80
Expert Net Control 2304
© 2022 GUDE Systems GmbH
Specifications
and phase start at zero):
Line: Line * 0x120 + Phase * 0x60 + Offset * 2
Port: Port * 0x120 + Phase * 0x60 + Offset * 2
For devices with only one phase, the phase is set to zero in the formula.
Examples:
"Power Active" for 1st line sensor and 3rd phase: 0x400 + 0 * 0x120 + 2 * 0x60 + 1 * 2 =
0x4C2
"Voltage" for 2nd line sensor and single phase device: 0x400 + 1 * 0x120 + 2 * 2 =
0x524
"Power Angle" for 4th port sensor and single phase device: 3 * 0x120 + 6 * 2 =
0x3d6c
Offset
Sensor Field
Unit
0
Absolute Active Energy
Wh
1
Power Active
W
2
Voltage
V
3
Current
mA
4
Frequency
0.01 hz
5
Power Factor
0.001
6
Power Angle
0.1 degree
7
Power Apparent
VA
8
Power Reactive
VAR
9
Absolute Active Energy Resettable
Wh
10
Absolute Reactive Energy
VARh
11
Absolute Reactive Energy Resettable
VARh
12
Reset Time - sec. since last Energy Counter Reset
s
13
Forward Active Energy
Wh
14
Forward Reactive Energy
VARh
15
Forward Active Energy Resettable
Wh
16
Forward Reactive Energy Resettable
VARh
17
Reverse Active Energy
Wh
18
Reverse Reactive Energy
VARh
19
Reverse Active Energy Resettable
Wh
20
Reverse Reactive Energy Resettable
VARh
21
Residual Current Type A
mA
22
Neutral Current
mA
Whether the measured values "Residual Current" and "Neutral Current" are suppor-
ted depends on the respective device model. For measured values such as "Neutral Cur-
rent", which are independent of the phase, the same value is returned for all phases.
DC Energy Sensors:
With the EPC 8291 / 8290 devices, the voltage and current of the individual banks and
Summary of Contents for Expert Net Control 2304
Page 1: ...Manual Expert Net Control 2304 2022 GUDE Systems GmbH Manual Ver 1 0 1 from Firmware Ver 1 0 ...
Page 2: ...2 Expert Net Control 2304 2022 GUDESystems GmbH ...
Page 5: ...Device Description ...
Page 12: ...Operating ...
Page 23: ...Configuration ...
Page 52: ...Specifications ...
Page 87: ...Support ...