember last state)
epc1104PortStartupDelay
.68.1.3.1.2.1.6.x
Integer32
RW
Delay in sec for startup action
epc1104PortRepow erTime
.68.1.3.1.2.1.7.x
Integer32
RW
Delay in sec for repow er port after sw itching off
epc1104PortResetDuration
.68.1.3.1.2.1.8.x
Integer32
RW
Delay in sec for turning Port on again after Reset action
epc1104NTPTimeValid
.68.1.5.15.1.0
INTEGER
RO
Show if valid Time is received
epc1104NTPUnixTime
.68.1.5.15.2.0
Unsigned32
RO
show received NTP time as unixtime (secs since 1 January 1970)
epc1104NTPLastValidTimestamp
.68.1.5.15.3.0
Unsigned32
RO
show seconds since last valid NTP timestamp received
epc1104SensorIndex
.68.1.6.1.1.1.x
Integer32
RO
None
epc1104TempSensor
.68.1.6.1.1.2.x
Integer32
RO
actual temperature
epc1104HygroSensor
.68.1.6.1.1.3.x
Integer32
RO
actual humidity
epc1104InputSensor
.68.1.6.1.1.4.x
INTEGER
RO
logical state of input sensor
epc1104AirPressure
.68.1.6.1.1.5.x
Integer32
RO
actual air pressure
epc1104Dew Point
.68.1.6.1.1.6.x
Integer32
RO
dew point for actual temperature and humidity
epc1104Dew PointDiff
.68.1.6.1.1.7.x
Integer32
RO
difference betw een dew point and actual temperature (Temp -
Summary of Contents for Expert Power Control 1104
Page 2: ...2 Expert Power Control 1104 1105 2022 GUDESystems GmbH...
Page 5: ...Device Description...
Page 12: ...Operating...
Page 22: ...Configuration...
Page 49: ...Specifications...
Page 95: ...Support...